General Catalog Air Movement Solutions North American Division April 2015 Updated April 2015 • Residential • Commercial • Industrial • Energy Recovery 1
S&P in the World At present, S&P is a company that is established and recognized all over the world with its own subsidiaries in Spain, Portugal, France, Great Britain, Holland, Belgium, Germany, Italy, Latvia, Austria, Mexico, the United States, Canada, Romania and Australia; with a network of exclusive, independent distributors in most of the countries of the rest of the world, and an expansive project to continue its growth in the Asian market.
S&P: A Global Strategy - A Local Policy S&P was founded in the locality of Ripoll (Spain) in 1951 by the engineers Eduard Soler and Josep Palau. From the beginning they had the clear vision that the future would depend on the expansion abroad, at first towards Europe, then to continue in the rest of the world markets.
Customer service: In a market as competitive as the current one it is simply not enough to produce excellent quality. A company should offer products and a wide range of services for its customers and consultants. At S&P this principle is very clear.
x TR See Warranty Statement on Page 9 x SDB/DB x STXB/TXB STXD/TXD x x x Airflow Exhaust x x x x x x x x x x x x x x x x x x x Supply x x x x x x x x Grease/Restaurant (UL762) Spark Resistant Contaminated Air General/Clean Air Smoke Control (UL) x x x x x x x x x x x x x x x x x x x x x x x x Centrifugal Roof and Sidewall Fans x x x x Energy Recovery Ventilators (ERV) x x x x x x Residential/Light Commercial High Temp above 200
See Warranty Statement on Page 9 7 Ceiling x x x TUB-HT x UBB/UBX TUB x UBSRD-HT/HT-1 UBRD x x UBS UBSRD x x x x x x x ARE/ARS x x x x HREB-C/HRED-C x x x x x x x x x x x x Exhaust HRSB/HRSD x WA x x x CTB x x x x CFD G/DD/DF x SQD/eSQD Hanging x Wall LC/L2/L3 x x Floor/Base SQB x KSF Roof Curb CSF/LSF Model Supply x x x x x x x x x x x Grease/Restaurant (UL762) Spark Resistant Contaminated Air General/Clean Air x x Centri
x x x x x x x x x x CM CM-RHUL CM-HT RCXII BGH RLX x x x x x DA Roof Curb TDD Floor/Base x Hanging TDB Model Ceiling x x x Exhaust x x x x x x x x x Supply x x x x x x x x x General/Clean Air Spark Resistant Contaminated Air x x x x x x x x Utility Sets x x Inline Tubeaxial x Grease/Restaurant (UL762) x x x Gravity Vents Intake/Relief x x x x x x Smoke Control (UL) x High Temp above 200° F x x x Belt x x x x x x Direct Wall
Limited Warranty S&P USA (Manufacturer) 6393 Powers Avenue, Jacksonville, Florida 32217 (USA), warrants equipment of its manufacture to be free from defects in design, materials and workmanship (exclusive of abrasion, corrosion or erosion) for one (1), two (2) or five (5) year(s) as noted from the date of shipment to the original purchaser or the date of notification of readiness to ship. Motor warranty is one (1) or three (3) year(s) as noted.
Product Catalog Index Residential/Light Commercial Product Range MODEL TD-MIXVENT MODEL PV MODEL TD-SILENT MODEL SWF 23 18 14 MODEL FF/FFC MODEL PC, PCD, & PCLP 41 34 27 Energy & Heat Recovery Ventilators Centrifugal Roof and Sidewall MODEL TR (ERV) MODEL LPD DIRECT DRIVE MODELS MODEL TXD 82 52 MODEL RED 189 MODEL eRED 92 86 MODEL TRC (Light Commercial ERV) 52 MODEL CWD MODEL STXD 142 197 MODEL SDBD MODEL CRT (Outdoor Cabinet with Cores) 102 70 BELT DRIVE MODELS MODEL SDB MODEL
Product Catalog Index Centrifugal Filtered Supply BELT DRIVE MODELS MODEL KSF MODEL CSF 203 MODEL LSF 214 214 Centrifugal Inline DIRECT DRIVE MODELS MODEL SQD/eSQD BELT DRIVE MODELS MODEL SQB 255 MODEL CFD 231 267 MODEL CTB 277 Propeller Sidewall Fans (Exhaust or Supply) DIRECT DRIVE MODELS LOW PRESSURE MODEL GED/GSD DIRECT DRIVE MODELS MEDIUM PRESSURE MODEL DFE/DFS 318 318 DIRECT DRIVE MODELS HIGH PRESSURE MODEL DDE/DDS 318 MODEL WA 337 BELT DRIVE MODELS LOW PRESSURE BELT DRIVE MODELS
Product Catalog Index Propeller Roof Ventilators (Exhaust or Supply) DIRECT DRIVE MODELS MODEL ARE/ARS 357 MODEL HRED-C (EXHAUST) 349 MODEL HRSD (SUPPLY) 340 MODEL UBX (EXHAUST) 371 SPECIAL APPLICATION MODELS MODEL UBSRD-HT/HT1 (EXHAUST, LIGHT DUTY, REMOTE DRIVE) 367 MODEL TUB-HT (EXHAUST, HEAVY DUTY, REMOTE DRIVE) 388 BELT DRIVE MODELS MODEL HREB-C (EXHAUST) 349 MODEL HRSB (SUPPLY) 340 MODEL UBS (EXHAUST, LIGHT DUTY) 360 MODEL UBSRD (EXHAUST, LIGHT DUTY, REMOTE DRIVE) 364 MODEL UBB (EXHAUST,
Product Catalog Index Inline Tubeaxial DIRECT DRIVE MODELS MODEL TDD BELT DRIVE MODELS MODEL TDB 419 392 MODEL DA 426 Utility Sets (Belt Drive) MODEL CM (HEAVY DUTY) 429 Gravity Vents Intake/Relief MODEL RCXII MODEL BGH 456 452 MODEL RCXII-SF MODEL RLX 452 464 13
MODEL TD-MIXVENT INLINE MIXED FLOW DUCT FAN MODEL FEATURES • Exhaust air up to 2,630 CFM with static pressure capabilities to 1” w.g.
MODEL TD-MIXVENT INLINE MIXED FLOW DUCT FAN CONSTRUCTION/SPECIFICATION CHECKLIST Construction The TD-MIXVENT models 100, 100x, 125, 150 and 200 are manufactured in tough reinforced plastic, models 250 and 315, 355 and 400 have a metal casing and are finished in a tough epoxypolyester paint coating. The TD fan duct connection flanges are manufactured from reinforced plastic, except for models 200, 200, 250, 315, 355 and 400 which are constructed from epoxy-polyester coated metal.
MODEL TD-MIXVENT INLINE MIXED FLOW DUCT FAN PERFORMANCE/DIMENSIONS Dimensions (inches/mm) Models 100 - 315 Model X 5 15/16 TD-100 7 3/8 TD-100x TD-125 TD-150 Model TD-355 TD-400 B 377 16 407 14 TD-315 9 3/8 9 4/5 C 17 11/16 238 19 3/8 249 188 303 10 3/16 11 492 8 5/6 10 1/2 5/8 295 233 356 302 15 3/16 386 17 11/16 450 E 16 7/9 224 19 1/6 267 C 3 3/4 138 6 15/16 4 1/2 176 6 15/16 11 7/8 291 5 7/16 258 D 451 232 11 15/16 212 11 7/16 TD-250 A 14 5/6 8 3/8 15
MODEL TD-MIXVENT INLINE MIXED FLOW DUCT FAN KIT - TD BATHROOM EXHAUST KITS FEATURING TD-MIXVENT FANS The TD-MIXVENT fan kits provide all the hardware needed to complete a simple in-line ducted ventilation installation. The kit includes a powerful TD in-line fan and exterior and interior grilles (with or without lights). Available in both Standard Exhaust Kits, for venting a single location, and Deluxe Exhaust Kits, for venting multiple locations with one fan.
MODEL TD-SILENT EXTREMELY QUIET INLINE MIXED FLOW DUCT FAN MODEL FEATURES • Exhaust air up to 530 CFM with static pressure capabilities to 1” w.g. • Mixed flow impeller for excellent air flow to pressure performance ratio • Direct connection, two-speed motor • Ideal for applications where space is limited • cULus Listed MODEL OVERVIEW The TD-SILENT fans as the name suggests, are extremely quiet, low profile “Mixed-flow” fans.
MODEL TD-SILENT EXTREMELY QUIET INLINE MIXED FLOW DUCT FAN CONSTRUCTION/SPECIFICATION CHECKLIST Construction The TD-SILENT consists of four (4) nominal sized in-line fans. All models are specifically designed for direct connection in-line with industry standard diameter round ducting. The TD-SILENT models 100XS (4” or 5”), 150S and 200S are manufactured in tough reinforced plastic. Sound waves are directed through the perforated inner skin and absorbed by a layer of soundabsorbent insulation.
MODEL TD-SILENT EXTREMELY QUIET INLINE MIXED FLOW DUCT FAN PERFORMANCE/DIMENSIONS Dimensions (inches/mm) Model A BØ TD-100XS 22 TD-150S 191/16 513/16 1013/16 811/16 49/16 TD-200S 223/8 713/16 127/8 103/8 511/16 5/8 3 9 13/16 C DØ 15/16 8 E 3 1/16 15/16 F 9 G 3 H 1/4 43/4 913/16 33/4 51/4 1311/16 51/16 67/16 13/16 Performance characteristics All models include a direct two speed motor connection. Model TD-100XS TD-150S TD-200S Duct Dia. Ins. Nom.
MODELS TD-MIXVENT & TD-SILENT ACCESSORIES MCA Backdraft dampers are installed at the fans’ discharge. They prevent the entry of odors, air currents and prevent heat leaks when the exhauster is not in operation.
MODELS TD-MIXVENT & TD-SILENT ACCESSORIES TD Bathroom Exhaust Controls - ASHRAE 62.2 CVC - Continuous Ventilation Control S&P’s CVC allow a new or existing bath fan to run continuously on a low speed. In conjunction with an S&P TD fan a CVC will immediately improve the air quality in the home and reduce the damaging effects of moisture and mold. The CVCs are designed to meet the requirements of ASHRAE 62.2 and the International Residential Code. In areas where ASHRAE 62.
MODEL PV INLINE CENTRIFUGAL DUCT FAN MODEL FEATURES • Exhaust air up to 942 CFM with static pressure capabilities to 1.5” w.g.
MODEL PV INLINE CENTRIFUGAL DUCT FAN CONSTRUCTION/SPECIFICATION CHECKLIST Casing • Manufactured from high grade pressed galvanized steel, with black baked enamel coating. • Extra long inlet and discharge collars make installation quick and trouble free. • Supplied with a strong galvanized steel mounting bracket. • Supplied with a prewired junction box. Wheel / Impeller • Backward curved centrifugal type. • Factory matched to an external rotor motor and dynamically balanced to eliminate vibration.
MODEL PV INLINE CENTRIFUGAL DUCT FAN PERFORMANCE/DIMENSIONS Dimensions in inches/mm Model A D C E B C D E F G Weight lbs(kgs) PV-100 313/16 313/16 43/4 711/16 71/2 43/4 99/16 7 97.5 97.5 120 196 190 120 243 3.0 PV-100x 313/16 313/16 43/4 711/16 71/2 43/4 99/16 7 97.5 97.5 120 196 190 120 243 3.0 PV-125 413/16 413/16 43/4 713/16 71/2 43/4 99/16 7 122.5 122.5 120 198 190 120 243 3.0 PV-125x 413/16 413/16 43/4 713/16 71/2 43/4 99/16 7 122.5 122.5 120 198 190 120 243 3.
MODEL PV INLINE CENTRIFUGAL DUCT FAN KIT - PV BATHROOM EXHAUST KITS FEATURING PV-POWERVENT FANS S&P PV-POWERVENT Series fans are also available as easy-to-install kits. This ultra powerful bathroom fan offers a choice of single or dual vent exhaust. These kits are used for installations that require long or complicated duct runs. All PV kits have standard 8-year warranty.
MODEL SWF SIDEWALL CENTRIFUGAL FAN MODEL FEATURES • Exhaust air up to 416 CFM with static pressure capabilities to 1.5” w.g.
MODEL SWF SIDEWALL CENTRIFUGAL FAN CONSTRUCTION/SPECIFICATION CHECKLIST Casing • Manufactured from high grade pressed galvanized steel, with baked enamel coating. • Removable top for easy access to motor for cleaning or inspection. • Large grille opening for easy passing of lint and other potentially clogging materials. • Supplied with a prewired junction box. Wheel / Impeller • Backward curved centrifugal type. • Factory matched to an external rotor motor and dynamically balanced to eliminate vibration.
MODEL SWF SIDEWALL CENTRIFUGAL FAN PERFORMANCE/DIMENSIONS Dimensions in inches/mm D Model C1 C C2 SWF-100 SWF-100x A SWF-150 SWF-150x SWF-200 A 13 1/4 13 1/4 15 1/2 15 1/2 15 B 337 337 394 394 1/2 394 13 1/4 13 1/4 13 1/4 16 1/16 16 C 337 337 337 408 1/16 408 9 228 9 228 10 3/16 10 11 C1 256 254 7/16 290 3 76 3 76 3 76 3 3/16 3 C2 81 3/8 87 2 7/16 62 2 7/16 62 2 7/16 62 2 7/16 2 D 62 7/16 62 4 4 6 6 8 100 100 150 150 200 B 2 mm Air Performance Current Watts
MODELS TD-MIXVENT, TD-SILENT, PV & SWF ACCESSORIES BATHROOM EXHAUST GRILLES FOR INLINE FANS Featuring Vent Lights and Premium Grilles S&P’s Grille Options give you the choice of seven (7) aesthetically pleasing grilles designed to match any bathroom decor. You can choose from our Vent Lights, Premium Grilles or Adjustable Grilles to fit your needs. These grilles are designed to be used exclusively with one of S&P’s remotely mounted inline fans (TD, PV, SWF) for virtually silent bathroom ventilation.
Premium Grilles PG MODELS TD-MIXVENT, TD-SILENT, PV & SWF ACCESSORIES S&P’s premium grilles come standard with steel collars for easy mounting and installation. Model PG-100 PG-150 Description 4” Plastic Grille with 4” Steel Collar 6” Plastic Grille with 6” Steel Collar Grille Dimensions (in inches) Grille Dia. Height PG-150G PG-100G 8 1/8 4 5/8 1 5/8 1 1/2 Fits Duct Dia.
MODELS TD-MIXVENT, TD-SILENT, PV & SWF ACCESSORIES ADDITIONAL GENERAL ASSEMBLY ACCESSORIES BOR/BOC Round plastic/metal adjustable grille PG MBR Round grille without built-in backdraft damper Connection Flanges PER-W PER GRA MFL SR SY ID SIL Plastic louver shutter Reducer High pressure aluminum louver shutter Y sheet metal adapter Aluminum exterior fixed grilles Flexible round duct Filtering Box Acoustic attenuators Electrical accessories EPBT Electronic push button timer 32 SCS
KIT - CLOTHES DRYER BOOSTING KITS FEATURING PV-100x FANS If you have a dryer with long or complicated duct runs, S&P offers the perfect solution to increase dryer efficiency: the PV100x Dryer Booster Fan. The PV100x has been specifically designed to handle dryer boosting applications when overcoming long or complicated duct runs. This system helps save on drying time, moisture build-up, wear and tear on your dryer, and helps save on your electric bill.
MODEL PC CEILING MOUNT BATHROOM FAN Features & Construction • • • • • • • • • • • • • • Performance Model PC50 PC80X PC110X PC150 Duct Size CFM 4” 4” 6” 4” 6” 6” 50/31 80/58 80/63 96/70 110/87 150/110 Extremely quiet operation <0.3 to 1.
MODEL PC CEILING MOUNT BATHROOM FAN PC Options Overview The simplicity of S&P’s Premium CHOICE Series comes in the options. While other premium bath fans come as lighted fans, speed control, motion sensor or humidity sensor built in, our Premium Choice bath fans give you the flexibility to choose your grille and control separately.
MODEL PC CEILING MOUNT BATHROOM FAN PC CONTROLS Humidity Sensor (PCHS) Using a PC fan with S&P’s humidity sensing control is a worry free solution to fighting excess humidity and possible mold problems. The sensor easily mounts inside the fan housing utilizing 2 pre-drilled holes and a standard receptacle. With the sensor at ceiling level it detects rapid increases in moisture where steam and humidity naturally rise, and automatically turns on the fan.
MODEL PC CEILING MOUNT BATHROOM FAN PC CONTRACTOR PACKS For simple installation, PC80X and PC110X are available as 4 packs with the fan housings ready for installation first, then after the drywall and painting are complete the motor and grilles are available to finish the job. The housing kit includes the housing and hanger bars, while the finish kit includes the motor plate, motor, wheel and grille.
MODELS PCD110M & PCD110H CEILING MOUNT BATHROOM FANS WITH DC MOTOR MODELS PCD110M & PCD110H CEILING MOUNT BATHROOM FANS WITH DC MOTOR Features and Construction • • • • • • • • • • • • Extremely quiet operation 0.
MODEL PCLP LOW PROFILE CEILING MOUNT BATHROOM FANS Features & Construction • Low profile housing design • Suitable for wall and ceiling installations • Quiet operation <0.4 to 2.0 Sones • Totally enclosed condenser motor for long life • Motor rated for 30,000 hours continuous on • Built-in backdraft damper • Robust steel housing • Attractive, sturdy grille • ETL Listed • ENERGY STAR® qualified • HVI Certified • 5-year warranty Performance and Dimensions PCLP50 PCLP80 PCLP100 CFM @ 0.1/0.
PCLP - LOW PROFILE PREMIUM CHOICE SERIES LED LIGHT KITS LED Grille Lights S&P offers Premium Choice Series Light Kits with LED lights for the PCLP models so you can choose a fan with lights now or later. This kit (PCLPLEDK) fits the PCLP50, 80, and 100. The LED lighted grilles come standard with an 11 Watt LED light and a 2 Watt LED night light setting.
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS MODEL FF FEATURES Model FF • Exhaust air up to 1500 CFM • Forward curve centrifugal wheel for high static pressure capabilities to 1” w.g.
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS CONSTRUCTION/SPECIFICATION CHECKLIST Grille • Conceals interior. • Low profile styling, blends with any decor. • White polymeric (FF50 - FF300). • Metal finished with white enamel finish (FF400-FF1500). Blower • Low RPM for quiet operation, speed controllable. • Resilient anti-vibration mounts (FF50 & FF80 rigid mount). • Balanced, polymeric, centrifugal blower wheel for quiet, efficient performance. (Metal wheel on FFC2000 & FFC3500).
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS OPTIONS/ACCESSORIES Roof Cap and Wall Cap • Weather resistant duct termination. Inline Adapter Kit • Converts FF units into inline units. • Available for FF100 through FF1500 Radiation Damper • UL rated for use in 1, 2, or 3 hour rated floor-ceiling, roof-ceiling design. • Mounts directly to the fan, screws provided. • Galvanized steel frame. • High temperature, non-asbestos, reinforced fiber thermal fabric. • 212oF fusible link.
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS OPTIONS/ACCESSORIES (cont.
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS OPTIONS/ACCESSORIES (cont.) 14 14 12 12 2” Speed Control • Adjust speed from 100 to 50% • 5 amp & 10 amp - 120V • 6 amp - 240V • 6 amp - 277V 9 9 22 16.
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS OPTIONAL ACCESSORY COMPATIBILITY CHART CEILING MOUNT MODEL FF VARIABLE SPEED CONTROLS 2727.1 (5 AMP 120V) FF50 FF80 FF100 FF150 FF200 FF250 FF300 X FF400 FF500 FF700 FF900 X X X 2828.
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS MODEL FF PERFORMANCE FF CEILING VENTILATORS MODEL FF 100 150 200 250 300 400 500 700 900 1500 CFM / Sones at Static Pressure (PS - Inches of H2O) 0 1/10 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 136 115 109 93 80 0.5 0.8 0.9 1.3 1.8 65 44 - - - 2.3 3.0 - - - 181 161 157 141 132 124 114 1.3 1.4 1.5 2.2 2.6 3.1 3.6 94 62 - 4.1 4.6 - 231 214 210 196 186 177 165 144 113 51 1.6 1.8 1.7 2.3 2.9 3.5 4.
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS MODEL FFC PERFORMANCE FFC INLINE/CABINET VENTILATORS MODEL FFC 100 150 200 250 300 400 500 700 900 1500 CFM / Sones at Static Pressure (PS - Inches of H2O) 0 1/10 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 121 108 106 97 93 86 0.5 0.7 0.7 1.1 1.4 1.8 70 44 - - 2.1 2.4 - - 153 148 147 140 134 125 111 0.9 1.0 1.1 1.4 1.6 1.9 2.1 91 54 - 2.2 2.4 - 205 196 195 190 185 175 158 135 96 47 1.7 1.9 1.9 2.
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS DIMENSIONS CEILING VENTILATOR FF50 INLINE/CABINET VENTILATOR 49
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS FF CEILING VENTILATORS QUICK SELECTION GUIDE FF50 FF80 FF100, FF150 FF200, FF250, FF300 FF400, FF500, FF700 FF900, FF1500 Models FF50, 80, 100, 150, 200, 250, 300, 400, 500, 700, 900, and 1500 Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings include the effects of inlet grille and backdraft damper.
MODELS FF & FFC CEILING AND INLINE/CABINET VENTILATORS FFC INLINE/CABINET VENTILATORS QUICK SELECTION GUIDE FFC200, FFC250, FFC100, FFC150 FFC300 FFC400, FFC500, FFC700 FFC2000, FFC3500 FFC900, FFC1500 FF & FFC QUICK SELECTION GUIDELINES 1. Locate desired CFM on bottom horizontal axis of graph. 2. Locate system static pressure on left vertical axis of graph. 3. Determine intersection of CFM and static pressure. 4. Select fan curve to the right of this intersection. 5.
MODELS TR & TRC TOTAL RECOVERY FOR ALL CLIMATES RESIDENTIAL OR COMMERCIAL APPLICATIONS With S&P’s TR & TRC (total recovery) Series for all climates, stale room air is exhausted and fresh outdoor air is brought back into the house. These two air streams are directed through a highly developed “air-to-air” energy exchange core. The air streams are physically separated by many layers of “plates” so there is no mixing or contamination of the fresh air.
MODELS TR & TRC TOTAL RECOVERY FOR ALL CLIMATES MODEL TR AND TRC SIZING Choosing the Right Size TR by Square Footage Choosing the correct size TR for your structure is easy, all you need to know is the square footage. If you structure is up to: 1500 Sq. Ft. you need a TR90/TR90G 2700 Sq. Ft. you need a TR130 4000 Sq. Ft. you need a TR200 6000 Sq. Ft.
