Specification Sheet

388
MODEL TUB-HT
TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER
FOR HEAT AND SMOKE REMOVAL
1 year fan housing warranty, 1 year motor warranty
MODEL OVERVIEW
Model TUB-HT has been designed and tested for emergency heat and smoke removal. This design
also lends itself to everyday nonemergency high capacity industrial and commercial roof exhaust
applications. Model TUB-HT successfully passed heat test of 1000°F for fteen (15) minutes, and
500°F for over four (4) hours by an independent testing agency. Model TUB-HT exceeds I.R.I (Industrial
Risk Insurers) guidelines and is UL-793 Listed as “Power Ventilator for Smoke Control Systems.”
The heavy-gauge design allows for years of standard commercial use and the dependability required
in a re emergency. The upblast conguration exhausts heat and smoke high above the roof line aiding
in the access and capabilities of re ghters. Unlike complete design dependence on gravity vents
which are sometimes limited by air temperature and wind velocity, the TUB-HT in conjunction with
gravity vents, will more effectively remove smoke, hot air, and gases when used in a properly designed
system. In the event of electrical failure, the 165°F fusible link will activate the spring assisted damper
doors to provide gravity ventilation. Fan CFM, sizing and location for both exhaust and supply air are
an important part of the overall heat and smoke venting building design needs. Refer to I.R.I., NFPA
(National Fire Protection Association), and local re codes for help in proper system design. Final
approval for the complete system design should be authorized by the local authority having jurisdiction.
Fan selections are available in 24, 30, 36, 42, 48, 54 and 60 inch sizes. Horsepower and CFM range
to 57,000 CFM and 15HP. Units are tested in accordance with AMCA Standard 301 (sound) and AMCA
210 (air) in an AMCA certied laboratory. Every unit is completely assembled and factory tested for
quality assurance prior to shipment.
MODEL FEATURES
Exhaust air up to 57,000 CFM in static pressure applications up to 3/4” w.g.
Motor and drives are located outside of the exhaust airstream
Designed and tested for emergency heat and smoke removal
Successfully passed heat test of 1000°F for 15 minutes and 500°F for
over 4 hours
Belt drives permit easy performance adjustments when needed
UL 793 Listed as Power Ventilator for Smoke Control Systems
All specications are subject to change without notice unless approved in submittal by S&P USA.
GC_TUB-HT_1012 October 2012