MODEL TR TOTAL RECOVERY FOR ALL CLIMATES MODEL FEATURES • MERV-8 filters • Less than 1 watt stand-by power consumption • Transformer/relay package allowing simple on/off control • Plastic double collars for 6 or 8” direct duct connection (TR300 is 8” only) • 3’ power cord • Integral mounting flange and hanging bracket system • Fully insulated case • Large cores for high efficiency • No condensate pan or drain required MODEL OVERVIEW To protect the two most valuable investments of your life, your home an
MODEL TR TOTAL RECOVERY FOR ALL CLIMATES STANDARD SPECIFICATIONS AND FEATURES Residential/Light Commercial Applications • MERV-8 filters • Less than 1 watt stand-by power consumption • Transformer/relay package allowing simple on/off control • Plastic double collars for 6 or 8” direct duct connection (TR300 is 8” only) • TR90, TR130, TR300 have painted case, low voltage controls, 3’ Power cord • TR90G has galvanized case, line voltage and no line cord • Integral mounting flange and hanging bracket system •
MODEL TR TOTAL RECOVERY FOR ALL CLIMATES TR APPLICATIONS Central Exhaust Your BEST choice for green ventilation, Series TR exhausts stale air, brings in fresh air and saves energy year-round. Series TR • Replaces bathroom exhaust fans • 20 CFM continuous per bathroom • 50 CFM intermittent per bathroom • Meets ASHRAE 62.2 when used with one of S&P’s Percentage Timer Controls • Other possible exhaust locations: kitchen area (cannot exhaust range hood), utility room, smoking room, hobby room, etc.
MODEL TR TOTAL RECOVERY FOR ALL CLIMATES CONTROLS SPTL - Percentage Timer Control • Primary control for TR90/TR90G, TR130, TR200 and TR300 • Runs unit an adjustable amount of time each hour • Two wire, low voltage connection to TR • Meets ASHRAE 62.
MODEL TR TOTAL RECOVERY FOR ALL CLIMATES TR90/TR90G LISTED DUCTED HEAT RECOVERY VENTILATOR 89S5 Performance Specifications Airflow CFM Temp EFF% Temp Winter%* Total EFF% Summer* 113 61 55 42 TR90G - Galvanized Case, Line Voltage, No Line Cord 98 64 58 46 Unit may be mounted in any orientation and in heated or unheated locations 85 67 61 49 73 69 33 53 Number Motors: Two, 0.03 HP each, totally enclosed, thermally protected, 0.
MODEL TR TOTAL RECOVERY FOR ALL CLIMATES TR130 Performance Airflow CFM LISTED DUCTED HEAT RECOVERY VENTILATOR 89S5 ESP in H 2O Temp EFF% Total EFF% Winter/Summer* 0.60 78 73/60 104 0.50 75 69/55 126 0.40 72 66/50 137 0.30 71 64/48 153 0.20 68 61/45 165 0.10 67 59/43 79 * Contact Factory for HVI certification report for complete certified rating.
TR200 MODEL TR TOTAL RECOVERY FOR ALL CLIMATES Performance Airflow CFM LISTED DUCTED HEAT RECOVERY VENTILATOR 89S5 ESP in H2O Temp EFF% Total EFF% Winter/Summer* 0.70 81 77/64 149 0.60 79 75/61 168 0.50 78 73/59 176 0.40 78 72/59 186 0.30 77 72/58 122 Specifications 192 0.20 77 71/57 207 0.10 76 70/56 * Contact Factory for HVI certification report for complete certified rating.
MODEL TR TOTAL RECOVERY FOR ALL CLIMATES TR300 Performance Airflow CFM LISTED DUCTED HEAT RECOVERY VENTILATOR 89S5 Specifications ESP in H2O Temp EFF% Total EFF% Winter/Summer* 1.0 78 73/59 191 0.9 77 71/57 215 0.8 75 69/55 256 0.7 73 66/51 277 0.6 71 65/49 170 295 0.5 70 63/47 311 0.4 69 62/46 * Contact Factory for HVI certification report for complete certified rating.
MODEL TRC TOTAL RECOVERY FOR ALL CLIMATES COMMERCIAL APPLICATIONS MODEL FEATURES • MERV-8 filters • Non-Fused disconnect • Transformer/relay package allowing simple on/off control • Access doors for easy access to blowers, core and filters • Fully insulated case • Large cores for high efficiency • No condensate pan or drain required MODEL OVERVIEW With S&P’s TRC (total recovery for commercial applications) Series for all climates, stale room air is exhausted and fresh outdoor air is brought back into th
MODEL TRC TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS STANDARD SPECIFICATIONS AND FEATURES • AHRI certified performance data for efficiency and cross leakage. • UL tested flammability and smoke generation that meets NFPA 90A and 90B test standards for commercial applications. • Easy installation and service.
MODEL TRC TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS CONTROLS These controls are intended to turn S&P commercial energy recovery ventilation systems on and off at appropriate times. Specification, installation and set-up is an easy process. The TRC units come standard with a 24 volt transformer/relay package for easy interface with all controls. It is not necessary that S&P controls be used to operate S&P units. A wide range of controls or building automation systems may be used.
TRC500 MODEL TRC TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS Performance Airflow CFM LISTED DUCTED HEAT RECOVERY VENTILATOR 89S5 ESP in H 2O Watts Temp EFF% Total EFF% Winter/Summer* 1.25 335 81 76/66 338 1.00 420 77 71/61 380 0.90 470 75 69/59 450 0.65 550 73 66/56 540 0.25 640 70 62/52 225 575 0.00 690 69 61/51 600 -0.25 735 68 60/50 * At AHRI 1060 standard conditions (see certified data on page 69 for core components.
EA: Exhaust Air to outside OA: Outside Air intake RA: Room Air to be exhausted FA: Fresh Air to inside LEFT VIEW FRONT VIEW WITH DOOR ON 16 3/8" Customer Approvals Control Wiring Inlet 7/8" dia. Power Wiring Inlet 7/8" dia. 2 1/8" FA EA 8" c/c typ. 1.
MODEL TRC TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS TRC800 Performance LISTED 250 Effectiveness (%) DUCTED HEAT RECOVERY VENTILATOR 89S5 500 CFM 750 1,000 80 Sensible Winter T otal Summ er Tot al 60 40 * At AHRI 1060 standard conditions (see certified data on page 69 for core components.
12" Dia. typical 12 7/8" 8 5/8" FA LEFT VIEW EA FRONT VIEW WITH DOOR ON 27 7/8" Power Wiring Inlet 7/8" dia. Control Wiring Inlet 7/8" dia. FA EA 1.5" clearance required to remove door Alt. Control Wiring Inlet 7/8" Dia. Alt. Power Wiring Inlet 7/8" Dia.
MODEL TRC TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS TRC1600 Performance LISTED 1,000 500 Effectiveness (%) DUCTED HEAT RECOVERY VENTILATOR 89S5 CFM 1,500 2,000 80 Sensible Winter T otal Summ er Tot al 60 40 * At AHRI 1060 standard conditions (see certified data on page 69 for core components.
68 41 3/8" CASE LEFT VIEW FA FA EA FRONT VIEW 51 3/8" 49 1/8" CASE TOP VIEW RA OA RIGHT VIEW RA OA 14" X 24" INLETS 34 3/4" CASE 36 3/4" ISOMETRIC VIEW TRC1600 EA Ø 7/8" CONTROL WIRING 37 3/8" MOUNTING HOLES Dimensions 14" X 24" OUTLETS Ø 7/8" POWER WIRING 41 3/4" 50 1/2" MOUNTING HOLES EA: Exhaust Air to outdoors OA: Outdoor Air intake RA: Room Air to be exhausted FA: Fresh Air to inside MODEL TRC TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS
MODEL TRC TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS AHRI 1060-2005 - CERTIFIED PERFORMANCE AHRI-1060 Certified Performance - Model Number L85-G5 (used in TRC500) Type Tilt Angle Plate N/A Leakage Ratings EATR OACF -1 in. H2O 1.0% Test 2 0 in. H2O 0.0% 1.02 N/A Test 3 1 in. H2O 0.0% 1.05 N/A 1.00 Pressure Drop 100% - 450 SCFM 0.6 in. H2O 75% - 338 SCFM 0.5 in.
MODEL CRT OUTDOOR CABINET WITH CORES MODEL FEATURES • MERV-8 filters • Fully insulated case • Large cores for high efficiency • No condensate pan or drain required • AHRI Certified • Rainhood included • Access door for easy maintenance and Cleaning • Integral lifting lugs MODEL OVERVIEW The Models CRT consist of an insulated sheet metal cabinet with 2, 3 or 4 ERV cores and MERV 8 filters.
Ind Blo MODEL CRT OUTDOOR CABINET WITH CORES SPECIFICATIONS Residential/Light Commercial Applications Typ AH Ventilation Type: Static Plate, Heat and Humidity Transfer Insulated sheet metal cabinets with energy exchange cores and filters Individual CRT Series units can be built to larger air handling systems Blower not included and must be specified to meet job requirements Description C2XRT G5C3XRT Performance C4XRT Typical Airflow Range CFM 500-2,200 750-3,300 1,000-4,000 CFM AHRI 1060 Certified Co
FA Curb C2XRT 32 5/8" OD 28 7/8" ID RA 55" Service Area 3" 14" 1-7/8" EA: Exhaust Air to outside OA: Outside Air intake RA: Room Air to be exhausted FA: Fresh Air to inside 1 3/8" 76 7/8" Service Area 3/4" x 3 1/2" Wooden Nailer 1 1/2" x 1/4" Neoprene Gasket (Supplied with Curb) 5 3/4" Left View 43 1/8" 9 3/8" OA inlet hood can be mounted to either side of the unit. Filters are 2" x 20" x 20" pleated disposable.
FA Curb C3XRT 1 3/8" RA 12 3/8" ID 28 7/8" ID 32 5/8" OD 55" Service Area EA: Exhaust Air to outside OA: Outside Air intake RA: Room Air to be exhausted 96" Service Area 3" 14" 1 7/8" 38 1/4" ID 3/4" x 3 1/2" Wooden Nailer 53 3/4" ID 1-7/8" 1 3/8" 5 1/8" 12 1/8" 9 3/4" Filters are 2" x 20" x 20" pleated disposable. Note: Filters are provided for installation in any two of the locations shown, depending on which duct connections are selected for inlets.
77 1/8" OD 116" Service Area FA Curb C4XRT 1 3/8" RA 32 5/8" OD 1 3/8" EA: Exhaust Air to outside OA: Outside Air intake RA: Room Air to be exhausted FA: Fresh Air to inside 13 3/8" 1 7/8" 55" Service Area 3" 3/4" x 3 1/2" Wooden Nailer 1 1/2" x 1/4" Neoprene Gasket (Supplied with Curb) 1-7/8" Left View 48" Note: Filters are provided for installation in any two of the locations shown, depending on which duct connections are selected for inlets.
MODEL HR HEAT RECOVERY VENTILATORS MODEL FEATURES • • • • • • • Polypropylene HRV core 3 operating modes Painted galvanized steel case Designed for simple installation by a single person Fully insulated case Limited lifetime warranty on the heat recovery core 5-year warranty on balance of unit MODEL OVERVIEW The S&P HR Series heat recovery ventilators (HRVs) are ideal for use in cold climates where home heating is essential.
MODEL HR HEAT RECOVERY VENTILATORS STANDARD SPECIFICATIONS AND FEATURES Residential/Light Commercial Applications • • • • • • • • • • Polypropylene HRV core 3 operating modes (Intermittent, Continuous and High Speed) DuotrolTM balancing system reduces noise that would be produced by balancing dampers Unique collar system for easy manipulation of duct for better and quicker installation Painted galvanized steel case Designed for simple installation by a single person Washable filters Fully insulated case L
MODEL HR HEAT RECOVERY VENTILATORS Types of Installation The HR Series can be installed as independent systems that use independent ductwork or they can be connected to the existing duct of the forced air heating or cooling system. The “Best” and “Better” systems meet the ASHRAE 62.2 Whole Building requirement when using an S&P HR control (see pg 18).
MODEL HR HEAT RECOVERY VENTILATORS CONTROLS HRT-3 - Push Button Timer • The HRT-3 model push button timer allows the homeowner control of the indoor humidity level in rooms were excess humidity is produced • Press the button once the LED comes on then release, this activates the ventilation system to high speed for 20 minutes. • Press the button until the LED blinks 2 times then release, this activates the ventilation system to high speed for 40 minutes.
MODEL HR HEAT RECOVERY VENTILATORS HR100V Energy Performance (Heating) Specifications Polypropylene HRV Core: cross-flow that transfers sensible heat Supply Temperature Net Air Flow Duct Connections: Four (4) 5” oval ISF double collar system °F °C CFM L/s Power Consumed (Watts) Number Motors: Two (2) PSC variable speed backward curved 32 0 40 19 28 64 Typical Airflow Range: 30-100 CFM V Hz Phase Amperage 120 60 Single 0.85 A / 66 watts Exchange surface: 63.
MODEL HR HEAT RECOVERY VENTILATORS HR160H Energy Performance (Heating) Specifications Polypropylene HRV Core: cross-flow that transfers sensible heat Supply Temperature Net Air Flow Duct Connections: Four (4) 6” dia.
MODEL HR HEAT RECOVERY VENTILATORS HR220H Energy Performance (Heating) Specifications Polypropylene HRV Core: cross-flow that transfers sensible heat Supply Temperature Net Air Flow Duct Connections: Four (4) 6” dia.
MODEL LPD LOW PROFILE DIRECT DRIVE CENTRIFUGAL ROOF/SIDEWALL EXHAUSTER MODEL FEATURES • Exhaust air up to 420 CFM in high static pressure applications up to 1-3/4” w.g.
MODEL LPD LOW PROFILE DIRECT DRIVE CENTRIFUGAL ROOF/SIDEWALL EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Ultra low profile, aluminum construction. • Curb cap has integral deep spun inlet for efficient performance and prepunched mounting holes for ease of installation. • Spun aluminum hood and skirt for weather protection and attractive appearance. • Up to 140°F airstream temperature. • Heavy-gauge motor support for rigidity and strength.
MODEL LPD LOW PROFILE DIRECT DRIVE CENTRIFUGAL ROOF/SIDEWALL EXHAUSTER OPTIONS/ACCESSORIES Solid State Speed Control: S&P’s solid state control is matched to allow smooth RPM variation and adjustment of airflow for system balancing. CFM is reduced in direct proportion to motor speed reduction. Speed controllers available for 115/1 or 230/1 operation. Exhauster performance can be controlled from the ventilated area.
MODEL LPD LOW PROFILE DIRECT DRIVE CENTRIFUGAL ROOF/SIDEWALL EXHAUSTER PERFORMANCE/DIMENSIONS O.D. Damper Size Roof Opening Curb O.D. A B Average Ship Wt. Lbs. 6 11 11-3/4 14-3/4 16-1/2 7 16-1/2 12 8 11 11-3/4 14-3/4 16-1/2 7 16-1/2 15 60 Hz Model LPD C CFM @ Static Pressure 1-1/4 1-1/2 1-3/4 RPM (Nom.) Max Motor Watts & Amps Sones @ 1/2" 0 1/8 1/4 3/8 1/2 5/8 3/4 1 LPD06A60 115/1/60 302 268 247 222 197 175 155 118 87 52 - 2800 90 / 0.8 7.
MODEL RED DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 3,000 CFM in high static pressure applications up to 1” w.g. • Attractive spun aluminum exterior • Direct drive units have low sound levels and quiet operation • Non-overloading backward inclined wheel for efficiency at higher static pressures • AMCA Air and Sound Licensed • cULus 705 Listed MODEL OVERVIEW Model RED direct drive fans are designed to exhaust air up to 3,000 CFM in high static pressure applications to 1”.
MODEL RED DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Curb cap has integral deep spun inlet for efficient performance and prepunched mounting holes for ease of installation. • Fan plate isolates motor compartment from contaminated exhaust air. • Spun aluminum hood and skirt for weather protection and attractive appearance. • Heavy-gauge motor support for rigidity and strength. • Neoprene isolators for reduction of vibration and sound.
MODEL RED DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER OPTIONS/ACCESSORIES Solid State Speed Control: S&P's solid state control is matched to the motor and blower wheel to allow continuous reduction in performance allowing adjustments of airflow for system balancing. CFM is reduced in direct proportion to motor speed reduction. Speed control is available for 115 or 230 volt single phase. Exhauster performance can be controlled from the ventilated area.
MODEL RED DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER PERFORMANCE/DIMENSIONS Model RED6 Damper I.D. O.D. Roof Opening 11 11 11-3/4 Curb O.D. A B C D Average Ship Wt. Lbs. 14-3/4 21-3/4 12 16-1/2 1-3/4 50 Fan RPM performances may vary from actual current motor offerings for any given model. See price publications or software for current motor RPM offerings CFM/BHP @ Static Pressure/Sones HP RPM (Nom.
MODEL RED DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER Models RED8 and RED10 I.D. Damper O.D. Roof Opening Curb O.D. A B C D Average Ship Wt. Lbs. RED812/810 11 11 11-3/4 14-3/4 21-3/4 13-1/2 16-1/2 1-3/4 50 RED8167 11 11 11-3/4 14-3/4 21-3/4 15-3/4 16-1/2 1-3/4 50 RED10 11 11 11-3/4 14-3/4 21-3/4 17-1/4 16-1/2 1-3/4 50 Size Fan RPM performances may vary from actual current motor offerings for any given model.
MODEL RED DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER Models RED12 and RED15 Damper I.D. O.D. Roof Opening 18 18 19-1/4 Curb O.D. A B C D Average Ship Wt. Lbs. 22-1/4 33-1/8 23-1/2 24 2 124 Fan RPM performances may vary from actual current motor offerings for any given model. See price publications or software for current motor RPM offerings RED15 RED12 CFM/BHP @ Static Pressure/Sones RPM Tip (Nom.) Speed 0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 Catalog Number HP 1209 .07/6.5 959 .
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR MODEL FEATURES • Exhaust air up to 3,000 CFM in high static pressure applications up to 1.5” w.g. • Attractive spun aluminum exterior • Motor has 80% usable turndown vs.
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Curb cap has integral deep spun inlet for efficient performance and prepunched mounting holes for ease of installation. • Fan plate isolates motor compartment from contaminated exhaust air. • Spun aluminum hood and skirt for weather protection and attractive appearance. • Heavy-gauge motor support for rigidity and strength.
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR eMotor - Electronically Commutated Motor S&P’s eMotor is 115/230V and 50/60 Hz and is available in 1/4, 1/3 and 1/2 HP. This fully controllable motor offers both reliability and low maintenance in one of the most efficient motor fan combinations in the industry. When used in S&P’s eRED downblast fan, the eMotor is the ideal solution for a low cost, fully controlled ventilation system.
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR Constant Pressure Control Options with eRED Constant Pressure Controls: For constant pressure control applications, the S&P constant pressure control package is available. This package includes the components that are needed to complete a demand-based exhaust ventilation system for kitchens, bathrooms, and/or clothes dryer exhaust in multi-story buildings.
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR OPTIONS/ACCESSORIES Roof Curb: Prefabricated heavy-gauge galvanized steel welded construction, 12" high with 1-1/2" wood nailer. Assures perfect fit of exhauster to roof curb. Options include burglar bars, single and double pitch construction, and additional curb heights. Sound Curb: Option of thermal acoustical lining or a complete maximum sound attenuating baffle system. Provision for mounting damper is available.
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR PERFORMANCE/DIMENSIONS Model eRED6 Damper RPM I.D. O.D. Roof Opening 11 11 11-3/4 Curb O.D. A B C D Average Ship Wt. Lbs. 14-3/4 21-3/4 12 16-1/2 1-3/4 50 CFM/BHP @ Static Pressure/Sones 0 0.125 0.25 0.375 0.5 0.625 850 190 0.01/1.5 - - - - - 900 202 0.01/1.9 95 0.01/1.2 - - - - 950 213 0.01/2.2 115 0.01/1.5 - - - - 1000 224 0.01/2.4 133 0.01/1.8 - - - - 1050 235 0.
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR Models eRED8 Damper RPM I.D. O.D. Roof Opening Curb O.D. A B C D Average Ship Wt. Lbs. 11 11 11-3/4 14-3/4 21-3/4 13-1/2 16-1/2 1-3/4 50 CFM/BHP @ Static Pressure/Sones 0 0.125 0.25 0.375 0.5 0.625 0.75 1 600 342 0.01/1.3 103 0.01/0.4 - - - - - - 650 371 0.01/1.7 175 0.01/0.6 - - - - - - 700 399 0.01/2.1 229 0.02/1 - - - - - - 750 428 0.02/2.5 275 0.02/1.
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR Models eRED10 Damper RPM I.D. O.D. Roof Opening Curb O.D. A B C D Average Ship Wt. Lbs. 11 11 11-3/4 14-3/4 21-3/4 17-1/4 16-1/2 1-3/4 50 CFM/BHP @ Static Pressure/Sones 0 0.125 0.25 0.375 0.5 0.625 0.75 1 550 488 0.01/1.5 59 0.01/0.6 - - - - - - 600 533 0.01/1.9 220 0.01/0.9 - - - - - - 650 577 0.02/2.3 312 0.02/1.4 - - - - - - 700 621 0.02/2.8 386 0.02/1.
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR Models eRED12 Damper RPM I.D. O.D. Roof Opening 18 18 19-1/4 Curb O.D. A B C D Average Ship Wt. Lbs. 22-1/4 33-1/8 23-1/2 24 2 124 CFM/BHP @ Static Pressure/Sones 0 0.125 0.25 0.375 0.5 0.625 0.75 1 1.25 1.5 500 751 0.01/2 248 0.01/1.1 - - - - - - - - 550 826 0.02/2.5 368 0.02/1.6 - - - - - - - - 600 901 0.02/3.1 466 0.02/2.2 - - - - - - - - 650 976 0.03/3.
MODEL eRED DOWNBLAST CENTRIFUGAL ROOF EXHAUSTER WITH ELECTRONICALLY COMMUTATED MOTOR Models eRED15 Damper RPM I.D. O.D. Roof Opening 18 18 19-1/4 Curb O.D. A B C D Average Ship Wt. Lbs. 22-1/4 33-1/8 23-1/2 24 2 124 CFM/BHP @ Static Pressure/Sones 0 0.125 0.25 0.375 0.5 0.625 0.75 400 1046 0.02/1.9 255 0.03/0.6 - - - - - 450 1177 0.03/2.7 524 0.03/1.3 - - - - - 500 1308 0.04/3.4 738 0.04/2.1 - - - - - 550 1439 0.05/4.2 931 0.05/2.9 245 0.
MODELS SDBD & SDB DIRECT DRIVE AND BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTERS MODEL SDBD - DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 4,980 CFM in high static pressure applications up to 1-1/2” w.g.
MODELS SDBD & SDB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTERS Downblast Model Overview & Construction Features Model SDB - Belt Drive Size Range Motor HP Range CFM Range Static Pressure Warranty Model SDBD - Direct Drive 6, 7, 8, 10, 12, 14, 15 & 16 1/4 to 1 40 to 4135 up to 1-1/2 in. w.g. 5 years Size Range Motor HP Range CFM Range Static Pressure Warranty 2 6, 7, 8, 10, 12, 14, 15 & 16 1/25 to 1-1/2 40 to 4980 up to 1-3/4 in. w.g.
MODELS SDBD & SDB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTERS Downblast Model Overview & Construction Features # Feature 1 Motor Cover 2 Motor Cover Cap 3 Quick-Release Latches Description Heavy-gauge aluminum motor cover provides weather protection for motor compartment. Heavy-gauge aluminum top with rolled bead for added strength and quick-release latches. Stainless steel latches for easy removal of motor cover cap for access to the motor compartment and motor.
MODELS SDBD & SDB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTERS DIMENSIONS Dimensions in Inches Model SDBD: Direct Drive Centrifugal Downblast B D A C 2.0 Size A B C D Roof Opening Curb O.D. Damper O.D. Average Ship Wt. Lbs.
MODELS SDBD & SDB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTERS OPTIONS/ACCESSORIES Solid State Speed Control (SDBD): S&P’s solid state control is matched to the motor and blower wheel to allow continuous reduction in performance allowing adjustments of airflow for system balancing. CFM is reduced in direct proportion to motor speed reduction. Speed control is available for 115 or 230 volt single phase. Exhauster performance can be controlled from the ventilated area.
MODELS SDBD DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Curb cap has integral deep spun inlet for efficient performance and prepunched mounting holes for ease of installation. • Spun aluminum hood and skirt for weather protection and attractive appearance. • Heavy-gauge motor support for rigidity and strength. • Neoprene isolators for reduction of vibration and sound. • Quick-Release latches on motor cover for easy access to motor compartment.
MODEL SDBD DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER PERFORMANCE Sizes 6 & 7 SDBD7 SDBD6 (1) SDBD6C (1) Model 108 Motor HP RPM 1/10 900 1/10 1050 1/10 1200 1/10 1350 1/10 1500 1/10 1650 1/10 900 1/10 1050 1/10 1200 1/10 1350 1/10 1500 1/10 1650 1/10 900 1/10 1050 1/10 1200 1/10 1350 1/10 1500 1/10 1650 CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones CFM BHP Sones C
MODEL SDBD DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER Size 8 Motor HP 1/25 1/25 1/25 1/25 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1/4 1/4 Static Pressure in Inches w.g. RPM 700 850 1000 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 CFM 381 188 - - - - - - BHP 0.01 0.01 - - - - - - Sones 2.4 1.2 - - - - - - CFM 463 343 - - - - - - BHP 0.01 0.
MODEL SDBD DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER Size 10 Motor HP 1/4 1/4 1/4 1/4 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 110 Static Pressure in Inches w.g. RPM 700 850 1000 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 CFM 589 416 - - - - - - - BHP 0.02 0.03 - - - - - - - Sones 3.0 2.5 - - - - - - - CFM 715 586 391 - - - - - - BHP 0.04 0.04 0.
MODEL SDBD DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER Size 12 Motor HP 1/4 1/4 1/4 1/4 1/4 1/4 1/2 1/2 1/2 1/2 Static Pressure in Inches w.g. RPM 900 950 1000 1050 1100 1150 1200 1250 1300 1350 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 CFM 1000 856 673 275 - - - - - - BHP 0.06 0.07 0.07 0.07 - - - - - - Sones 6.0 5.4 4.9 4.8 - - - - - - CFM 1055 920 756 479 - - - - - - BHP 0.07 0.08 0.09 0.
MODEL SDBD DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER Size 14 Motor HP 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1 Static Pressure in Inches w.g. RPM 750 800 850 900 950 1000 1050 1100 1725 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 CFM 1511 1269 942 - - - - - - - - BHP 0.07 0.08 0.08 - - - - - - - - Sones 6.5 5.7 4.6 - - - - - - - - CFM 1612 1387 1103 - - - - - - - - BHP 0.08 0.09 0.
MODEL SDBD DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER Size 15 Motor HP 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1-1/2 Static Pressure in Inches w.g. RPM 750 800 850 900 950 1000 1050 1100 1150 1750 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 1.75 CFM 1748 1556 1282 779 - - - - - - - - BHP 0.08 0.09 0.10 0.10 - - - - - - - - Sones 7.4 6.9 6.2 5.6 - - - - - - - - CFM 1865 1688 1445 1140 - - - - - - - - BHP 0.
MODEL SDBD DIRECT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER Size 16 Motor HP 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1-1/2 Static Pressure in Inches w.g. RPM 750 800 850 900 950 1000 1050 1100 1150 1750 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 CFM 2172 1945 1680 1317 - - - - - - - 1.75 - BHP 0.11 0.13 0.13 0.14 - - - - - - - - Sones 8.6 8.1 7.4 6.7 - - - - - - - CFM 2316 2105 1864 1555 - - - - - - - - BHP 0.13 0.
MODEL SDB BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Curb cap has integral deep spun inlet for efficient performance and prepunched mounting holes for ease of installation. • Lifting lugs for easy and safe placement of the fan on the roof. • Spun aluminum hood and skirt for weather protection and attractive appearance. • Heavy-gauge motor support for rigidity and strength. • Neoprene isolators for reduction of vibration and sound.
MODEL SDB BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER SIZE 6 Motor HP 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 Static Pressure in Inches w.g. RPM 700 850 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 CFM 131 41 - - - - - - BHP 0.01 0.01 - - - - - - Sones 1.2 1.2 - - - - - - CFM 159 104 - - - - - - BHP 0.01 0.02 - - - - - - Sones 2.1 2.
MODEL SDB BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER SIZE 7 Motor HP 700 1/4 1/4 800 1/4 900 1/4 1000 1/4 1100 1/4 1200 1/4 1300 1/4 1400 1/4 1500 1/4 1600 1/4 1700 1/4 1800 1/4 1900 1/4 Static Pressure in Inches w.g. RPM 2000 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 CFM 192 44 - - - - - - BHP 0.01 0.01 - - - - - - Sones 1.3 1.4 - - - - - - CFM 219 102 - - - - - - BHP 0.01 0.01 - - - - - - Sones 2.1 2.
MODEL SDB BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER SIZE 8 Motor HP 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/3 1/3 Static Pressure in Inches w.g. RPM 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 CFM 377 194 - - - - - - - BHP 0.01 0.01 - - - - - - - Sones 2.0 1.4 - - - - - - - CFM 431 302 - - - - - - - BHP 0.02 0.
MODEL SDB BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER SIZE 10 Motor HP 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/3 1/3 1/3 Static Pressure in Inches w.g. RPM 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 CFM 586 423 - - - - - - - BHP 0.02 0.02 - - - - - - - Sones 3.1 2.6 - - - - - - CFM 669 537 244 - - - - - - BHP 0.02 0.03 0.03 - - - - - - Sones 4.1 3.5 3.
MODEL SDB BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER SIZE 12 Motor HP RPM 1/4 600 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/3 1/2 1/2 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 Static Pressure in Inches w.g. 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 CFM 660 425 - - - - - - - - BHP 0.01 0.02 - - - - - - - - Sones 2.5 2.1 - - - - - - - - CFM 770 585 - - - - - - - - BHP 0.02 0.03 - - - - - - - - Sones 3.
MODEL SDB BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER SIZE 14 Motor HP RPM 1/4 550 1/4 650 1/4 750 1/4 850 1/4 950 1/4 1050 1/3 1150 1/2 1250 1/2 1350 3/4 1450 3/4 1550 1 1650 1 1750 Static Pressure in Inches w.g. 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 CFM 1108 802 - - - - - - - - - BHP 0.03 0.03 - - - - - - - - - Sones 3.4 2.4 - - - - - - - - - CFM 1309 1070 - - - - - - - - - BHP 0.04 0.
MODEL SDB BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER SIZE 15 Motor HP RPM 1/4 500 1/4 600 1/4 700 1/4 800 1/4 900 1/3 1000 1/3 1100 1/2 1200 3/4 1300 3/4 1400 1 1500 1 1600 Static Pressure in Inches w.g. 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 CFM 1164 843 - - - - - - - - - BHP 0.02 0.03 - - - - - - - - - Sones 3.3 2.4 - - - - - - - - - CFM 1396 1146 543 - - - - - - - - BHP 0.04 0.05 0.
MODEL SDB BELT DRIVE CENTRIFUGAL DOWNBLAST ROOF EXHAUSTER SIZE 16 Motor HP RPM 1/4 550 1/4 650 1/4 750 1/4 850 1/3 950 1/2 1050 3/4 1150 3/4 1250 1 1350 1 1450 Static Pressure in Inches w.g. 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 CFM 1568 1275 - - - - - - - - - BHP 0.04 0.06 - - - - - - - - - Sones 4.4 3.5 - - - - - - - - - CFM 1853 1614 1292 - - - - - - - - BHP 0.07 0.08 0.10 - - - - - - - - Sones 6.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 28,000 CFM in high static pressure applications up to 1-1/4” w.g.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER CONSTRUCTION FEATURES AND OPTIONS Drives Sized for 150% of drive HP, adjustable pitch motor sheaves Aluminum Motor Cover Provides weather protection for motor compartment and easy access for servicing Motor Open drip-proof construction standard Motor Base Adjusts for maintaining proper belt tension Disconnect Switch Standard with ODP single speed motors Neoprene Vibration Isolators Reduce vibration and sound Bearings Air handling ball bearing type with cas
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Curb cap with integral deep spun inlet for efficient performance. • Heavy-gauge aluminum for extra strength. • Designed for maximum weather protection and attractive appearance. • Heavy-gauge motor support for rigidity and strength. • Neoprene isolators for reduction of vibration and sound. • Quick-Release latches on motor cover for easy access to motor compartment.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER OPTIONS/ACCESSORIES Automatic Belt Tensioner: Available on sizes 6-24, The Automatic Belt Tensioners eliminate the need for regular manual retensioning of drives, and the risk of inadvertently over-tensioning drive components is avoided and overall drive operating efficiency is enhanced. Benefits include reduction in startup and maintenance costs, increased belt life, increased drive efficiency, and ensure drive components do not snag obstructions.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER PERFORMANCE/DIMENSIONS SIZE 6 Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 11 11-1/2 14-3/4 20 -1/2 17-1/2 16-1/2 3-1/2 16-1/8 1-3/4 43 80 Drive Range RPM HP Tip Speed CFM / BHP @ Static Pressure / Sones 1/2 5/8 3/4 7/8 1 1-1/4 Catalog Number - - - - - - - - 601 700 1/4 2058 - - - - - - - - 602 750 1/4 2205 - - - - - - - - 603 800 1/4 2352 - - - - - - - - 604 850 1/4
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 8 Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 11 11-1/2 14-3/4 20 -1/2 17-1/2 16-1/2 3-1/2 16-1/8 1-3/4 42 80 RPM HP Tip Speed CFM / BHP @ Static Pressure / Sones Drive Range 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 1-1/4 Catalog Number 478 .01/1.9 - - - - - - - - - 801 650 1/4 1911 508 .01/2.2 252 .02/1.2 - - - - - - - - 802 690 1/4 2029 552 .02/2.8 338 .02/1.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 9 Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 11 11-1/2 14-3/4 20 -1/2 17-1/2 16-1/2 3-1/2 16-1/8 1-3/4 44 80 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 901 710 1/4 2277 - 902 750 1/4 2405 - - 903 790 1/4 2534 - - - 904 830 1/4 2662 - - - - 905 870 1/4 2790 - - - - - 906 910 1/4 2918 - - - - - - 907 950 1/4 3047 - - - - - - - 908 990 1/4 3175 699
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 11 Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 18 19-1/2 22-1/4 28-3/8 23 24 3-1/2 22-1/2 2 64 130 RPM HP Tip Speed CFM / BHP @ Static Pressure / Sones Drive Range 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 1-1/4 Catalog Number 771 .02/3.8 508 .03/2.8 - - - - - - - - 1101 670 1/4 2275 846 .03/4.6 613 .03/3.7 - - - - - - - - 1102 735 1/4 2489 921 .04/5.5 711 .04/4.7 436 .04/4.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 12 Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 18 19-1/2 22-1/4 28-3/8 23 24 3-1/2 22-1/2 2 65 130 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 1201 640 1/4 2371 - 1202 690 1/4 2556 - - 1203 740 1/4 2742 - - - 1204 790 1/4 2927 - - - - 1205 840 1/4 3112 - - - - - 1206 890 1/4 3297 390 .08/4.9 - - - - - 1207 940 1/4 3483 937 .13/6.6 621 .12/5.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 14 Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 18 19-1/2 22-1/4 28-3/8 23 24 3-1/2 22-1/2 2 71 140 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 1401 435 1/4 1732 - 1402 475 1/4 1891 - - 1403 525 1/4 2090 - - - 1404 575 1/4 2289 - - - - 1405 625 1/4 2488 - - - - - 1406 675 1/4 2687 - - - - - - 1407 725 1/4 2886 1017 .11/5.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 16 Dimensional Data Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 18 19-1/2 22-1/4 32-1/4 24 24 6 26-1/4 2-1/2 79 145 RPM HP Tip Speed CFM / BHP @ Static Pressure / Sones 1/4 3/8 1/2 5/8 3/4 7/8 1 1-1/4 Catalog Number 1578 .04/2.9 851 .04/1.8 - - - - - - - - 1601 425 1/4 2030 1726 .05/3.6 1118 .05/2.6 - - - - - - - - 1602 465 1/4 2221 1875 .06/4.3 1338 .07/3.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 18 Dimensional Data Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 24 24-3/4 27-3/4 32-1/4 24 29-1/2 4-1/2 26-1/4 2-1/2 96 160 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 1801 535 1/4 2556 - 1802 580 1/4 2771 - - 1803 625 1/4 2986 - - - 1804 670 1/4 3201 - - - - 1805 715 1/4 3416 - - - - - 1806 760 1/3 3631 1873 .30/9.8 - - - - - 1807 805 1/3 3846 2507 .38/11.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 20 Dimensional Data Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 24 24-3/4 27-3/4 36-3/4 24-1/2 29-1/2 4-1/2 26-1/4 2-1/2 98 215 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 2001 440 1/4 2460 - 2002 480 1/4 2683 - - 2003 520 1/4 2907 - - - 2004 560 1/4 3130 - - - - 2005 600 1/4 3354 - - - - - 2006 635 1/3 3550 2145 .33/8.3 1281 .26/7.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 24 Dimensional Data Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 30 30-3/4 33-3/4 41-1/4 26-1/2 35-3/4 8-1/2 30 2-1/2 155 290 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 2401 330 1/4 2102 - 2402 365 1/4 2325 - - 2403 400 1/4 2548 - - - 2404 450 1/4 2867 - - - - 2405 470 1/3 2994 - - - - - 2406 490 1/3 3121 2055 .32/8.6 - - - - - 2407 540 1/2 3440 3972 .48/9.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 30 Dimensional Data Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 36 37-1/4 40-3/4 58-3/8 37 42-1/2 5-1/2 41 2-1/2 265 465 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 3001 235 1/3 1871 - 3002 265 1/3 2110 - - 3003 295 1/3 2349 - - - 3004 325 1/3 2588 - - - - 3005 355 1/3 2827 - - - - - 3006 385 1/2 3066 2246 .38/6.8 - - - - - 3007 410 1/2 3265 5087 .60/7.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 36 Dimensional Data Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 36 37-1/4 40-3/4 58-3/8 37 42-1/2 10 41 2-1/2 275 475 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 3601 210 1/2 1945 - 3602 235 1/2 2177 - - 3603 260 1/2 2408 - - - 3604 285 1/2 2640 - - - - 3605 310 1/2 2871 - - - - - 3606 330 3/4 3057 - - - - - - 3607 355 3/4 3288 6450 .80/8.9 3321 .57/8.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 42 Dimensional Data Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 48 50-1/4 53-1/4 73 40-1/2 55 10 54-5/8 2-1/2 425 700 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 4201 180 1/2 1966 - 4202 195 1/2 2129 - - 4203 210 1/2 2293 - - - 4204 225 1/2 2457 - - - - 4205 240 1/2 2621 - - - - - 4206 260 3/4 2839 - - - - - - 4207 275 3/4 3003 4980 .63/9.
MODEL DB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER SIZE 48 Dimensional Data Damper OD Roof Opening Curb OD A B C D E F Fan Wt Ship Wt 48 50-1/4 53-1/4 73 40-1/2 55 13 54-5/8 2-1/2 550 830 CFM / BHP @ Static Pressure / Sones RPM HP Tip Speed 165 1/2 2037 175 1/2 2161 190 1/2 2347 200 3/4 2470 220 3/4 2655 230 1 2841 4807 240 1 2964 6153 0.9/9.6 4808 255 1-1/2 3149 12732 1.59/10.6 9568 1.4/10.8 4809 280 1-1/2 3335 15638 1.85/11.4 13535 1.78/11.
MODELS STXD & STXB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL ROOF EXHAUSTERS MODEL STXD DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 4,780 CFM in high static pressure applications up to 1-1/2” w.g.
MODELS STXD & STXB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTERS MODEL STXB BELT DRIVE CENTRIFUGAL ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 3,975 CFM in high static pressure applications up to 1-1/2” w.g.
MODELS STXD & STXB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Upblast Model Overview & Construction Features Model STXB - Belt Drive Size Range Motor HP Range CFM Range Static Pressure Mounting Warranty Model STXD - Direct Drive 8, 10, 12, 14, 15 & 16 1/4 to 1-1/2 200 to 3975 up to 1-1/2 in. w.g. Suitable for Roof or Wall 5 years/2 years for RHUL models Size Range Motor HP Range CFM Range Static Pressure 6, 7, 8, 10, 12, 14, 15 & 16 1/25 to 1-1/2 55 to 4780 up to 1-1/2 in. w.g.
MODELS STXD & STXB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Upblast Model Overview & Construction Features # Feature Description Heavy-gauge aluminum motor cover provides weather protection for 1 Motor Cover motor compartment. Heavy-gauge aluminum top with rolled bead for added strength and 2 Motor Cover Cap quick-release latches. Stainless steel latches for easy removal of motor cover cap for 3 Quick-Release Latches access to the motor compartment and motor.
MODELS STXD & STXB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTERS DIMENSIONS Dimensions in Inches Model STXD: Direct Drive Centrifugal Upblast C B D 2.0 A Size A B C D Roof Opening Curb O.D. Damper (O.D.) Average Ship Wt. Lbs.
MODELS STXD & STXB DIRECT DRIVE & BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTERS OPTIONS/ACCESSORIES Solid State Speed Control (STXD): S&P’s solid state control is matched to the motor and blower wheel to allow continuous reduction in performance allowing adjustments of airflow for system balancing. CFM is reduced in direct proportion to motor speed reduction. Speed control is available for 115 or 230 volt single phase. Exhauster performance can be controlled from the ventilated area.
MODEL STXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Curb cap with integral deep single piece spun inlet for efficient performance and prevention of leakage into ductwork. • Heavy-gauge aluminum housing and curb cap for strength and rigidity. Curb cap is galvanized steel on all UL762 units. • Stainless steel exterior fasteners. • Enclosed, ventilated motor compartment isolates motor from exhaust air.
MODEL STXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 6 Model HP RPM 1/10 900 STXD6C (1) 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1200 1350 1500 1650 900 1050 1200 STXD6 (1) 1/10 1050 1/10 1/10 1/10 1350 1500 1650 Static Pressure in Inches w.g. 0 .125 .25 .375 .5 .625 .75 CFM 125 92 - - - - - BHP 0.01 0.01 - - - - - Sones 2.1 1.7 - - - - - CFM 145 119 81 - - - - BHP 0.01 0.01 0.01 - - - - Sones 3.1 2.6 2.
MODEL STXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 7 HP 1/10 1/10 1/10 1/10 1/10 1/10 Static Pressure in Inches w.g. RPM 900 1050 1200 1350 1500 1650 0 .125 .25 .375 .5 .625 .75 CFM 242 150 - - - - - BHP 0.00 0.01 - - - - - Sones 2.4 1.9 - - - - - CFM 283 209 104 - - - - BHP 0.01 0.01 0.01 - - - - Sones 3.3 2.7 3.1 - - - - CFM 323 261 182 83 - - - BHP 0.01 0.01 0.02 0.02 - - - Sones 4.2 3.7 3.8 4.
MODEL STXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 8 HP 1/25 1/25 1/25 1/25 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1/4 1/4 Static Pressure in Inches w.g. RPM 700 850 1000 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 0 .125 .25 .375 .5 .625 .75 .875 CFM 379 205 - - - - - - BHP 0.01 0.01 - - - - - - Sones 2.3 1.6 - - - - - - CFM 460 342 - - - - - - BHP 0.01 0.
MODEL STXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 10 HP RPM 1/4 700 1/4 1/4 1/4 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 1/3 152 850 1000 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 Static Pressure in Inches w.g. 0 .125 .25 .375 .5 .625 .75 .875 1 CFM 587 410 - - - - - - - BHP 0.02 0.03 - - - - - - - Sones 3.2 2.4 - - - - - - - CFM 712 575 377 - - - - - - BHP 0.04 0.04 0.
MODEL STXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 12 HP 1/4 1/4 1/4 1/4 1/4 1/4 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 Static Pressure in Inches w.g. RPM 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 0 .125 .25 .375 .5 .625 .75 .875 1 CFM 998 833 642 - - - - - - 1.25 - BHP 0.05 0.06 0.07 - - - - - - - Sones 5.7 5.3 5.
MODEL STXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 14 HP 1/4 750 1/4 850 1/4 1/4 1 Static Pressure in Inches w.g. RPM 950 1100 1725 0 .125 .25 .375 .5 .625 .75 .875 1 1.25 CFM 1479 1246 930 - - - - - - - 1.5 - BHP 0.07 0.08 0.09 - - - - - - - - Sones 6.4 5.7 5.1 - - - - - - - - CFM 1677 1481 1240 868 - - - - - - - BHP 0.10 0.12 0.12 0.12 - - - - - - - Sones 8.1 7.4 6.7 6.
MODEL STXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 15 Motor HP 1/2 750 1/2 800 1/2 850 1/2 900 1/2 950 1/2 1000 1/2 1050 1/2 1100 1/2 1150 1-1/2 Static Pressure in Inches w.g. RPM 1750 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 1.75 CFM 1719 1515 1258 800 - - - - - - - - BHP 0.08 0.09 0.10 0.10 - - - - - - - - Sones 6.8 6.1 5.4 4.8 - - - - - - - - CFM 1834 1647 1404 1124 - - - - - - - - BHP 0.10 0.
MODEL STXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 16 Motor HP 1/2 750 1/2 800 1/2 850 1/2 900 1/2 950 1/2 1000 1/2 1050 1/2 1100 1/2 1150 1-1/2 Static Pressure in Inches w.g. RPM 1750 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 1.75 CFM 2108 1894 1633 1272 - - - - - - - - BHP 0.11 0.13 0.14 0.14 - - - - - - - - Sones 7.9 7.7 6.7 6.3 - - - - - - - - CFM 2248 2048 1815 1515 - - - - - - - - BHP 0.14 0.
MODEL STXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Curb cap with integral deep single piece spun inlet for efficient performance and prevention of leakage into ductwork. • Lifting lugs for easy and safe placement of the fan on the roof. • Heavy-gauge aluminum housing and curb cap for strength and rigidity. Curb cap is galvanized steel on all UL 762 units. • Adjustable motor base for proper belt tension and ease of adjustment.
MODEL STXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 8 Motor HP RPM 1/4 700 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/3 1/3 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 Static Pressure in Inches w.g. 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 CFM 376 201 - - - - - - - BHP 0.01 0.01 - - - - - - - Sones 2.1 1.3 - - - - - - - CFM 430 302 - - - - - - - BHP 0.02 0.
MODEL STXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 10 Motor HP 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/3 1/3 Static Pressure in Inches w.g. RPM 650 750 850 950 1050 1150 1250 1350 1450 1550 1650 1750 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 CFM 545 348 - - - - - - - BHP 0.01 0.02 - - - - - - - Sones 2.6 2.0 - - - - - - - CFM 629 468 - - - - - - - BHP 0.02 0.03 - - - - - - - Sones 3.6 2.
MODEL STXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 12 Motor HP RPM 1/4 800 1/4 1/4 1/4 1/4 1/4 1/4 1/3 1/3 1/2 1/2 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 Static Pressure in Inches w.g. 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 CFM 884 715 475 - - - - - - - BHP 0.03 0.04 0.04 - - - - - - - Sones 4.4 3.9 3.4 - - - - - - - CFM 995 849 666 318 - - - - - - BHP 0.05 0.06 0.06 0.
MODEL STXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 14 Motor HP 1/4 1/4 1/4 1/4 1/4 1/4 1/3 1/2 1/2 3/4 3/4 1 Static Pressure in Inches w.g. RPM 550 650 750 850 950 1050 1150 1250 1350 1450 1550 1650 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 CFM 1111 808 - - - - - - - - - BHP 0.03 0.03 - - - - - - - - - Sones 3.3 2.3 - - - - - - - - - CFM 1313 1081 - - - - - - - - - BHP 0.04 0.
MODEL STXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 15 Motor HP RPM 1/4 700 1/4 1/4 1/4 1/3 1/2 3/4 3/4 1 1 800 900 1000 1100 1200 1300 1400 1500 1600 Static Pressure in Inches w.g. 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 1.75 CFM 1612 1394 1126 - - - - - - - - - BHP 0.06 0.07 0.09 - - - - - - - - - Sones 5.5 4.8 4.4 - - - - - - - - - CFM 1842 1656 1448 1162 - - - - - - - - BHP 0.09 0.11 0.12 0.
MODEL STXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 15 HIGH PRESSURE Motor HP RPM 1/4 750 1/4 1/4 1/4 1/4 1/3 1/2 1/2 3/4 3/4 1 1 850 950 1050 1150 1250 1350 1450 1550 1650 1750 1850 Static Pressure in Inches w.g. 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 1.75 2 2.25 2.5 CFM 881 483 - - - - - - - - - - - BHP 0.07 0.07 - - - - - - - - - - - Sones 4.4 4.
MODEL STXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 16 Motor HP RPM 1/4 700 1/4 1/4 1/4 1/4 1/4 1/3 1/2 1/2 3/4 3/4 3/4 1 1 1 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400 Static Pressure in Inches w.g. 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 CFM 1988 1762 1494 977 BHP 0.09 0.10 0.12 0.12 - - - - - - - - - - - - - Sones 6.8 6.3 5.3 4.
MODEL STXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 16 HIGH PRESSURE Motor HP RPM 1/4 800 1/4 1/4 1/3 1/2 1/3 3/4 1 1 1 900 1000 1100 1200 1300 1400 1500 1600 1700 Static Pressure in Inches w.g. 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 1.75 - - - - - - - - - - - - 2 2.25 CFM 1294 1054 - BHP 0.11 0.12 - - - - - - - - - - Sones 6.2 5.7 - - - - - - - CFM 1560 1362 1140 603 - - - - - - - - BHP 0.15 0.16 0.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 35,000 CFM in high static pressure applications up to 3-1/4” w.g.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER STANDARD CONSTRUCTION FEATURES AND OPTIONS Model TXB Spun Top Easily removable for servicing. Enclosed Motor Compartment Isolates motor and drives from exhaust air. Drives Sized for 150% of drive HP, adjustable pitch sheaves. Oversized Vent Tube For maximum motor cooling. Disconnect Switch Standard with single speed dripproof and totally enclosed motors. Motor Open drip-proof construction standard. 1 year warranty.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER STANDARD CONSTRUCTION FEATURES AND OPTIONS Model TXB-UL762 Restaurant Exhaust Enclosed Motor Compartment Isolates motor and drives from exhaust air. Spun Top Easily removable for servicing. Drives Sized for 150% of drive HP, adjustable pitch sheaves. Oversized Vent Tube For maximum motor cooling. Motor Open drip-proof construction standard. 1 year warranty. Motor Base Motor is adjustable for proper belt tension.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Curb cap with integral deep single piece spun inlet for efficient performance and prevention of leakage into ductwork. • Heavy-gauge aluminum housing and curb cap for strength and rigidity. Curb cap is galvanized steel on all UL 762 units. • Adjustable motor base for proper belt tension and ease of adjustment. • Enclosed ventilated motor/drive compartment isolates motor and drives from exhaust air.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER OPTIONS/ACCESSORIES Motor Pulley Fan Pulley Automatic Belt Tensioner: Available on sizes 8-24, Belt Tensioner Pulley The Automatic Belt Tensioners eliminate the need for Belt Tensioner Arm regular manual retensioning of drives, and the risk Belt Tensioner of inadvertently over-tensioning drive components Bracket Motor Bracket is avoided and overall drive operating efficiency is enhanced.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER PERFORMANCE/DIMENSIONS SIZE 8 B Dimensions (in.) B C D E 16-1/2 24 24 27 1-3/4 Dimensional Data D C A Damper ID OD Roof Opening 11 11 11-3/4 Metal Thickness Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 14-3/4 .063 .050 .050 68 E A CFM / BHP @ Static Pressure / Sones 0 1/8 431 0.01/3.8 485 0.02/4.6 512 0.02/5.1 538 0.03/5.6 565 0.03/6.1 592 0.04/6.6 619 0.04/7.2 646 0.05/7.8 673 0.05/8.4 700 0.06/9.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 10 B Dimensions (in.) B C D E 16-1/2 27 26 29 1-3/4 Dimensional Data D C A Damper ID OD Roof Opening 11 11 11-3/4 Metal Thickness Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 14-3/4 .063 .050 .050 70 E A CFM / BHP @ Static Pressure / Sones 0 1/8 628 0.02/2.9 667 0.03/3.3 706 0.03/3.7 746 0.04/4.2 785 0.05/4.8 863 0.06/5.8 903 0.07/6.3 981 0.09/7.5 1020 0.10/8.0 1099 0.13/9.3 1128 0.14/9.7 1236 0.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 12 B Dimensions (in.) B C D E 24 31-1/2 26 29 2-1/2 Dimensional Data ID OD Roof Opening Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 18 18 19-1/4 22-1/4 .063 .050 .050 90 D C A Damper Metal Thickness E A CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 3/8 1/2 1055 0.09/7.7 1120 0.10/8.7 1185 0.12/9.8 1251 0.14/10.6 1316 0.17/11.5 1346 0.18/12.0 1381 0.19/12.5 1411 0.21/13.0 1446 0.22/13.6 1477 0.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 15 B Dimensions (in.) B C D E 24 31-1/2 26 29 2-1/2 Dimensional Data ID OD Roof Opening Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 18 18 19-1/4 22-1/4 .063 .050 .050 95 D C A Damper Metal Thickness E A CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 3/8 1/2 5/8 3/4 1 1-1/4 1-1/2 1-3/4 2 Catalog Number RPM HP Tip Speed 1525 0.09/6.8 1710 0.12/8.3 1895 0.17/9.9 1938 0.18/10.3 1982 0.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 15 - HIGH PRESSURE Dimensions (in.) B B C D E 24 31-1/2 26 29 2-1/2 Dimensional Data D C A Damper ID OD Roof Opening 18 18 19-1/4 Metal Thickness Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 22-1/4 .063 .050 .050 95 E A CFM / BHP @ Static Pressure / Sones 1/4 3/8 1033 0.09/5.4 1266 0.13/7.5 1479 0.17/9.7 1539 0.18/10.4 1586 0.19/11.0 1645 0.21/11.7 1692 0.22/12.3 1749 0.24/13.1 1795 0.25/13.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 16 B Dimensions (in.) B C D E 24 31-1/2 26 29 2-1/2 Dimensional Data D C A Damper ID OD Roof Opening 18 18 19-1/4 Metal Thickness Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 22-1/4 .063 .050 .050 100 E A CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 3/8 2223 0.15/7.9 2289 0.16/8.4 2354 0.18/8.8 2485 0.21/9.8 2550 0.23/10.2 2616 0.24/10.7 2681 0.26/11.2 2747 0.28/11.7 2877 0.32/12.8 2943 0.35/13.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 18 Dimensions (in.) B B C D E 29-1/2 37-3/4 28-1/2 32 2-1/2 Dimensional Data Metal Thickness ID OD Roof Opening Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 24 24 24-3/4 27-3/4 .080 .050 .
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 18 - HIGH PRESSURE Dimensions (in.) B B C D E 29-1/2 37-3/4 28-1/2 32 2-1/2 Dimensional Data D C A Damper ID OD Roof Opening 24 24 24-3/4 Metal Thickness Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 27-3/4 .080 .050 .050 120 E A CFM / BHP @ Static Pressure / Sones 5/8 1326 0.24/13.1 1479 0.26/13.5 1611 0.29/14.0 1731 0.31/14.5 1842 0.33/15.0 2021 0.37/15.9 2164 0.41/16.7 2323 0.45/17.8 2456 0.50/19.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 20 B Dimensions (in.) B C D E 29-1/2 37-3/4 28-1/2 32 2-1/2 Dimensional Data D C A ID OD Roof Opening Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 24 24 24-3/4 27-3/4 .063 .050 .050 120 Damper Metal Thickness E A CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 2813 0.15/7.6 3322 0.24/10.3 3429 0.26/10.7 3617 0.31/11.4 3777 0.35/11.9 3965 0.41/12.8 4152 0.47/13.7 4286 0.52/14.4 4420 0.57/15.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 20 - HIGH PRESSURE Dimensions (in.) B A B C D E 29-1/2 37-3/4 28-1/2 32 2-1/2 Dimensional Data ID OD Roof Opening Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 24 24 24-3/4 27-3/4 .080 .050 .050 120 Damper D C Metal Thickness E A CFM / BHP @ Static Pressure / Sones 3/8 1/2 5/8 2313 0.30/9.4 2612 0.36/10.4 2890 0.44/11.5 3156 0.52/12.7 3284 0.57/13.4 3437 0.63/14.6 3586 0.69/15.8 3734 0.75/16.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 24 B Dimensions (in.) B C D E 35-1/2 47-1/4 31-1/2 42 2-1/2 Dimensional Data ID OD Roof Opening Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 30 30 30-3/4 33-3/4 .10 .050 .050 245 D C A Damper Metal Thickness E A CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 3681 0.15/7.3 4141 0.22/9.1 4371 0.26/9.8 4555 0.29/10.3 4601 0.30/10.4 4831 0.35/11.1 5015 0.39/11.6 5199 0.44/12.2 5291 0.46/12.6 5705 0.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 24 - HIGH PRESSURE B Dimensions (in.) B C D E 47-1/4 31-1/2 42 2-1/2 Dimensional Data D C A 35-1/2 Damper ID OD Roof Opening 30 30 30-3/4 Metal Thickness Curb OD Curb Cap 33-3/4 .10 Wind Motor Band Cover .050 Avg. Ship Wt. (lbs.) .050 245 E A CFM / BHP @ Static Pressure / Sones 1/2 5/8 2597 0.38/7.7 3129 0.47/9.0 3364 0.52/9.7 3639 0.58/10.7 3848 0.63/11.5 4294 0.76/13.3 4483 0.82/14.0 4668 0.88/14.8 4850 0.95/15.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 30 B Dimensions (in.) B C D E 42-1/2 56-3/4 41 45 2-1/2 Dimensional Data ID OD Roof Opening Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 36 36 37-3/4 40-3/4 .090 .050 .050 365 D C A Damper Metal Thickness E A CFM / BHP @ Static Pressure / Sones 1/8 3720 0.16/3.8 4477 0.23/4.9 5280 0.32/6.2 5572 0.36/6.7 5860 0.41/7.2 6240 0.47/7.9 6615 0.54/8.6 6987 0.62/9.3 7356 0.70/10.0 7631 0.77/10.7 7904 0.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 30 - HIGH PRESSURE B Dimensions (in.) A B C D E 42-1/2 56-3/4 41 45 2-1/2 Dimensional Data D C Damper ID OD Roof Opening 36 36 37-3/4 Metal Thickness Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 40-3/4 .090 .050 .050 365 E A CFM / BHP @ Static Pressure / Sones 1/4 3328 0.24/4.3 4276 0.34/ 5.5 4666 0.39/6.2 4942 0.43/6.7 5298 0.49/7.3 5643 0.56/8.0 5980 0.63/8.7 6311 0.70/9.5 6638 0.79/10.3 6880 0.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 36 B Dimensions (in.) B C D E 42-1/2 66 44 48 2-1/2 Dimensional Data ID OD Roof Opening Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 36 36 37-3/4 40-3/4 .090 .050 .050 365 D C A Damper Metal Thickness E A CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 7797 0.30/5.3 8953 0.45/6.8 9386 0.52/7.3 9819 0.60/7.9 10252 0.68/8.5 10685 0.77/9.1 10974 0.83/9.5 11407 0.93/10.2 11985 1.08/11.0 12418 1.21/11.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 36 - HIGH PRESSURE Dimensions (in.) B B C D E 42-1/2 66 44 48 2-1/2 Dimensional Data D C A Damper ID OD Roof Opening 36 36 37-3/4 Metal Thickness Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 40-3/4 .090 .050 .050 365 E A CFM / BHP @ Static Pressure / Sones 1/2 5889 0.83/7.6 6412 0.90/7.9 7078 1.02/8.4 7862 1.17/9.2 8575 1.33/9.9 9240 1.50/10.7 9715 1.63/11.3 10021 1.72/11.8 10467 1.86/12.5 10760 1.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 42 B Dimensions (in.) B C D E 55 72-1/2 48 52 2-1/2 Dimensional Data ID OD Roof Opening Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 48 48 50-1/4 53-1/4 .100 .050 .050 385 D C A Damper Metal Thickness E A CFM / BHP @ Static Pressure / Sones 0 1/8 10306 0.28/6.8 11852 0.43/8.2 12625 0.52/9.0 13656 0.66/10.0 14429 0.78/10.8 14944 0.86/11.4 15459 0.96/11.9 16232 1.11/12.6 17005 1.27/13.4 17521 1.
MODEL TXB BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER SIZE 48 B Dimensions (in.) D C A B C D E 55 78-3/4 52 55 2-1/2 Dimensional Data Damper E ID OD Roof Opening 48 48 50-1/4 Metal Thickness Curb OD Curb Cap Wind Band Motor Cover Avg. Ship Wt. (lbs.) 53-1/4 .100 .050 .050 490 A CFM / BHP @ Static Pressure / Sones 0 1/8 11713 0.33/3.5 12402 0.39/3.9 13091 0.46/4.3 13091 0.46/4.3 14813 0.67/5.4 15847 0.82/6.1 16536 0.93/6.0 17225 1.05/7.0 17914 1.18/7.4 18603 1.32/7.
MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 3,400 CFM in high static pressure applications up to 1-1/4” w.g.
MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER STANDARD CONSTRUCTION FEATURES AND OPTIONS Model TXD Spun Top Easily removable for servicing. Enclosed Motor Compartment Isolates motor from exhaust air. Motor Open drip-proof construction standard. 1 year warranty. Oversized Vent Tube For maximum motor cooling. Neoprene Isolators Reduce vibration and sound. Spun Shroud Provides maximum air performance. Mounted Disconnect Switch Standard with single speed drip-proof motors.
MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Curb cap with integral deep single piece spun inlet for efficient performance and prevention of leakage into ductwork. • Heavy-gauge aluminum housing and curb cap for strength and rigidity. Curb cap is galvanized steel on all UL762 units. • Stainless steel alloy exterior fasteners. • Enclosed, ventilated motor compartment isolates motor from exhaust air.
MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER OPTIONS/ACCESSORIES Solid State Speed Control: S&P’s solid state control is matched to allow smooth RPM variation and adjustment of airflow for system balancing. CFM is reduced in direct proportion to motor speed reduction. Speed controllers available for 115/1 or 230/1 operation. Exhauster performance can be controlled from the ventilated area.
MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER PERFORMANCE/DIMENSIONS TXD 6 AND 8 DAMPER OD ROOF OPENING CURB OD A B C D FAN WT SHIP WT 11 12 15 24 22 16-1/2 2 45 76 TXD 8 TXD 6 CFM / BHP @ Static Pressure / Sones 0 1/8 253 .02/3.1 274 .03/3.6 294 .03/4.2 315 .04/4.9 335 .05/5.6 356 .06/6.3 377 .07/7.0 397 .08/7.8 410 .09/8.2 533 .01/2.3 604 .02/3.2 674 .03/4.1 745 .03/5.0 815 .04/5.9 886 .06/6.8 960 .07/7.8 1031 .09/8.8 1101 .11/9.9 1172 .13/11.0 1242 .16/12.1 1313 .19/13.
MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER TXD 10 DAMPER OD ROOF OPENING CURB OD A B C D FAN WT SHIP WT 11 12 15 27-1/4 22 16-1/2 2 70 105 CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 Catalog Number HP RPM Tip Speed 580 .02/2.7 357 .02/3.0 - - - - - - - TXD-102511SC 1/4 680 2122 656 .02/3.9 468 .03/4.2 139 .02/3.8 - - - - - - TXD-102511SC 1/4 770 2402 695 .03/4.5 518 .03/4.8 268 .03/4.
MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER TXD 12 DAMPER OD ROOF OPENING CURB OD A B C D FAN WT SHIP WT 18 19-1/4 22-1/4 31-1/2 23 24 2 80 115 CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 1-1/4 Catalog Number HP RPM Tip Speed 964 .03/4.3 712 .03/3.3 352 .03/2.5 - - - - - - - TXD-1225SC 1/4 680 2519 1028 .03/4.9 797 .03/3.9 492 .04/3.1 - - - - - - - TXD-1225SC 1/4 725 2686 1092 .04/5.5 881 .05/4.5 610 .05/3.
MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER TXD 14 AND 15 DAMPER OD ROOF OPENING CURB OD A B C D FAN WT SHIP WT 18 19-1/4 22-1/4 31-1/2 23 24 2 85 120 TXD 15 TXD 14 CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 1-1/4 Catalog Number HP RPM Tip Speed 983 .04/3.6 680 .05/3.1 338 .04/16 - - - - - - - TXD-1425SC 1/4 650 2514 1058 .05/4.4 784 .06/3.9 461 .06/3.6 - - - - - - - TXD-1425SC 1/4 700 2707 1134 .06/5.
MODEL CWD DIRECT DRIVE CENTRIFUGAL SIDEWALL EXHAUSTER MODEL FEATURES • Exhaust air up to 3,360 CFM in high static pressure applications up to 1” w.g.
MODEL CWD DIRECT DRIVE CENTRIFUGAL SIDEWALL EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Integral spun inlet for efficient performance. • Spun aluminum dome for weather protection and attractive appearance. • Motor support of heavy-gauge aluminum for rigidity and strength. • Ventilated motor compartment with motor out of air stream for long trouble-free service. • Dome easily removes for access to motor compartment. • Water-tight construction. • Duct connection provided at wheel inlet.
MODEL CWD DIRECT DRIVE CENTRIFUGAL SIDEWALL EXHAUSTER OPTIONS/ACCESSORIES Solid State Speed Control: Available with direct drive models. Control is matched to the motor and blower wheel to allow reduction in performance from full motor speed to 60% of full speed. CFM is reduced in direct proportion to motor speed reduction. Exhauster performance can be controlled from the ventilated area. Motor Operated Damper: Motor operated aluminum damper for positive closure against backdraft.
MODEL CWD DIRECT DRIVE CENTRIFUGAL SIDEWALL EXHAUSTER PERFORMANCE/DIMENSIONS SIZES 7, 8 & 9 Size A B C D E G Avg. Ship Wt. (lbs.) 7 15 8 5-15/16 1-1/2 8 8 12 8 20 9 9-15/16 2 12 11 20 9 26 13-1/2 11-15/16 3 15 14 37 CWD 9 CWD 8 CWD 7 CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 Catalog Number HP RPM Tip Speed 152 .02/2.3 84 .01/1.5 - - - - - - - 070A S 1/25 930 1723 175 .02/3.1 120 .02/2.
MODEL CWD DIRECT DRIVE CENTRIFUGAL SIDEWALL EXHAUSTER SIZES 10 & 11 Size A B C D CWD 10 G Avg. Ship Wt. (lbs.) 10 26 13-1/2 11-15/16 3 15 14 37 11 30 15-1/2 13-15/16 3 17-1/2 14 50 CFM / BHP @ Static Pressure / Sones CWD 11 E 0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 Catalog Number HP RPM Tip Speed 629 .04/3.0 326 .03/2.6 - - - - - - - 101A S 1/4 685 2093 734 .05/4.2 474 .04/3.7 224 .04/3.6 - - - - - - 101A S 1/4 800 2444 826 .07/5.3 618 .07/4.
MODEL CWD DIRECT DRIVE CENTRIFUGAL SIDEWALL EXHAUSTER SIZES 12, 14 & 16 Size A B C D E G Avg. Ship Wt. (lbs.) 12 30 15-1/2 13-15/16 3 17-1/2 14 50 14 36 16-1/2 17-15/16 4 22 18 84 16 36 16-1/2 17-15/16 4 22 18 84 CWD 16 CWD 14 CWD 12 CFM / BHP @ Static Pressure / Sones 0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 Catalog Number HP RPM Tip Speed 986 .07/5.4 670 .06/3.6 365 .05/3.1 - - - - - - 121A S 1/4 685 2471 1152 .12/6.9 885 .10/5.4 621 .09/4.1 348 .
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN MODEL FEATURES • Supply air to over 12,000 CFM in static pressure capabilities to 2” w.g.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN CONSTRUCTION/SPECIFICATION CHECKLIST Blower • Statically and dynamically balanced forward curved wheel. • 12-gauge galvanized steel blower plate/discharge opening. • 18-gauge galvanized steel housing. • Prepunched mounting holes. • Conduit opening for wiring from below unit. Motors • 1 year warranty. • Brands are nationally recognized and locally serviced. • Single speed open drip-proof are standard.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN OPTIONS/ACCESSORIES Insulated Hood: High performance and ecologically friendly fiberglass free insulation only. Intake Extension: Extensions are available for all size KSF fans to provide NFPA required clearance from the exhaust fan on factory supplied common curbs. Extensions are made from heavy-gauge galvanized steel and require equipment supports on the intake end.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN NFPA96 INSTALLATION AND COMMON CURB ADAPTOR Typical Installation NFPA96 requires a 10 foot minimum distance between the exhaust fan and supply fan intake. The intake extension (optional) provides this clearance. Also required are hinged curb caps on the exhaust fan and some areas require a vented curb extension.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN PERFORMANCE/DIMENSIONS KSF9 MODEL CFM KSF 375 475 575 675 775 875 975 1075 1175 1275 9 1375 1475 1575 1675 1775 1875 1975 2075 2175 2275 2375 GC_KSF_0313 OV 426 540 653 767 881 994 1108 1222 1335 1449 1563 1676 1790 1903 2017 2131 2244 2358 2472 2585 2699 Static Pressure in Inches w.g. 1/2 5/8 3/4 1 1 1/4 1 1/2 1/8 1/4 3/8 RPM 486 - - - - - - - - 2 - BHP 0.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN KSF10 MODEL CFM KSF 1050 1150 1250 1350 1450 1550 1650 1750 1850 1950 10 2050 2150 2250 2350 2450 2550 2650 2750 2850 2950 3050 208 GC_KSF_0313 OV 981 1075 1168 1262 1355 1449 1542 1636 1729 1822 1916 2009 2103 2196 2290 2383 2477 2570 2664 2757 2850 Static Pressure in Inches w.g. 3/8 1/2 5/8 3/4 1 1/8 1/4 RPM 533 - - - - - - 1 1/4 1 1/2 - - BHP 0.11 - - - - - - - - Sones 7.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN KSF12 MODEL CFM KSF 1150 1350 1600 1800 2000 2200 2400 2600 2700 2800 OV 767 900 1067 1200 1333 1467 1600 1733 1800 1867 12 2900 3000 3100 3200 3400 3600 3800 4000 4200 4400 GC_KSF_0313 1933 2000 2067 2133 2267 2400 2533 2667 2800 2933 Static Pressure in Inches w.g. 3/8 1/2 5/8 3/4 1 1/8 1/4 RPM 378 495 - - - - - 1 1/4 1 1/2 - - BHP 0.1 0.17 - - - - - - - Sones 3.5 5.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN KSF15 MODEL CFM KSF 1625 2025 2425 2825 3230 3640 3840 4045 4245 15 4445 4645 4850 5050 5200 5400 5600 5800 6000 6400 210 GC_KSF_0313 OV 763 951 1138 1326 1516 1709 1803 1899 1993 2087 2181 2277 2371 2441 2535 2629 2723 2817 3005 Static Pressure in Inches w.g. 1/2 5/8 3/4 1 1 1/4 1 1/2 1/8 1/4 3/8 RPM 355 441 517 - - - - - - 2 - BHP 0.12 0.18 0.25 - - - - - - - Sones 5.3 6.5 8.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN KSF18 MODEL CFM KSF 2200 2400 2800 3000 3400 3600 4200 4600 5200 5400 18 5800 6000 6400 6600 7000 7200 OV 748 816 952 1020 1156 1224 1429 1565 1769 1837 1973 2041 2177 2245 2381 2449 Static Pressure in Inches w.g. 1/2 5/8 3/4 1 1 1/4 1 1/2 1/8 1/4 3/8 RPM 324 386 - - - - - - - 2 - BHP 0.15 0.21 - - - - - - - - Sones 5.3 6.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN KSF20 MODEL CFM KSF 2600 3000 3400 3800 4600 5000 5400 5800 6600 7000 20 7400 8200 8600 9200 9600 10000 OV 652 752 852 952 1153 1253 1353 1454 1654 1754 1855 2055 2155 2306 2406 2506 Static Pressure in Inches w.g. 1/2 5/8 3/4 1 1 1/4 1 1/2 1/8 1/4 3/8 RPM 245 307 359 - - - - - - 2 - BHP 0.14 0.23 0.32 - - - - - - - Sones 4.1 5.8 7.
MODEL KSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN DIMENSIONS Model Size Damper OD Roof Opening Curb OD Curb Cap ID A B C D Ship Wt KSF 9 16 19-1/2 22-3/4 24 24-1/4 24-1/2 17-7/8 19 215 KSF 10 20 23-1/2 26-1/2 28 27-3/8 28-1/2 21-1/8 22-1/2 245 KSF 12 24 28 30-1/2 32 32-3/4 32-1/2 26-1/2 27-7/8 255 KSF 15 24 28 30-1/2 32 37-3/8 32-1/2 34-1/4 30-1/8 310 KSF 18 27 32 34-5/8 36 41-3/8 36-1/2 38-1/4 33-3/8 350 KSF 20 42 46-1/2 49 51 49-1/2 51
MODELS CSF & LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS MODEL FEATURES Model CSF Hooded Design • Supply air to over 13,000 CFM in static pressure capabilities to 2” w.g.
MODELS CSF & LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS CONSTRUCTION/SPECIFICATION CHECKLIST Blower/Housing • Statically and dynamically balanced forward curved wheel. • 12-gauge galvanized steel blower plate/discharge opening. • Heavy-gauge galvanized steel housing. • Prepunched mounting holes. • Conduit opening for wiring from below unit. Hooded/Louvered Top • Heavy-gauge aluminum louvered design. (LSF) • Heavy-gauge galvanized steel hood. (CSF) • Quick-release latches for removal from housing.
MODELS CSF & LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS OPTIONS/ACCESSORIES Roof Curb: Prefabricated heavy-gauge galvanized steel, welded construction, 12” high with 1-1/2” wood nailer. Options include burglar bars, single and double pitch construction, and additional curb heights. Motor Operated Damper: Motor operated aluminum damper for positive closure against backdraft (counter balanced).
MODELS CSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS CSF PERFORMANCE CSF 9 MODEL CFM CSF OV 1/8 RPM 475 575 675 775 875 975 1075 1175 1275 1375 540 653 767 881 994 1108 1222 1335 1449 1563 9 1475 1575 1675 1775 1875 1975 2075 2175 2275 1676 1790 1903 2017 2131 2244 2358 2472 2585 440 Static Pressure in Inches w.g. 1/4 3/8 1/2 5/8 3/4 - - - - - 1 - BHP 0.03 - - - - - - Sones 12.3 - - - - - - RPM 445 - - - - - - BHP 0.
MODELS CSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS CSF 10 MODEL CFM CSF 700 825 950 654 771 888 1075 1005 1200 1121 1325 1238 1450 1355 1575 1472 1700 1589 1825 1706 10 1950 1822 2075 1939 2200 2056 2325 2173 2450 2290 2575 2407 2700 2523 2825 2640 2950 2757 3075 2874 3200 2991 218 Static Pressure in Inches w.g. OV GC_CSF-LSF_0113 1/8 1/4 3/8 1/2 5/8 3/4 1 RPM 377 516 - - - - - 1-1/4 1-1/2 - - 2 - BHP 0.04 0.07 - - - - - - - - Sones 3.3 5.
MODELS CSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS CSF12 MODEL CFM CSF 1150 1300 1450 767 867 967 1600 1067 1750 1167 1900 1267 2050 1367 2200 1467 2350 1567 2500 1667 12 Static Pressure in Inches w.g. OV 2650 1767 2800 1867 2950 1967 3100 2067 3250 2167 3400 2267 3550 2367 3700 2467 3850 2567 4000 2667 4150 2767 GC_CSF-LSF_0113 1/8 1/4 3/8 1/2 5/8 3/4 1 RPM 338 - - - - - - 1-1/4 1-1/2 - - 2 - BHP 0.08 - - - - - - - - - Sones 3.
MODELS CSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS CSF 15 MODEL CFM CSF 1625 1825 2125 763 857 998 2325 1092 2625 1232 2825 1326 3125 1467 3325 1561 3625 1702 15 3825 1796 4125 1937 4325 2031 4625 2171 4825 2265 5125 2406 5325 2500 5625 2641 5825 2735 6125 2876 220 Static Pressure in Inches w.g. OV GC_CSF-LSF_0113 1/8 1/4 3/8 1/2 5/8 3/4 1 RPM 285 - - - - - - 1-1/4 1-1/2 - - 2 - BHP 0.1 - - - - - - - - - Sones 3.
MODELS CSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS CSF18 MODEL CSF CFM 2250 2600 2950 3300 3650 4000 4350 4700 5050 765 884 1003 1122 1241 1361 1480 1599 1718 18 5400 5750 6100 6450 6800 7150 7500 7850 8200 Static Pressure in Inches w.g. OV 1837 1956 2075 2194 2313 2432 2551 2670 2789 GC_CSF-LSF_0113 1/8 1/4 3/8 1/2 5/8 3/4 1 RPM 253 - - - - - - 1-1/4 1-1/2 - - 2 - BHP 0.14 - - - - - - - - - Sones 2.
MODELS CSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS CSF18 Cont. MODEL CSF CFM 8550 8900 9250 18 9600 9950 10300 10650 222 Static Pressure in Inches w.g. OV 2908 3027 3146 3265 3384 3503 3622 GC_CSF-LSF_0113 1/8 1/4 3/8 1/2 5/8 3/4 1 RPM 647 673 697 721 744 767 812 1-1/4 1-1/2 856 900 987 2 BHP 3.81 4.07 4.31 4.55 4.79 5.03 5.51 6.01 6.51 7.58 Sones 36 35 30 28 27 27 27 27 28 29 RPM 672 696 720 743 766 788 831 874 916 - BHP 4.28 4.
MODELS CSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS CSF20 MODEL CSF CFM 2800 3340 3880 4420 4960 5500 6040 6580 7120 20 7660 8200 8740 9280 9820 10360 10900 11440 11980 12520 Static Pressure in Inches w.g. OV 698 833 968 1102 1237 1372 1506 1641 1776 1910 2045 2180 2314 2449 2584 2718 2853 2988 3122 GC_CSF-LSF_0113 1/8 1/4 3/8 1/2 5/8 3/4 1 RPM 223 288 342 - - - - 1-1/4 1-1/2 - - 2 - BHP 0.16 0.25 0.35 - - - - - - - Sones 3.7 5.
MODELS LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS LSF PERFORMANCE LSF 9 MODEL CFM LSF 475 575 675 775 875 975 1075 1175 1275 1375 OV 540 653 767 881 994 1108 1222 1335 1449 1563 9 1475 1575 1675 1775 1875 1975 2075 2175 2275 2375 224 1676 1790 1903 2017 2131 2244 2358 2472 2585 2699 GC_CSF-LSF_0113 1/8 Static Pressure in Inches w.g. 1/4 3/8 1/2 5/8 3/4 - - - - - 1 RPM 431 - BHP 0.03 - - - - - - Sones 4.
MODELS LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS LSF 10 MODEL CFM LSF 950 888 1075 1005 1200 1121 1325 1238 1450 1355 1575 1472 1700 1589 1825 1706 1950 1822 10 Static Pressure in Inches w.g. OV 2075 1939 2200 2056 1/8 1/4 3/8 1/2 5/8 3/4 1 RPM 421 - - - - - - - - BHP 0.07 - - - - - - - - Sones 5.5 - - - - - - - - RPM 444 - - - - - - - - BHP 0.09 - - - - - - - - Sones 6.
MODELS LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS LSF 12 MODEL LSF CFM 1450 1600 1750 1900 2050 Static Pressure in Inches w.g. OV 967 1067 1167 1267 1367 1/8 1/4 3/8 1/2 5/8 3/4 1 1-1/4 RPM 391 478 575 - - - - - BHP 0.14 0.2 0.28 - - - - - Sones 6.4 8 11.1 - - - - - RPM 414 492 576 - - - - - BHP 0.18 0.24 0.31 - - - - - Sones 7.5 8.6 11.2 - - - - - RPM 439 510 583 663 - - - - BHP 0.22 0.28 0.36 0.
MODELS LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS LSF 15 MODEL LSF CFM 1625 1825 2125 2325 2625 2825 3125 3325 3625 15 3825 4125 Static Pressure in Inches w.g. OV 763 857 998 1092 1232 1326 1467 1561 1702 1796 1937 1/8 1/4 3/8 1/2 5/8 3/4 1 RPM 293 - - - - - - - - BHP 0.1 - - - - - - - - Sones 4.5 - - - - - - - - RPM 305 390 - - - - - - - BHP 0.13 0.19 - - - - - - - Sones 5.1 6.
MODELS LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS LSF 18 MODEL LSF 18 CFM OV 2250 765 2600 884 2950 1003 3300 1122 3650 1241 4000 1361 4350 1480 4700 1599 5050 1718 5400 1837 5750 1956 6100 2075 6450 2194 6800 2313 7150 2432 7500 2551 7850 2670 8200 2789 8550 2908 8900 3027 9250 3146 9600 3265 9950 3384 10300 3503 10650 3622 228 GC_CSF-LSF_0113 RPM BHP Sones RPM BHP Sones RPM BHP Sones RPM BHP Sones RPM BHP Sones RPM BHP Sones RPM BHP Sones RPM BHP
MODELS LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS LSF 20 MODEL LSF CFM 2800 3340 3880 4420 4960 5500 Static Pressure in Inches w.g. OV 698 833 968 1102 1237 1372 1/8 1/4 3/8 1/2 5/8 3/4 1 RPM 222 - - - - - - - - - BHP 0.15 - - - - - - - - - Sones 3.5 - - - - - - - - - RPM 239 297 350 - - - - - - - BHP 0.21 0.31 0.42 - - - - - - 1506 - 4.6 5.8 7.2 - - - - - - - RPM 259 312 359 405 - - - - - - BHP 0.3 0.
MODELS CSF & LSF BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FANS DIMENSIONS CSF Discharge Opening Model Size A Housing OD B Overall Width C Overall Height D Intake Height Roof Opening E Curb Cap ID Damper OD Discharge Opening Filter Size/No. No. Tiers Avg. Ship Weight (lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN MODEL FEATURES • Exhaust air up to 24,000 CFM in high static pressure applications up to 3-1/2” w.g.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN CONSTRUCTION/SPECIFICATION CHECKLIST Blower/Housing • Aluminum, non-overloading, backward inclined centrifugal wheel statically and dynamically balanced. • Deep spun venturi inlet. • Heavy-gauge galvanized steel housing. • Integral inlet and outlet duct collars. • Universal mounting - horizontal, vertical, or any angle. • Motors and drives out of the airstream. • Removable drive and bearing covers for easy access.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN OPTIONS/ACCESSORIES Mounted and Wired Disconnect Switch Belt Guard Vibration Isolators / Mounting Brackets Insulated Housing (Steel housing only).
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN Hanging Bracket/ Mounting Foot with Hanging Spring Isolator Hanging Spring Isolators Assorted Disconnects Backdraft Damper 234 Hanging Rubber in Shear Isolators Heavy-duty Disconnect Insulated Housing
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN FILTER BOX OPTIONS Features • Designed for use with SQB Fans • Designed to handle 1” or 2” filters • Galvanized or aluminum construction up to size 24 • Galvanized construction sizes 30-42 • Standard filter is washable aluminum • MERV 7 (1”) or MERV 8 (2”) disposable pleated filters available by special quote • Removable side panels for easy access to filters C D A 1" 1" B Dimensions - Filter Box with 1" Aluminum Filters Fan Size Avg. Ship Wgt.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN FILTER BOX OPTIONS Cont. PRESSURE LOSS GUIDE FOR 1” FILTER BOX Use the estimated pressure drop graphs to help select the proper fan that will deliver the desired airflow. Enter the graph from the bottom at the specified CFM and move vertically upward to the fan curve for the desired size, then horizontally to the left and read the estimated static pressure drop resulting from these typical accessory packages.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SIDE DISCHARGE OPTION Dimensions (in.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN PERFORMANCE/DIMENSIONS SQB 7 Outlet Velocity = CFM x 1.02 Tip Speed = RPM x 2.6835 Maximum Motor Frame Size = 145T Maximum RPM = 2430 Maximum BHP at a Given RPM = (RPM/3022)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 75 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 8 Outlet Velocity = CFM x 1.02 Tip Speed = RPM x 2.6835 Maximum Motor Frame Size = 145T Maximum RPM = 2625 Maximum BHP at a Given RPM = (RPM/2876)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 75 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 10 Outlet Velocity = CFM x 0.74 Tip Speed = RPM x 3.207 Maximum Motor Frame Size = 145T Maximum RPM = 2400 Maximum BHP at a Given RPM = (RPM/2376)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 85 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 12 Outlet Velocity = CFM x 0.45 Tip Speed = RPM x 3.534 Maximum Motor Frame Size = 145T Maximum RPM = 2125 Maximum BHP at a Given RPM = (RPM/1821)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 95 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 15 Outlet Velocity = CFM x 0.30 Tip Speed = RPM x 4.058 Maximum Motor Frame Size = 184T Maximum RPM = 1910 Maximum BHP at a Given RPM = (RPM/1492)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 140 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQBHP 15 Outlet Velocity = CFM x 0.30 Tip Speed = RPM x 4.058 Maximum Motor Frame Size = 184T Maximum RPM = 2130 Maximum BHP at a Given RPM = (RPM/1708)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 140 lbs. 30” CFM / BHP @ Static Pressure / Sones 1-3/4 2 2-1/4 2-1/2 - - - - - - - - - - 1220 .48/16.8 1326 .52/17.4 1422 .55/17.9 1595 .62/19.1 1751 .70/20 1896 .77/21 2033 .85/23 2163 .93/25 2290 1.02/27 2352 1.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 18 Outlet Velocity = CFM x 0.25 Tip Speed = RPM x 4.843 Maximum Motor Frame Size = 184T Maximum RPM = 1640 Maximum BHP at a Given RPM = (RPM/1122)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 190 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQBHP 18 Outlet Velocity = CFM x 0.25 Tip Speed = RPM x 4.843 Maximum Motor Frame Size = 184T Maximum RPM = 1800 Maximum BHP at a Given RPM = (RPM/1251)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 190 lbs. CFM / BHP @ Static Pressure / Sones 1-1/2 1-3/4 2 2-1/4 2-1/2 - - - - - - - - - - - - 1857 .69/11.2 2095 .78/11.9 2410 .91/13.3 2664 1.04/14.7 2780 1.10/15.4 3000 1.23/16.7 3207 1.36/18.0 3407 1.51/19.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 20 Outlet Velocity = CFM x 0.18 Tip Speed = RPM x 5.629 Maximum Motor Frame Size = 184T Maximum RPM = 1275 Maximum BHP at a Given RPM = (RPM/870)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 220 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQBHP 20 Outlet Velocity = CFM x 0.18 Tip Speed = RPM x 5.629 Maximum Motor Frame Size = 184T Maximum RPM = 1440 Maximum BHP at a Given RPM = (RPM/988)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 220 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 24 Outlet Velocity = CFM x 0.11 Tip Speed = RPM x 6.48 Maximum Motor Frame Size = 215T Maximum RPM = 1235 Maximum BHP at a Given RPM = (RPM/711)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 320 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQBHP 24 Outlet Velocity = CFM x 0.11 Tip Speed = RPM x 6.48 Maximum Motor Frame Size = 215T Maximum RPM = 1515 Maximum BHP at a Given RPM = (RPM/774)3 Unit Specifications Housing Metal Thickness = 18 GA. Approximate Weight = 320 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 30 Outlet Velocity = CFM x 0.09 Tip Speed = RPM x 8.017 Maximum Motor Frame Size = 215T Maximum RPM = 1000 Maximum BHP at a Given RPM = (RPM/510)3 Unit Specifications Housing Metal Thickness = 16 GA. Approximate Weight = 420 lbs. CFM / BHP @ Static Pressure / Sones 5239 .57/7.1 6341 .63/8.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQBHP 30 Outlet Velocity = CFM x 0.09 Tip Speed = RPM x 8.017 Maximum Motor Frame Size = 215T Maximum RPM = 1120 Maximum BHP at a Given RPM = (RPM/572)3 Unit Specifications Housing Metal Thickness = 16 GA. Approximate Weight = 420 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 36 Outlet Velocity = CFM x 0.06 Tip Speed = RPM x 9.344 Maximum Motor Frame Size = 215T Maximum RPM = 725 Maximum BHP at a Given RPM = (RPM/375)3 Unit Specifications Housing Metal Thickness = 16 GA. Approximate Weight = 600 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQBHP 36 Outlet Velocity = CFM x 0.06 Tip Speed = RPM x 9.344 Maximum Motor Frame Size = 215T Maximum RPM = 840 Maximum BHP at a Given RPM = (RPM/426)3 Unit Specifications Housing Metal Thickness = 16 GA. Approximate Weight = 600 lbs.
MODEL SQB BELT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SQB 42 Outlet Velocity = CFM x 0.04 Tip Speed = RPM x 10.995 Maximum Motor Frame Size = 215T Maximum RPM = 565 Maximum BHP at a Given RPM = (RPM/289)3 Unit Specifications Housing Metal Thickness = 16 GA. Approximate Weight = 725 lbs. CFM / BHP @ Static Pressure / Sones 3/8 1/2 5/8 3/4 1/8 1/4 11079 .96/7.9 8897 .94/8.3 - 12360 1.23/9.6 13114 1.41/10.4 14353 1.76/11.6 14843 1.91/12.1 15087 1.99/12.4 15573 2.16/12.9 16299 2.42/13.7 17498 2.
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN MODEL FEATURES • Exhaust air up to 2,800 CFM in high static pressure applications up to 1” w.g.
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN CONSTRUCTION/SPECIFICATION CHECKLIST Blower/Housing • Aluminum, non-overloading, backward inclined centrifugal wheel statically and dynamically balanced. SQD 60 has composite wheel. • Deep spun venturi inlet. • Heavy-gauge galvanized steel housing. • Integral inlet and outlet duct collars. • Universal mounting - horizontal, vertical, or any angle.
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN eMotor - Electronically Commutated Motor S&P’s eMotor is 115V and 60 Hz and is available in 1/4, 1/3 and 1/2 HP. This fully controllable motor offers both reliability and low maintenance in one of the most efficient motor fan combinations in the industry. When used in S&P’s eSQD inline fan, the eMotor is the ideal solution for a low cost, fully controlled ventilation system.
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN OPTIONS/ACCESSORIES Mounted and Wired Disconnect Hanging Bracket/ Mounting Foot with Hanging Spring Isolator Side Discharge Hanging Spring Isolators Backdraft Damper Assorted Disconnects 258 Inlet/Outlet Guard Hanging Rubber in Shear Isolators Insulated Housing Speed Controls For SQD models only, not compatible with eSQD
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN FILTER BOX OPTIONS Features • Designed for use with SQD Fans • Designed to handle 1” or 2” filters • Galvanized or aluminum construction • Standard filter is washable aluminum • MERV 7 (1”) or MERV 8 (2”) disposable pleated filters available by special quote • Removable side panels for easy access to filters C D A 1" 1" B Dimensions - Filter Box with 1" Aluminum Filters Fan Size Avg. Ship Wgt. (lbs) Filter Box Dimensions No.
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN FILTER BOX OPTIONS Cont. PRESSURE LOSS GUIDE FOR 1” FILTER BOX Use the estimated pressure drop graphs to help select the proper fan that will deliver the desired airflow. Enter the graph from the bottom at the specified CFM and move vertically upward to the fan curve for the desired size, then horizontally to the left and read the estimated static pressure drop resulting from these typical accessory packages.
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN SIDE DISCHARGE OPTION A (SQ) D B (SQ) C A (IN) BDimensions (IN) C (IN) Side Discharge MODEL SQD 60 8-7/8 8-7/8 13-3/4 SQD 610 8-7/8 8-7/8 13-3/4 MODEL SQD 8125 11-7/8 SQD 6011-7/8 SQD 825 SQD 610 SQD 1025 13-7/8 SQDSQD 1050 8125 13-7/8 SQD 1225 15-7/8 SQD 825 SQD 1250 15-7/8 SQD 1025 SQD 1550 19-7/8 SQD 1050 SQD 1225 SQD 1250 SQD 1550 A (IN) 17-7/8 8-7/8 17-7/8 8-7/8 13-7/8 13-7/8 11-7/8 15-7/8 11-7/8 15-7/8 13-7/8 19-7/8 13-7/8
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN PERFORMANCE/DIMENSIONS Unit Specifications • 18 Ga. galvanized housing. • Approximate unit weight 30 lbs. • Aluminum backward inclined wheel. (SQD 60 has composite wheel) • Removable access panels. • Integral inlet & outlet duct collars. • AMCA Licensed Air & Sound. • Disconnect switch. • Universal/any angle mounting. SQD 60 Motor HP 100 WATT 2700 RPM .95 Max Amps @ 115/60/1 0 151 1.9 199 3.4 238 4.6 294 6.6 334 8.1 382 10.1 424 12.
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN Unit Specifications • 18 Ga. galvanized housing. • Approximate unit weight 60 lbs. • Aluminum backward inclined wheel. • Removable access panels. • Integral inlet & outlet duct collars. • AMCA Licensed Air & Sound. • Disconnect switch. • Universal/any angle mounting. SQD 8125 Motor HP 1/25 HP 1050 RPM CFM / BHP / Sones @ Static Pressure 0 1/8 1/4 329 149 .01/1.6 .01/1.0 376 235 .01/2.5 .02/1.8 423 304 .02/3.3 .02/2.7 446 336 164 .03/3.8 .
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN Unit Specifications • 18 Ga. galvanized housing. • Approximate unit weight 75 lbs. • Aluminum backward inclined wheel. • Removable access panels. • Integral inlet & outlet duct collars. • AMCA Licensed Air & Sound. • Disconnect switch. • Universal/any angle mounting. SQD 1025 CFM / BHP / Sones @ Static Pressure RPM 0 1/8 1/4 3/8 1/2 562 305 600 .02/2.3 .02/1.5 655 451 700 .04/3.3 .04/2.7 749 575 800 .05/4.5 .05/3.
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN Unit Specifications • 18 Ga. galvanized housing. • Approximate unit weight 90 lbs. • Aluminum backward inclined wheel. • Removable access panels. • Integral inlet & outlet duct collars. • AMCA Licensed Air & Sound. • Disconnect switch. • Universal/any angle mounting. SQD 1225 CFM / BHP / Sones @ Static Pressure 0 1/8 1/4 3/8 1/2 920 599 .04/3.7 .04/3.0 1132 878 595 .07/5.7 .07/5.0 .07/4.4 1273 1051 809 529 .10/7.2 .10/6.5 .10/6.0 .09/5.
MODEL SQD & eSQD DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN Unit Specifications • 18 Ga. galvanized housing. • Approximate unit weight 120 lbs. • Aluminum backward inclined wheel. • Removable access panels. • Integral inlet & outlet duct collars. • AMCA Licensed Air & Sound. • Disconnect switch. • Universal/any angle mounting. SQD 1550 Motor HP 0 1348 .05/3.8 1618 .09/5.5 1887 .14/7.2 2157 1/2 HP 1075 RPM .22/9.2 2426 .31/11.5 2696 .42/14.0 2879 .51/15.
MODEL CFD Forward Curved Belt Driven Inline Duct Blower MODEL FEATURES • Rated up to 5,800 CFM in static pressure applications up to 2-1/2” w.g.
MODEL CFD BELT DRIVE FORWARD CURVED INLINE DUCT FAN CONSTRUCTION/SPECIFICATION CHECKLIST Fan Housing • Statically and dynamically balanced forward curved wheel • 12-gauge galvanized steel blower plate/discharge opening • 18-gauge galvanized steel housing • Prepunched mounting holes • Conduit opening for wiring from below unit Drives • Adjustable motor pulleys are standard • Sized for minimum 150% of drive horsepower • Machined cast iron adjustable motor pulleys • Pivoting motor plate for belt tensioning •
MODEL CFD BELT DRIVE FORWARD CURVED INLINE DUCT FAN OPTIONS/ACCESSORIES Rubber Isolator (Hanging) Filter Section Spring Isolator (Hanging) Rubber Isolator (Floor) Spring Isolator (Floor) Hanging & Floor Brackets: For base or ceiling mounting. Neoprene and spring isolators are available. Filter Section: For applications with dusty or dirt laden air. The filters are easily removable for cleaning. Insulated Housing: Used for condensation control or noise reduction.
MODEL CFD BELT DRIVE FORWARD CURVED INLINE DUCT FAN PERFORMANCE DATA CFD07 CFM OV 200 467 0.125” SP 0.25” SP 0.375” SP 0.5” SP 0.625” SP 0.75” SP 1” SP 1.25” SP 1.5” SP 1.75” SP 2” SP 2.25” SP 2.5” SP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 507 706 856 980 1088 0.07 1184 1354 1502 1634 0.21 1756 1869 1975 2074 0.01 0.03 0.04 0.05 0.09 0.13 0.17 0.26 0.31 0.36 300 701 530 0.02 719 0.
MODEL CFD BELT DRIVE FORWARD CURVED INLINE DUCT FAN CFD10 CFM OV 400 474 500 593 0.125” SP 0.25” SP 0.375” SP 0.5” SP 0.625” SP 0.75” SP 1” SP 1.25” SP 1.5” SP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 372 0.02 512 0.04 617 0.07 707 0.09 785 0.12 856 0.15 380 0.03 521 0.05 627 0.08 718 0.1 795 0.13 866 1.75” SP 2” SP 2.25” SP 2.5” SP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 982 0.21 1093 0.28 1193 0.36 1286 0.44 1371 0.
MODEL CFD BELT DRIVE FORWARD CURVED INLINE DUCT FAN CFD12 CFM OV 0.125” SP 0.25” SP 0.375” SP 0.5” SP 0.625” SP 0.75” SP 1” SP 1.25” SP 1.5” SP 1.75” SP 2” SP 2.25” SP 2.5” SP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 800 678 345 0.05 475 0.09 573 0.13 654 0.18 724 0.23 787 0.28 896 0.39 992 0.51 1077 0.64 1155 0.77 1228 0.91 1296 1.05 1360 1.2 900 763 349 0.06 478 0.1 578 0.
MODEL CFD BELT DRIVE FORWARD CURVED INLINE DUCT FAN CFD15 CFM OV 0.125” SP 0.25” SP 0.375” SP 0.5” SP 0.625” SP 0.75” SP 1” SP 1.25” SP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1700 1039 283 0.11 - - - - - - - - - - - - - - 1800 1100 289 0.12 - - - - - - - - - - - - - - 1900 1161 295 0.13 - - - - - - - - - - - - - - 2000 1222 302 0.15 - - - - - - - - - - - - - - 2100 1283 310 0.
MODEL CFD BELT DRIVE FORWARD CURVED INLINE DUCT FAN SOUND DATA CFD07 RPM Sound Performance Sones (Inches w.g.) 0.125 0.25 0.375 0.5 0.625 0.75 1 1.25 1.5 1.75 2 2.25 2.5 500 2 - - - - - - - - - - - - 600 3.8 - - - - - - - - - - - - 700 5.5 4.3 - - - - - - - - - - - 800 7.4 6.2 5.3 - - - - - - - - - - 900 11.3 8.2 7.2 6.5 - - - - - - - - - 1000 11.7 10.4 9.3 8.5 7.9 - - - - - - - - 1100 13.7 12.9 11.7 10.
MODEL CFD BELT DRIVE FORWARD CURVED INLINE DUCT FAN CFD10 Sound Performance Sones (Inches w.g.) RPM 0.125 0.25 0.375 0.5 0.625 0.75 1 1.25 1.5 1.75 2 2.25 2.5 400 2.7 - - - - - - - - - - - - 450 4.4 - - - - - - - - - - - - 500 6 3.1 - - - - - - - - - - - 550 7.6 4.8 - - - - - - - - - - - 600 9.3 6.7 4.6 - - - - - - - - - - 650 11 8.8 6.2 - - - - - - - - - - 700 12.8 10.7 8 6.
MODEL CFD BELT DRIVE FORWARD CURVED INLINE DUCT FAN CFD12 RPM Sound Performance Sones (Inches w.g.) 0.125 0.25 0.375 0.5 0.625 0.75 1 1.25 1.5 1.75 2 2.25 2.5 400 3.9 - - - - - - - - - - - - 450 5.3 4 - - - - - - - - - - - 500 6.8 5.4 4.4 - - - - - - - - - - 550 8.6 6.9 5.9 - - - - - - - - - - 600 10.5 8.6 7.4 6.6 - - - - - - - - - 650 12.6 10.5 9.1 8.2 7.4 - - - - - - - - 700 14.7 12.6 11 9.9 9.2 8.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN MODEL FEATURES • • • • • • • Rated up to 20,000 CFM in static pressure applications up to 2-1/2” w.g.
STANDARD CONSTRUCTION FEATURES Model CTB Motor National brands with local service. Standard motors are heavy-duty open drip-proof. Other options available. Motor Base Adjustable steel motor base is designed for strength and ease of belt tensioning. Mounting Supports Eight (8) mounting supports are welded to each fan to allow for universal mounting. Drives Sized for a minimum 150% of motor horsepower. Drives are variable pitch as standard through 7-1/2 HP.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN STANDARD CONSTRUCTION FEATURES Model CTBRHUL Restaurant Exhaust Motor Base Adjustable steel motor base is designed for strength and ease of belt tensioning. Motor National brands with local service. Standard motors are heavy-duty open drip-proof. Other options available. Mounting Supports Eight (8) mounting supports are welded to each fan to allow for universal mounting. Drives Sized for a minimum 150% of motor horsepower.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN CONSTRUCTION/SPECIFICATION CHECKLIST Fan Housing • Heavy-gauge rolled steel construction. • Integral inlet and outlet flanges with mounting holes. • Continuously welded and epoxy coated. • Belt and bearing tube to protect drive components. • Removable bearing cover for ease of maintenance. • Eight mounting supports welded to each fan. • Adjustable motor base for belt tensioning. • Extended lube lines.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN OPTIONS/ACCESSORIES Motor Cover Belt Guard Hanging Brackets (4) Inlet Guard Companion Flange (Outlet) Companion Flange (Inlet) Outlet Guard Floor Brackets (4) Mounting Rails Inspection Door (See location options below) Inspection Door Location Options Floor or Hanging Isolator Options CTB UL762 • Inspection Door Includes Gasket Rubber Isolator (Floor) Spring Isolator (Floor) Rubber Isolator (Hanging) 8 o’clock 4 o’clock Spring Isolator (Han
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN OPTIONS/ACCESSORIES Hanging & Floor Brackets: For base or ceiling mounting. Neoprene and spring isolators are available. Mounting Rails: Designed for vertical and horizontal mounting. Rail kits include mounting brackets. Inlet/Outlet Guard: Prevents objects from entering the fan inlet or outlet. Includes companion flange. Inspection Door: For inspection and blade service/cleaning. Bolted. UL762 inspection door option includes gasket.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN DIMENSIONS/PHYSICAL DATA Model No. Housings Holes B.C.D. E (Max) Dia. CTB # CTBRHUL # Shaft Size Max Motor Frame Steel Housing Gauges Avg. Ship Wt. (Lbs) I.D. A O.D.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN PERFORMANCE/DIMENSIONS Size 9 Static Pressure (Inches W.G.) CFM OV 0.125 RPM BHP Sones 300 164 350 191 400 219 450 246 500 273 550 301 600 328 650 355 700 383 750 410 800 437 850 464 900 492 950 519 1000 546 1050 574 1100 601 1150 628 1200 656 1250 683 843 0.25 RPM Sones 0.02 1025 0.03 1087 3.3 921 0.04 1157 0.05 1175 0.08 1475 0.10 1561 0.12 1648 12.2 13.9 1819 0.23 2007 15.5 2009 0.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN Size 11 Static Pressure (Inches W.G.) CFM OV 0.125 RPM BHP Sones 500 275 600 330 650 357 750 412 800 440 900 495 950 522 1000 549 1050 577 1100 604 1150 632 1250 687 1350 742 1400 769 1500 824 1550 852 1600 879 1650 907 1700 934 1800 989 1850 1016 1900 1044 1950 1071 733 0.04 0.25 RPM 864 0.05 941 0.07 985 0.08 0.09 0.08 0.12 1077 0.13 0.15 0.17 0.19 0.22 1224 1276 0.27 1593 0.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN Size 13 Static Pressure (Inches W.G.) CFM OV 0.125 RPM 0.25 BHP Sones 600 268 700 313 800 357 900 402 1000 446 1100 491 1200 536 1300 580 1400 625 1500 670 1600 714 1700 759 1800 804 1900 848 2000 893 2100 938 2200 982 2300 1027 2400 1071 2500 1116 2600 1161 2700 1205 2800 1250 2900 1295 603 0.04 RPM 754 0.05 788 0.06 830 0.09 879 0.11 932 0.11 0.13 988 0.14 0.17 0.15 1046 0.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN Size 15 Static Pressure (Inches W.G.) CFM OV 0.125 RPM BHP Sones 900 281 1000 313 1100 344 1200 375 1300 406 1500 469 1700 531 1900 594 2000 625 2100 656 2300 719 2400 750 2500 781 2700 844 2800 875 2900 906 3100 969 3300 1031 3500 1094 3600 1125 586 0.05 0.25 RPM 699 0.08 0.06 731 0.07 765 0.09 801 0.1 839 0.14 918 0.19 1002 0.25 1088 11.6 13.6 0.45 0.51 1176 1266 0.63 0.69 1499 0.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN Size 18 Static Pressure (Inches W.G.) CFM OV 0.125 RPM BHP Sones 1200 240 1500 300 1800 360 2100 420 2400 480 2700 540 3000 600 3300 660 3600 720 3900 780 4200 840 4500 900 4800 960 5100 1020 5400 1080 5700 1140 448 0.06 0.25 RPM 540 0.1 0.09 593 0.13 655 0.18 723 741 0.25 820 0.33 0.44 0.56 0.71 0.88 1225 1.08 1.3 1390 1030 2.18 1.45 1403 1.75 BHP Sones RPM 2 BHP Sones RPM 2.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN Size 22 Static Pressure (Inches W.G.) CFM OV 0.125 RPM BHP Sones 1200 166 1600 222 2000 277 2400 332 2800 388 3200 443 3600 499 4000 4400 554 609 4800 665 5200 720 5600 6000 6400 6800 776 831 886 942 346 0.06 0.25 RPM Sones 443 0.11 1.9 397 0.08 478 0.12 526 0.17 580 580 639 0.33 0.43 763 0.57 827 892 0.91 958 16.9 1.36 1.96 1226 971 0.44 1.29 15.6 1.37 17.5 831 1161 1.85 1226 866 0.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN Size 24 Static Pressure (Inches W.G.) CFM OV 0.125 RPM BHP Sones 2000 201 2500 252 3000 302 3500 352 4000 402 4500 453 5000 503 5500 553 6000 604 6500 654 7000 704 7500 755 8000 805 8500 855 9000 905 9500 956 10000 1006 339 0.09 0.25 RPM 412 0.16 0.13 449 0.19 0.25 540 13.7 16.7 651 693 0.76 765 1.44 913 1.74 998 2.08 1027 2.46 1084 45 1115 2.89 3.37 1233 3.15 1199 2.75 1135 1126 3.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN Size 30 Static Pressure (Inches W.G.) CFM OV 0.125 RPM BHP Sones 2250 177 3000 236 3750 295 4500 354 5250 413 6000 472 6750 531 7500 591 8250 650 9000 709 9750 768 10500 827 11250 886 12000 945 12750 1004 13500 1063 14250 1122 246 0.1 0.25 RPM 316 0.14 341 0.21 372 0.29 407 399 0.41 443 0.55 1.22 1.53 657 675 1.9 703 723 2.32 749 29 771 2.81 795 3.36 842 36 868 3.98 889 4.67 937 5.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN Size 36 Static Pressure (Inches W.G.) CFM OV 0.125 RPM 0.25 BHP RPM Sones 4600 276 5400 324 6200 372 7000 420 7800 468 8600 517 9400 565 10200 613 11000 661 11800 709 12600 757 13400 805 14200 853 15000 901 16100 16900 17700 967 1015 1063 247 0.23 307 0.3 362 0.63 374 385 0.79 0.88 409 0.98 1.06 435 1.21 462 1.46 488 1.76 516 522 2.09 545 2.47 2.9 3.37 632 4.1 673 4.7 703 2.
MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN Size 42 Static Pressure (Inches W.G.) CFM OV 0.25 RPM 0.5 BHP RPM Sones 8300 414 9300 464 10300 514 11300 564 12300 613 13300 663 14300 713 15300 763 16300 813 17300 863 18300 913 19300 963 20300 1012 308 1.01 383 1.21 1.44 428 2.02 445 403 2.38 463 426 2.78 481 15.7 448 3.23 500 3.73 4.46 520 4.67 532 5.35 24 564 5.91 26 5.2 23 21 18.6 550 22 3.95 4.85 23 4.18 516 18.8 17.2 470 3.49 4.
MODELS LCE/LCS, L2E/L2S, L3E/L3S LINE OVERVIEW BELT DRIVE SIDEWALL PROPELLER FANS S&P’s Belt Drive Sidewall Propeller Fan line is designed to exhaust or supply large volumes of air at relatively low static pressures.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS WALL HOUSING MOUNTING OPTION This heavy-gauge, all galvanized G-90 steel housing provides a simple solution to installing a fan and all required accessories in a rough wall opening. It can be used in exhaust or supply applications and in fan sizes 20 through 72 inch. Depending on space and maintenance requirements, the wall housing may be installed inward or outwards of the building.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS WALL HOUSING STANDARD MOUNTING ARRANGEMENTS The most common mounting arrangement (below left) leaves a clean building exterior and allows access to the fan, motor and drives from inside the building. Additional bracing angle, rod or cable (field provided) should be used in addition to the mounting angles to support the fan and wall housing assembly.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS FILTERED WALL HOUSING MOUNTING OPTIONS Filtered wall housings are available in both supply and exhaust configurations. They are available in eight (8) sizes for fans ranging from size 20 to 60 inches. They are designed with the draw-thru concept to achieve the highest filter and fan efficiencies. Filtered Supply Filtered Exhaust Standard construction is galvanized steel.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS FILTERED WALL HOUSING MOUNTING OPTIONS Cont. Filtered Wall Housing Dimensions Filtered Supply Optional Rainhood (90 deg.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS WALL COLLAR MOUNTING OPTION The heavy-gauge, all G-90 galvanized mounting collar provides a simple solution to installing a fan in a rough wall opening when a rear safety guard is NOT required. A front wire guard, shutter, and/or rainhood can be attached to the front prepunched flanges. The wall collar can be used in exhaust or supply applications for all fan sizes.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Accessory or Option Safety Guards Safety Guards (Standard or Heavy-Duty Flat Guards) are strongly recommended to protect personnel from accidental injury and to prevent debris from entering the fan. OSHA approved guards are required in many installations including when the fans are within 7 feet of the floor or work/access area.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Cont. Safety Guards Safety guards are strongly recommended to protect personnel from accidental injury and to prevent debris from entering the fan. OSHA approved guards are required in many installations including when the fans are within 7 feet of the floor or work/access area.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Cont. Rainhoods or Weatherhoods Designed to provide additional weather protection by partially shielding the wall opening and should be used for all supply applications and whenever additional weather resistance is desired. The galvanized (aluminum optional) hood attaches to the wall housing or wall collar flanges. Field flashing and caulking will reduce moisture penetration.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Cont. Damper Types (Shutters) Heavy-Duty Galvanized Exhaust Motorized Shutter This damper has a flanged frame and is designed to fit the inside flanges of the optional wall housing or wall mounting collar. The frame and blades are constructed of galvanized steel and are rated to 3000 FPM with proper clearance as provided by all factory accessories.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Cont. Dimensions (Standard and Heavy-Duty Dampers) EXHAUST AIR FLOW 14" MAX 14" MAX B A A B A SUPPLY AIR FLOW B 3" 10" MAX 10" MAX MOTOR MOUNT MP-2781 MOTOR MOUNT MA-220 7" MAX A A B B DETAIL #1 DETAIL #2 A A Fan Size A Sq. Size B Sq.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS Electrical Accessories are available to simplify the installation and reduce the total project cost. Disconnect Switches can be shipped loose or factory mounted and wired (except explosion proof and two speed) in NEMA 1, 3R, 4X, or other enclosures. Two-speed and explosion proof disconnects are available but may be subject to more stringent code requirements.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS MODEL LC - CONSTRUCTION LEVEL 1 Application Model LCE (exhaust) and LCS (supply) are high capacity belt driven propeller fans rated from 3,000 to 40,000 cfm to .625" w.g. static pressure.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS MODEL L2 - CONSTRUCTION LEVEL 2 Application Models L2E (exhaust) and L2S (supply) are high capacity wall mounted belt driven propeller fans rated from 5000 to 47,000 CFM and to .75" w.g. static pressure.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS MODEL L3 - CONSTRUCTION LEVEL 3 Application Models L3E (exhaust) and L3S (supply) are high capacity wall mounted belt driven propeller fans rated from 35,000 to 85,000 and to 1.0" w.g. static pressure.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS PERFORMANCE Model LC Size 20 Limits Model RPM Motor Frame LC 1350 56H Size Motor HP 1/3 Model LC 20 Level 1 Construction 1/4 1/2 3/4 Panel OD Min. Wall Square Opening 24 Damper OD Approx. Wt 22 1/2 85 25 1/2 Static Pressure (Inches W.G) Max BHP Fan RPM Sones (0.00” SP) .000 .100 .125 .150 .200 .250 .300 .375 .500 0.25 905 10.5 3774 3364 3247 3113 - - - - - 0.27 920 10.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS Model LC and Model L2 Size 24 SOUND and AIR R PERFORMANCE Limits Panel OD Min. Wall Square Opening Model RPM Motor Frame LC 1100 145T 30 L2 1145 145T 30 Size Motor HP 1/4 Model LC 24 Level 1 Construction 1/3 1/2 3/4 1 1 1/2 1/4 1/3 Model L2 24 Level 2 Construction 1/2 3/4 1 1 1/2 2 Damper OD Approx. Wt 31 1/2 28 1/2 90 31 1/2 28 1/2 120 AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS Model LC and Model L2 Size 30 Limits RPM Motor Frame LC 815 145T 36 L2 1070 182T 36 Motor HP 1/4 Model LC 30 Level 1 Construction 1/3 1/2 3/4 1 1 1/2 1/3 3/4 Model L2 30 Level 2 Construction 1/2 1 1 1/2 2 3 and AIR PERFORMANCE Panel OD Min. Wall Square Opening Model Size SOUND R Damper OD Approx. Wt 37 1/2 34 1/2 100 37 1/2 34 1/2 180 AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS Model LC and Model L2 Size 36 SOUND and AIR R PERFORMANCE Limits Panel OD Min. Wall Square Opening Model RPM Motor Frame LC 695 145T 42 L2 845 184T 42 Size Motor HP 1/3 Model LC 36 Level 1 Construction 1/2 3/4 1 1 1/2 2 1/2 1 Model L2 36 Level 2 Construction 3/4 1.5 2 3 5 Damper OD Approx. Wt 43 1/2 40 1/2 105 43 1/2 40 1/2 215 AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS Model LC, Model L2 and Model L3 Size 42 Panel OD Min. Wall Square Opening Damper OD Approx.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS Model LC, Model L2 and Model L3 Size 48 SOUND and AIR R PERFORMANCE Limits Model RPM Motor Frame LC 455 145T 52 1/2 125 605 184T 54 55 1/2 52 1/2 300 765 215T 54 55 1/2 52 1/2 330 Motor HP Model LC 48 3/4 Level 1 Construction 55 1/2 Approx. Wt L2 1/2 1 1 1/2 2 1/2 3/4 1 Model L2 48 Level 2 Construction 54 Damper OD L3 Size 1 1/2 2 3 Model L3 48 5 Level 3 Construction Panel OD Min.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS Model LC, Model L2 and Model L3 Size 54 Limits SOUND and Panel OD Min. Wall Square Opening Damper OD Approx.
MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS Model LC, Model L2 and Model L3 Size 60 SOUND Limits Model RPM and Motor Frame Panel OD Min. Wall Square Opening Damper OD Approx. Wt LC 380 182T 66 67 1/2 64 1/2 285 L2 460 184T 66 67 1/2 64 1/2 490 L3 700 256T 66 67 1/2 64 1/2 530 AIR R PERFORMANCE AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. ® S&P USA Ventilation Systems, LLC., Div.
Model L3 Size 72 MODELS LCE/LCS, L2E/L2S, L3E/L3S BELT DRIVE SIDEWALL PROPELLER FANS SOUND and AIR R PERFORMANCE Limits Model RPM Motor Frame L3 545 256T Panel OD Min. Wall Square Opening 80 Damper OD Approx. Wt 78 1/2 600 81 1/2 AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. ® S&P USA Ventilation Systems, LLC., Div. of Soler & Palau Ventilation Group, certifies that the models shown herein are licensed to bear the AMCA Seal.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS LINE OVERVIEW S&P’s Direct Drive Sidewall Propeller Fan line is designed to exhaust or supply large volumes of air at relatively low static pressures.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS WALL HOUSING MOUNTING OPTIONS WALL HOUSING: This heavy-gauge, all galvanized G-90 steel (aluminum optional) housing provides a simple solution to installing a fan and all specified accessories in a rough wall opening. It can be used in exhaust or supply applications and maintains the proper clearance between the fan and damper.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS WALL HOUSING STANDARD MOUNTING ARRANGEMENTS The most common mounting arrangement (below left) leaves a clean building exterior and allows access to the fan, motor and drives from inside the building. Additional bracing angle, rod or cable (field provided) should be used in addition to the mounting angles to support the fan and wall housing assembly.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS FILTERED WALL HOUSING MOUNTING OPTIONS Filtered wall housings are available in both supply and exhaust configurations. They are available in nine (9) sizes for fans ranging from size 14 to 60 inches. They are designed with the draw-thru concept to achieve the highest filter and fan efficiencies. Filtered Supply Filtered Exhaust Standard construction is galvanized steel.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS FILTERED WALL HOUSING MOUNTING OPTIONS Cont. Filtered Wall Housing Dimensions Filtered Supply Optional Rainhood (90 deg. supply) Wall Mounting Flanges Optional Damper Filter Box Lifting Lugs Mounting Flanges Wall Housing A D Fan Size A (S.Q.) O.D.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS WALL COLLAR MOUNTING OPTIONS WALL COLLAR: This heavy-gauge, all G-90 galvanized (aluminum optional) mounting collar provides a simple solution to installing a fan in a rough wall opening when a rear safety guard is NOT required. A front wire guard or shutter and rainhood can be attached to the front flanges.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Accessory or Option Safety Guards Safety Guards (Standard or Heavy-Duty Flat Guards) are strongly recommended to protect personnel from accidental injury and to prevent debris from entering the fan. OSHA approved guards are required in many installations including when the fans are within 7 feet of the floor or work/access area.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Cont. Safety Guards Safety guards are strongly recommended to protect personnel from accidental injury and to prevent debris from entering the fan. OSHA approved guards are required in many installations including when the fans are within 7 feet of the floor or work/access area.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Cont. Rainhoods or Weatherhoods Designed to provide additional weather protection by partially shielding the wall opening and should be used for all supply applications and whenever additional weather resistance is desired. The galvanized (aluminum optional) hood attaches to the wall housing or wall collar flanges. Field flashing and caulking will reduce moisture penetration.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Cont. Damper Types (Shutters) Heavy-Duty Galvanized Exhaust Motorized Shutter This damper has a flanged frame and is designed to fit the inside flanges of the optional wall housing or wall mounting collar. The frame and blades are constructed of galvanized steel and are rated to 3000 FPM with proper clearance as provided by all factory accessories.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS FOR MOUNTING ARRANGEMENTS Cont. Dimensions (Standard and Heavy-Duty Dampers) EXHAUST AIR FLOW 14" MAX 14" MAX B A 3" A 10" MAX 10" MAX MOTOR MOUNT MP-2781 MOTOR MOUNT MA-220 B B DETAIL #1 DETAIL #2 A A SUPPLY AIR FLOW B 7" MAX A A B Fan Size A Sq. Size B Sq.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS ACCESSORIES & OPTIONS Electrical Accessories are available to simplify the installation and reduce the total project cost. Disconnect Switches can be shipped loose or factory mounted and wired (except explosion proof and two speed) in NEMA 1, 3R, 4X, or other enclosures. Two-speed and explosion proof disconnects are available but may be subject to more stringent code requirements.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS MODEL GED & GSD CONSTRUCTION FEATURES Panel Galvanized steel with spun venturi. Entire Unit Suitable for allangle installation. Propeller Fabricated Aluminum blades. Motor Nationally recognized brands, locally serviced. Motor Side Guard Integral OSHA approved guard is standard. Mounting Holes Prepunched in panel for ease in installation. Factory Run & Tested For quality assurance and dependable operation.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS PERFORMANCE/DIMENSIONS Model GED (Exhaust) & GSD (Supply) A E F B A AIR FLOW C AIR FLOW C D REAR VIEW EXHAUST SUPPLY F* Avg. Ship Wt. (lbs.) 11 9 30 14 12 30 A. Outside dimension of square panel. B. Diameter of venturi. C. Width of flange, 1" for all models. D. Depth of venturi, 2" for all models. E. Depth of fan (exhaust). F. Depth of fan (supply). 14 12 34 * Varies with motor selection.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS MODEL DFE & DFS CONSTRUCTION FEATURES Model DFE & DFS Entire Unit Suitable for all-angle installation. Panel Galvanized steel with spun venturi. Propeller Fabricated Aluminum blades. Motor Nationally recognized brands, locally serviced. Factory Run & Tested For quality assurance and dependable operation. Mounting Holes Prepunched in panel for ease in installation.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS PERFORMANCE/DIMENSIONS Model DFE (Exhaust) / DFS (Supply) DFE/ DFS Size A B C* D E* F G H I J* K Avg. Ship Wt. (lbs.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS MODEL DDE & DDS CONSTRUCTION FEATURES Panel Assembly All welded galvanized steel construction. Propeller Precision pitched extruded or cast aluminum blades. Deep Spun Venturi One piece for maximum efficiency. Motor Nationally recognized brands, locally serviced. Mounting Holes Prepunched in panel for ease in installation. Entire Unit Suitable for all-angle installation.
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS PERFORMANCE Model DDE (Exhaust) / DDS (Supply) Model DDE/DDS 24 30 36 42 48 54 60 MOTOR HP RPM 1/3 1160 1/2 1160 3/4 1160 1 1160 1/2 1750 3/4 1750 1 1750 1 1/2 1750 2 1750 3 1750 1 870 1 1/2 870 3/4 1160 1 1160 1 1/2 1160 2 1160 3 1160 2 1750 3 1750 1 870 1 1/2 870 2 870 3 870 3/4 1160 1 1160 1 1/2 1160 2 1160 3 1160 5 1160 7 1/2 1160 3 1750 5 1750 7 1/2 1750 1 1/2 870 2 870 3 870 5 870 3 1160 5 1160 7 1/2 1160 5 1750 7 1/2 1750
MODELS GED/GSD, DFE/DFS, DDE/DDS DIRECT DRIVE SIDEWALL PROPELLER FANS DIMENSIONS Model DDE & DDS 336 Dimensions (in.) DDE/ DDS Size A B C* D E* F G H I J K 24 30 2 11 9 21 25 3 9 4 20 11 30 36 2 11 9 21 31 3 9 4 20 11 36 42 2 11 9 21 37 3 9 4 20 11 42 48 2 11 9 21 43 3 9 4 20 11 48 54 2 12 10 23 49-1/4 4 10 4 22 12 54 60 2 13 11 25 55-1/4 5 11 4 24 13 60 66 2 13 11 25 61-1/4 5 11 4 24 13 A.
MODEL WA COMPACT WALL AXIAL FAN MODEL FEATURES • Exhaust air up to 4,520 CFM with static pressure capabilities to 1/2” w.g.
MODEL WA COMPACT WALL AXIAL FAN CONSTRUCTION/SPECIFICATION CHECKLIST Motor • All models include asynchronous induction capacitor run and start motors. • Constructed from die cast aluminum and finished in a black polyester paint coating. • 100% Speed controllable. • Totally enclosed IP/65 protection. • Class F insulation. • Suitable working temperatures -40°C (-40°F) up to 60°C (140°F). • All models include a Safety Auto Reset Thermal Overload Protection.
MODEL WA COMPACT WALL AXIAL FAN PERFORMANCE/DIMENSIONS Dimensions in inches/mm D J H F G A B C Model A B WA 12 153/4 400 1215/16 330 11 280 127/16 315 3/8 WA 16 1911/16 500 165/8 420 1315/16 355 153/4 400 3/8 22 18 15 17 3/8 WA 18 E WA 20 1/16 560 2413/16 630 C 3/4 480 211/8 537 D 3/4 400 17 3/4 450 E 3/4 450 1911/16 500 3/8 F G 10 1215/16 329 27/8 10 165/8 422 31/16 18 3 10 3/4 476 211/8 536 10 H 11/4 73 15/8 78 1 3/4 37/8 95 98 21/2 3
MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS MODEL FEATURES • Supply air to over 56,000 CFM up to 3/4” w.g. • Belt drives permit easy performance adjustments when needed • Direct drive units have low sound levels and quiet operation.
MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS CONSTRUCTION FEATURES AND OPTIONS Hood Heavy-gauge galvanized steel pivots for access to fan. Rain Gutter To prevent water entrainment. Drives (belt drive) Adjustable pitch through 3HP, all are sized for minimum 150% of drive HP. Bearings (belt drive) Cast iron pillow blocks, double sealed and prelubricated, designed for 200,000 hour life. Propeller Adjustable pitch aluminum airfoil blades.
MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS Construction/Specification Checklist Panel Assembly • Heavy-gauge G90 galvanized steel panel. • One piece spun venturi for maximum efficiency. • All welded support structure of schedule 40 galvanized pipe. • Motor/bearing plates of minimum 10 gauge galvanized steel. • All welds coated with cold galvanized paint. Hood • All heavy-gauge G90 galvanized steel. • Low silhouette design for pleasing appearance.
MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS Options/Accessories Filters: Permanent cleanable aluminum mesh 2” filters installed in hood opening. See pages 298 and 299 for certified performance data with filters in place. Roof Curb: Prefabricated heavy-gauge galvanized steel, welded construction, 12” high (other heights are also available) with 1-1/2” wood nailer. Assures perfect fit of unit to roof opening.
MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS PERFORMANCE DATA - HRSB BELT DRIVE Model HRSB 24 30 CFM @ Static Pressure 0 1/8 3/8 1/2 5/8 Max BHP 2979 - - - - 1/3 930 3 .38 15 3000 - - - 1/2 1060 4 .58 19 6171 5648 5049 4244 3315 - - 3/4 1215 3 .85 24 6781 6302 5841 5121 4374 3493 - 1 1335 3 1.13 28 7771 7354 6946 6467 5830 5189 4436 1 1/2 1530 3 1.70 34 8533 8153 7777 7412 6881 6298 5715 2 1680 4 2.
MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS PERFORMANCE DATA - HRSD DIRECT DRIVE Model HRSD 24 30 36 42 48 54 0 4645 4455 5433 6336 6756 6232 7709 8646 9447 9272 10276 8691 10150 11973 13020 11269 14249 17790 12436 14185 16237 18084 15289 17594 20753 24253 22388 27417 15924 20258 22642 26128 24423 30979 21071 30329 19172 23378 26407 24151 29404 35765 41979 32705 40052 45047 43139 50109 1/8 4210 3793 4766 5750 6091 5838 7308 8212 9023 8232 9223 7744 9275 11016 12213 10688 13723 17198 10693
MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS PERFORMANCE DATA - HRSB-F BELT DRIVE WITH FILTERS Model HRSB-F 24 30 36 42 48 0 4327 4984 5653 6277 7194 7899 7242 8226 9034 10366 11412 13028 9637 11002 12110 13901 15266 17483 13841 15198 17369 19133 21846 17949 20571 22587 25814 30654 35091 38721 1/8 3650 4430 5211 5891 6857 7592 6003 7196 8128 9599 10715 12418 7192 8881 10205 12276 13792 16196 10120 11764 14370 16415 19467 12146 15261 17713 21489 27000 31899 35828 CFM @ Static Pressure 1/4 3/
MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS PERFORMANCE DATA - HRSD-F DIRECT DRIVE WITH FILTERS Model HRSD-F 24 30 36 42 48 0 5724 6204 5932 7164 7988 8779 8273 9111 7919 9019 10319 11489 10360 12739 15375 10814 12029 13467 15229 13211 15197 17216 20545 19654 23366 13965 16958 18835 20709 25471 26240 21205 24860 28822 35091 28661 33747 36844 1/8 5215 5713 5527 6778 7544 8476 7251 8130 7012 8119 9275 10703 9677 12155 14701 9160 10298 11303 13606 11941 13942 15783 19284 18794 22527 11651 1478
MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS DIMENSIONS Model HRSB-F - Belt Drive Model HRSD-F - Direct Drive Model HRSB - Belt Drive Model HRSD - Direct Drive Model HRSB/ HRSD 24 30 36 42 48 54 60 Model HRSB-F/ HRSD-F 24 24 30 30 36 36 42 42 48 48 Dimensions (Inches) A B C D E F 58 66 78 87 99 111 111 35 41 47 53 59 65 71 30 36 42 48 54 60 66 31 32 34 43 44 45 46 23 23 23 30 30 30 30 33-1/4 39-1/4 45-1/4 51-1/4 57-1/4 63-1/4 69-1/4 Dimensions (Inches) Curb Cap 16 16 16 16 14 14 14
MODELS HREB-C & HRED-C HOODED PROPELLER ROOF EXHAUST FANS MODEL FEATURES • Exhaust air to over 40,000 CFM up to 3/4” w.g. • Belt drives permit easy performance adjustments when needed • Direct drive units have low sound levels and quiet operation.
MODELS HREB-C & HRED-C HOODED PROPELLER ROOF EXHAUST FANS CONSTRUCTION FEATURES AND OPTIONS Hood Modular hood design for maximum strength and lower cost. All galvanized and welded construction. Hood Heavy-gauge galvanized steel (aluminum optional) pivots for access to fan - removal is not necessary. Drives (belt drive) Adjustable pitch through 3HP, sized for minimum 150% of drive HP with outboard drives for ease of maintenance. Rain Gutter To prevent water entrainment.
MODELS HREB-C & HRED-C HOODED PROPELLER ROOF EXHAUST FANS CONSTRUCTION/SPECIFICATION CHECKLIST Panel Assembly • Heavy-gauge G90 galvanized steel panel. • One piece spun venturi for maximum efficiency. • All welded support structure of minimum schedule 40 galvanized pipe. • Motor/bearing plates of minimum 10 gauge galvanized steel. • All welds coated with cold galvanized paint. Hood • All heavy-gauge G90 galvanized steel. • Low silhouette design for pleasing appearance.
MODELS HREB-C & HRED-C HOODED PROPELLER ROOF EXHAUST FANS OPTIONS/ACCESSORIES Roof Curb: Prefabricated heavy-gauge galvanized steel, welded construction, 12” high (other heights are also available) with 1-1/2” wood nailer. Assures perfect fit of exhauster to roof opening. Options include burglar bars, single or double pitch construction and hinged curbs for easy duct access. Disconnect Switch: Nonfused safety disconnects are available for all motor sizes in rain-tight or open enclosures.
MODELS HREB-C & HRED-C HOODED PROPELLER ROOF EXHAUST FANS PERFORMANCE DATA - HREB-C BELT DRIVE Model HREB-C 24 30 36 42 48 54 60 CFM / BHP @ Static Pressure 0 1/8 1/4 3/8 1/2 5/8 3/4 HP RPM Sones @ 5 ft. 5702/ 0.377 4678 / 0.400 3661 / 0.397 2480 / 0.392 1159 / 0.416 - - 1/3 970 14.9 6525/ 0.565 5613 / 0.599 4764 / 0.599 3792 / 0.595 2730 / 0.587 1582 / 0.624 - 1/2 1110 18.3 7466/ 0.847 6653 / 0.894 5915 / 0.896 5153 / 0.896 4271 / 0.890 3399 / 0.891 2240 / 0.
MODELS HREB-C & HRED-C HOODED PROPELLER ROOF EXHAUST FANS PERFORMANCE DATA - HRED-C DIRECT DRIVE Model HRED-C 24 30 36 CFM / BHP @ Static Pressure 0 1/8 1/4 3/8 1/2 5/8 3/4 5991 / 0.541 5222 / 0.607 4453 / 0.617 2966 / 0.597 2203 / 0.609 6908 / 0.867 6081 / 0.86 5194 / 0.854 3735 / 0.831 2780 / 0.842 5219 / 0.325 4327 / 0.384 3555 / 0.398 2526 / 0.381 1709 / 0.363 6390 / 0.570 5597 / 0.622 4739 / 0.627 3798 / 0.617 2572 / 0.617 1297 / 0.606 7394 / 0.892 6553 / 0.
MODELS HREB-C & HRED-C HOODED PROPELLER ROOF EXHAUST FANS PERFORMANCE DATA - HRED-C DIRECT DRIVE cont. Model HRED-C 42 48 54 60 CFM / BHP @ Static Pressure 0 1/8 1/4 3/8 1/2 5/8 3/4 HP RPM Sones @ 5 ft. 6570 / 1.609 14167 / 1.551 11262 / 1.420 7973 / 1.426 - - - 1-1/2 870 33 19940 / 2.305 17744 / 2.305 15655 / 2.306 13058 / 2.215 10682 / 2.153 - - 2 870 37 21640 / 3.95 19785 / 3.89 17763 / 3.81 15602 / 3.72 13345 / 3.67 11007/3.67 8532 3.73 3 870 41 21966 / 3.
MODELS HREB-C & HRED-C HOODED PROPELLER ROOF EXHAUST FANS DIMENSIONS Model HRED-C Direct Drive Model HREB-C Belt Drive Dimensions (Inches) Size A B C D Metal Gauges E F Hood Crown Base Curb Cap Avg. Wt.
MODELS ARE & ARS DOME AXIAL POWER ROOF VENTILATORS (EXHAUST/SUPPLY) MODEL FEATURES • Exhaust air up to 3,100 CFM in static pressure applications up to 3/4” w.g.
MODELS ARE & ARS DOME AXIAL POWER ROOF VENTILATORS CONSTRUCTION/SPECIFICATION CHECKLIST Housing • Heavy-gauge all aluminum housing. • Exclusive U-Spring suspension compensates for both radial and lateral movement and provides 44% better vibration isolation than rubber isolators. • External wiring chase for easy connection. • High point of discharge with low silhouette design. • Quick access to motor compartment for easy maintenance. Propellers • Attaches directly to fan shaft for maximum efficiency.
MODELS ARE & ARS DOME AXIAL POWER ROOF VENTILATORS PERFORMANCE Model ARE (Exhaust) CFM / BHP @ Static Pressure / Sones 0 1/10 1/8 1/4 3/8 1/2 5/8 3/4 Catalog Number HP RPM 336 0.13 1.6 167 0.15 2.8 147 0.15 2.8 22 0.16 3.4 - - - - - - - - - - - - ARE 100A S 1/15 930 445 0.11 3.0 299 0.14 4.1 270 0.14 4.9 175 0.15 4.9 81 0.15 5.3 - - - - - - - - - ARE 100A S 1/15 1230 561 0.11 5.0 463 0.10 5.2 425 0.13 5.3 298 0.14 7.3 228 0.
MODEL UBS & UBS-P BELT DRIVE UPBLAST PROPELLER ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 51,000 CFM in static pressure applications up to 1/2” w.g. • Straight-through air flow design results in maximum exhaust efficiency • Belt drives permit easy performance adjustments when needed • cULus 705 Listed MODEL OVERVIEW Models UBS and UBS-P arehigh capacity roof mounted exhausters rated from 7,000 to 51,000 CFM.
MODEL UBS & UBS-P BELT DRIVE UPBLAST PROPELLER ROOF EXHAUSTERS CONSTRUCTION FEATURES AND OPTIONS Galvanized Steel Windband Damper Rod Stainless Steel. Rain Channel Integral Galvanized Steel. Galvanized Steel Butterfly Dampers Propeller Blades Die Formed Epoxy Coated Steel on UBS. Plastic Poly Propeller on UBS-P Lifting Eyes At All Four Corners of Curb Cap. Steel Hub Plate Heavy Epoxy Coated. Keyed to Fan Shaft. Galvanized Curb Cap With Fully Welded Corners.
MODEL UBS & UBS-P BELT DRIVE UPBLAST PROPELLER ROOF EXHAUSTERS CONSTRUCTION/SPECIFICATION CHECKLIST Panel Assembly • Heavy-gauge G90 galvanized steel panel on all sizes. • One piece venturi for maximum efficiency. • Welded and bolted support structure of schedule 40 galvanized pipe. • Motor/bearing plates of heavy-gauge galvanized steel. • Lifting eyes standard for ease of installation. Windband/Butterfly Dampers • Heavy-gauge galvanized steel windband. • Galvanized steel butterfly dampers standard.
MODEL UBS & UBS-P BELT DRIVE UPBLAST PROPELLER ROOF EXHAUSTERS PERFORMANCE MODEL UBS 24 30 36 42 48 54 60 0 7079 7939 10546 12781 14388 11872 14557 16415 19087 16307 19184 22382 25259 22656 27187 31480 29460 36456 44555 50996 CFM @ STATIC PRESSURE 1/8 1/4 3/8 6599 6023 5284 7511 7068 6461 9463 7865 5230 11952 10895 9435 13700 12782 11745 10354 8064 5301 13389 11962 9903 15416 14200 12722 18221 17299 16291 14087 11400 7270 17283 15281 12804 20749 19150 17245 23813 22382 20885 20052 16506 10504 25018 25
MODEL UBSRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 52,000 CFM in static pressure applications up to 3/4” w.g.
MODEL UBSRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTERS CONSTRUCTION/SPECIFICATION CHECKLIST Panel Assembly • Heavy-gauge G90 galvanized steel panel, size 24-60. • One piece venturi for maximum efficiency and strength. • Motor mounting plates of heavy-gauge galvanized steel. • Bearing mounting plates of heavy-gauge galvanized steel. • Lifting eyes standard for ease of installation. Windband/Butterfly Dampers • Heavy-gauge galvanized steel windband. • Galvanized steel butterfly dampers standard.
MODEL UBSRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTERS OPTIONS/ACCESSORIES Roof Curb: Prefabricated heavy-gauge galvanized steel, welded construction, 12” high with 1-1/2” wood nailer. Options include burglar bars, single and double pitch construction, and additional curb heights. Disconnect Switch: Nonfused safety disconnects are available for all motor sizes in rain-tight or open enclosures. Magnetic Latches: Help reduce damper chatter when the units are not in operation.
MODELS UBSRD-HT & UBSRD-HT1 REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTERS FOR HEAT AND SMOKE REMOVAL MODEL FEATURES • Exhaust air up to 52,000 CFM in static pressure applications up to 3/4” w.g.
MODELS UBSRD-HT & UBSRD-HT1 REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTERS FOR HEAT AND SMOKE REMOVAL CONSTRUCTION/SPECIFICATION CHECKLIST 1. Successfully heat tested by independent laboratory for; (a) 1000°F for 15 minutes. (b) 500°F for minimum 4 hours. 2. All ferrous construction in airstream. 3. 165°F fusible link in damper spring mechanism (HT1 unit only). 4. Motor out-of-airstream design. 5. Belt & bearings enclosed in ventilated housing. 6. Minimum dual groove drive/belt combination. 7.
MODELS UBSRD, UBSRD-HT & UBSRD-HT1 REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTERS PERFORMANCE DATA Model 24L 30L 30H 36L 36H 42L 42H 48L 48H 54L 54H 60L 60H Motor Max. Sones RPM HP BHP @ .375 CFM @ Static Pressure in Inches of Water 0.000 0.100 0.125 0.150 0.200 0.250 1/2 989 0.55 17 6153 5747 5645 5511 5244 4977 3/4 1123 0.82 22 6987 6629 6539 6435 6227 6019 0.300 0.375 5761 5373 0.500 1 1233 1.
MODELS UBSRD, UBSRD-HT & UBSRD-HT1 REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTERS DIMENSIONS Model Number Code The model number code is designed to completely identify the fan. Below is a detailed explanation of the model number codes: UBS RD HT - 36 L Upblast Propeller Roof Fan Motor out-ofairstream Model A B C D E F G H I Wt.
MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS BELT AND DIRECT DRIVE MODEL FEATURES • Exhaust air up to 78,000 CFM in static pressure applications up to 1/2” w.g.
MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS CONSTRUCTION FEATURES AND OPTIONS Windband Heavy-gauge galvanized steel. Butterfly Dampers Available in aluminum, steel or translucent fiberglass. Lifting Lugs Provide for safe, easy placement on roof. Damper Bearings Galvanized damper shaft rotates in bronze bushing. Rain Channel Galvanized steel channel drains water to roof. Propeller Adjustable pitch aluminum air-foil blades standard, steel blades available when required.
MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS CONSTRUCTION/SPECIFICATION CHECKLIST Panel Assembly • Heavy-gauge G90 galvanized steel panel on all sizes. • One piece venturi for maximum efficiency. • All welded support structure of schedule 40 galvanized pipe. • Motor/bearing plates of minimum 10 gauge galvanized steel. Windband/Butterfly Dampers • Heavy-gauge galvanized steel windband. • Steel dampers standard (except on sizes 48-72).
MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS OPTIONS/ACCESSORIES Roof Curb: Prefabricated heavy-gauge galvanized steel, welded construction, 12” high with 1-1/2” wood nailer. Options include burglar bars, single and double pitch construction, and additional curb heights. Disconnect Switch: Nonfused safety disconnects are available for all motor sizes in rain-tight or open enclosures. Magnetic Latches: Help reduce damper chatter when the units are not in operation.
MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS PERFORMANCE UBB - Belt Drive Model UBB 24 30 36 42 48 54 60 72 CFM @ Static Pressure 0 1/8 1/4 3/8 1/2 HP RPM Blades / Pitch Max. BHP Sones @ 5 ft. 22 7180 6500 5720 4800 - 3/4 1210 3 0.82 7920 7300 6610 5880 - 1 1335 3 1.11 25 9080 8550 7960 7340 6600 1-1/2 1525 3 1.65 32 10000 9500 9000 8450 7900 2 1680 3 2.21 37 9398 8323 7039 5381 3254 1 960 3 1.
MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS UBX - Direct Drive (Cont.) Model UBX 36 42 48 54 CFM @ Static Pressure 0 1/8 1/4 3/8 1/2 HP RPM Blades / Pitch Max BHP Sones @ 5 ft. 23 14200 12000 - - - 1 870 2 1.10 15900 14300 12500 - - 1-1/2 870 4 1.64 25 17700 16200 14300 12400 - 2 870 4 2.17 33 36 18900 17700 16300 14800 12700 3 870 6 3.24 15700 14200 12400 - - 1-1/2 1160 2 1.65 36 17600 16000 14300 12200 - 2 1160 2 2.
MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS DIMENSIONS 2" Model UBB - Belt Drive Size 24 30 36 42 48 54 60 72 A B 30 36 42 48 54 60 66 80 33 36 38 41 44 47 50 56 Dimensions (Inches) D E C Sq. Sq. 16 32 24 17 38 30 17 44 36 18 50 42 22 56 48 22 62 54 22 68 60 31 82 72 Model UBX - Direct Drive F Sq. 31 37 43 49 55 61 67 81 G Sq. 28 34 40 46 52 58 64 78 Metal Gauges WindCurb Fan band Cap Panel 18 16 16 18 16 16 18 16 16 18 16 16 18 14 16 18 14 14 18 14 14 18 12 12 Avg. Wt.
MODEL UBRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 72,000 CFM in static pressure applications up to 1/2” w.g. • Straight-through air flow design results in maximum exhaust efficiency • Motor and drives are located outside of the exhaust airstream • Belt drives permit easy performance adjustments when needed • cULus 705 Listed MODEL OVERVIEW Model UBRD units are high capacity belt driven roof mounted exhausters rated from 4,500 to 72,000 CFM.
MODEL UBRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Panel Assembly • Heavy-gauge G90 galvanized steel panel, size 24-72. • One piece venturi for maximum efficiency and strength. • All welded support structure of schedule 40 galvanized pipe (minimum). • Motor/bearing plates of minimum 10 gauge galvanized steel. Windband/Butterfly Dampers • Heavy-gauge galvanized steel windband. • Steel dampers standard (except on sizes 48-72).
MODEL UBRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTER OPTIONS/ACCESSORIES Roof Curb: Prefabricated heavy-gauge galvanized steel, welded construction, 12” high with 1-1/2” wood nailer. Options include burglar bars, single and double pitch construction, and additional curb heights. Disconnect Switch: Nonfused safety disconnects are available for all motor sizes in rain-tight or open enclosures. Magnetic Latches: Help reduce damper chatter when the units are not in operation.
MODEL UBRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTER PERFORMANCE Model UBRD 24 30 36 42 48 54 60 72 0 6605 7286 8353 9200 10230 11625 12741 14508 12861 14688 16512 18816 18414 20553 23250 27261 24196 27784 32660 37352 41216 33250 39140 44840 49210 44826 51336 56730 57381 65751 72726 CFM @ Static Pressure 1/8 1/4 3/8 5980 5262 4416 6715 6081 5410 7866 7323 6752 8740 8280 7774 9114 7812 10602 9579 8370 11904 10881 9858 13764 12927 12090 10752 12768 10656 14880 12960 10848 17280 15744 14112 15624
MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER MODEL FEATURES • Exhaust air up to 60,116 CFM in static pressure applications up to 1” w.g. • Straight-through air flow design results in maximum exhaust efficiency • Motor and drives are located outside of the exhaust airstream • Belt drives permit easy performance adjustments when needed • cULus 705 Listed MODEL OVERVIEW Model TUB is designed for high capacity industrial and commercial roof exhaust applications.
MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER CONSTRUCTION FEATURES AND OPTIONS Butterfly Dampers Available in steel or fiberglass. Windband Heavy-gauge galvanized steel. Blades Statically and dynamically balanced aluminum airfoil extrusion or polypropylene propellers for optimum performance. High temperatures fans use steel blades. Rain Channel Galvanized metal channel section drains water out of the fan area when the damper doors are closed.
MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER CONSTRUCTION/SPECIFICATION CHECKLIST Construction The TUB series is built with heavy-gauge steel to provide years of reliable service. Tubes 24-60" (to 10HP) are G-90 galvanized steel. Sizes 24-60" have rolled 2" flanged ends. The TUB series is also available in aluminum construction sizes 24-48" with welded aluminum angle flanges on each end. Upblast fans include a heavy-gauge galvanized steel windband with pressure operated damper doors.
MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER OPTIONS/ACCESSORIES Roof Curb: Prefabricated heavy-gauge galvanized steel, welded construction, 12” high with 1-1/2” wood nailer. Options include burglar bars, single and double pitch construction, and additional curb heights. Outlet Guard: 1/2” x 1” wire mesh guard will prevent birds and other objects from entering fan. Inspection Door: For inspection and blade service/cleaning.
MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER PERFORMANCE Model TUB-A - Belt Drive - Aluminum Blade Model TUB 24 30 36 42 48 54 60 0 6210 6805 7840 8668 9035 9973 11405 12590 14318 13854 15894 17424 19719 23798 27028 14588 16046 18300 20157 23074 27349 32037 20266 23104 25536 29184 34656 39519 45327 31028 38951 44741 49215 33008 39133 44918 49342 1/8 5807 6443 7537 8398 8175 9213 10755 12009 13813 12440 14689 16337 18769 23021 26347 14024 16539 18561 21682 26140 30976 16694 20044 22821 2686
MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER Model TUB-P - Belt Drive - Polypropylene Blade Model TUB 24 30 36 42 48 54 60 0 6350 6998 8265 9246 10626 8697 9775 11515 12821 14525 17514 14809 16823 19331 22940 26230 29020 17451 19563 22893 27670 31120 34310 20303 21414 25236 30791 35748 39574 31896 34454 40051 44750 51252 44454 52235 58295 60116 1/8 5962 6680 7943 8996 10323 7942 9121 10920 12222 14029 17112 13921 16002 18540 22026 25850 28671 15670 17981 21562 26551 30830 33537 18249 19321
MODEL TUB-HT TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER FOR HEAT AND SMOKE REMOVAL MODEL FEATURES • Exhaust air up to 57,000 CFM in static pressure applications up to 3/4” w.g.
MODEL TUB-HT TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER FOR HEAT AND SMOKE REMOVAL CONSTRUCTION/SPECIFICATION CHECKLIST 1. Successfully heat tested by independent laboratory for: (a) 1000°F for 15 minutes. (b) 500°F for minimum 4 hours. 2. All ferrous construction in airstream. 3. 165°F fusible link in damper mechanism (heat & smoke vent). 4. Motor out-of-airstream design. 5. Belt & bearings enclosed in ventilated housing. 6. Minimum dual groove drive/belt combination. 7. Shaft heat slinger. 8.
MODEL TUB-HT TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER FOR HEAT AND SMOKE REMOVAL DIMENSIONS Model TUBHT 390 Dimensions (Inches) A B sq. O.D I.D. Curb Windband Cap C sq. Min. I.D. Opg D Height E Windband Height F Tube Height G (Max.
MODEL TUB-HT TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER FOR HEAT AND SMOKE REMOVAL PERFORMANCE DATA TUB-HT - Belt Drive - Steel Blade Model TUB-HT 24 30 36 42 48 54 60 0 6255 6962 7896 8693 9631 11324 11952 13871 16225 14173 15114 18020 20849 18628 22193 25960 29490 20302 27001 29173 33418 36776 27348 34050 42632 47064 49325 35718 42487 48378 54617 57143 CFM / BHP @ Static Pressure 1/8 1/4 3/8 1/2 5/8 5297 4821 4035 6547 6115 5446 7272 6601 6216 5814 5248 8109 7688 7265 6276 5409 8703 6835 6478 10
MODEL TDB TUBEAXIAL INLINE BELT DRIVEN DUCT FAN MODEL FEATURES • Rated up to 75,490 CFM in static pressure applications up to 1-1/2” w.g.
MODEL TDB TUBEAXIAL INLINE BELT DRIVEN DUCT FAN CONSTRUCTION/SPECIFICATION CHECKLIST Fan Housing • Heavy-gauge rolled steel construction. • Integral inlet and outlet flanges with mounting holes. • Continuous welded and epoxy coated. • Belt and bearing tube. • Removable bearing cover for ease of maintenance. • Eight mounting supports welded to each fan. • Adjustable motor base for belt tensioning. • Extended lube lines. Propeller • Aluminum airfoil propeller. • Blades are pitched for optimum efficiency.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN OPTIONS/ACCESSORIES Motor Cover Belt Guard Hanging Brackets (4) Outlet Guard Companion Flange (outlet) Companion Flange (inlet) Inlet Guard Floor Brackets (4) Mounting Rails Inspection Door (See location options below) Floor or Hanging Isolator Options Inspection Door Location Options Rubber Isolator (Floor) Spring Isolator (Floor) 8 o’clock 4 o’clock Rubber Isolator (Hanging) Spring Isolator (Hanging) 394
MODEL TDB TUBEAXIAL INLINE BELT DRIVEN DUCT FAN OPTIONS/ACCESSORIES Hanging & Floor Brackets: For base or ceiling mounting. Neoprene and spring isolators are available. Mounting Rails: Designed for vertical and horizontal mounting. Rail kits include mounting brackets. Vertical mounting available by special quote on sizes 34-48”. Inlet/Outlet Guard: Prevents objects from entering the fan inlet or outlet. Includes companion flange. Inspection Door: For inspection and blade service/cleaning. Bolted.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN PERFORMANCE/DIMENSIONS Size 12 Max. Motor Frame: 145T Shaft Size: 5/8" Housing Gauge: 16 Approximate Weight: 90 lbs. Flange Holes: 6 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized C E B.C.D. A B Air Flow A B C E B.C.D. 12-3/8 14-1/2 12* 21 13-1/2 A: ID B: OD C: Length E: Max. Height *Motor may extend past unit .436 Dia. Side View Front View Static Pressure (Inches W.G.) HP 1/4 1/3 1/2 3/4 RPM 0 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 16 Max. Motor Frame: 145T Shaft Size: 5/8" Housing Gauge: 16 Approximate Weight: 110 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized C E B.C.D. A B Air Flow A B C E B.C.D. 16-3/8 18-1/2 17* 23 17-3/8 A: ID B: OD C: Length E: Max. Height *Motor may extend past unit .436 Dia. Side View Front View Static Pressure (Inches W.G.) HP 1/4 1/3 1/2 3/4 1 RPM 0 0.125 0.25 0.375 0.5 0.625 0.75 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 18 C B.C.D. B A E D Air Flow Max. Motor Frame: 182T Shaft Size: 1" Housing Gauge: 14 Approximate Weight: 140 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized A .436 Dia. B C 18-3/8 22-1/2 D 22* E 17-15/16 25-1/2 A: ID B: OD C: Length E: Max. Height *Motor may extend past unit B.C.D. 19-3/4 Side View D Front View Static Pressure (Inches W.G.) HP 1/4 1/3 1/2 3/4 1 1 1/2 RPM 0 0.125 0.25 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 20 C B.C.D. B A E D Air Flow Max. Motor Frame: 184T Shaft Size: 1" Housing Gauge: 14 Approximate Weight: 150 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized .436 Dia. A B C 20-3/8 24-1/2 22 D E B.C.D. 18-3/8 26-1/2 21-3/4 A: ID B: OD C: Length E: Max. Height Side View D Front View Static Pressure (Inches W.G.) HP 1/3 1/2 3/4 1 1 1/2 2 RPM 0 0.125 0.25 0.375 0.5 0.625 0.75 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 24 C B.C.D. B A E D Air Flow Max. Motor Frame: 184T Shaft Size: 1" Housing Gauge: 12 Approximate Weight: 220 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized .436 Dia. A B C 24-3/8 28-9/16 23 D E 21-1/4 28-1/2 A: ID B: OD C: Length E: Max. Height B.C.D. 25-3/4 Side View D Front View Static Pressure (Inches W.G.) HP 1/2 3/4 1 1 1/2 2 3 RPM 0 0.125 0.25 0.375 0.5 0.625 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 30 C B.C.D. B A E D Air Flow Max. Motor Frame: 254T Shaft Size: 1-3/16" Housing Gauge: 12 Approximate Weight: 260 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized .436 Dia. A B C D E B.C.D. 30-3/8 34-9/16 24 25-1/2 35 32 A: ID B: OD C: Length E: Max. Height Side View D Front View Static Pressure (Inches W.G.) HP 1/2 3/4 1 1 1/2 2 3 5 RPM 0 0.125 0.25 0.375 0.5 0.625 0.75 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 34 C B.C.D. B A E D Air Flow Max. Motor Frame: 254T Shaft Size: 1-7/16" Housing Gauge: 12 Approximate Weight: 310 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized .436 Dia. A B C D E B.C.D. 34-3/8 38-9/16 27 28-5/8 37 36-3/8 A: ID B: OD C: Length E: Max. Height Side View D Front View Static Pressure (Inches W.G.) HP RPM 0 CFM 3/4 1 1 1/2 2 3 5 7 1/2 0.125 BHP CFM BHP 0.25 CFM 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 36 C B.C.D. B A E D Air Flow Max. Motor Frame: 254T Shaft Size: 1-7/16" Housing Gauge: 10 Approximate Weight: 410 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized .436 Dia. A B C D E B.C.D. 36-3/8 40-5/8 29 29-13/16 38 38 A: ID B: OD C: Length E: Max. Height Side View D Front View Static Pressure (Inches W.G.) HP RPM 0 CFM 3/4 1 1 1/2 2 3 0.125 0.25 0.375 0.5 0.625 0.75 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 42 C B.C.D. B A E D Air Flow Max. Motor Frame: 254T Shaft Size: 1-7/16" Housing Gauge: 10 Approximate Weight: 480 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized .436 Dia. A B C D E B.C.D. 42-1/2 47 30 34-1/8 42 44-1/4 A: ID B: OD C: Length E: Max. Height Side View D Front View Static Pressure (Inches W.G.) HP RPM 0 CFM 1 1 1/2 2 3 0.125 BHP CFM BHP 480 11943 0.45 9569 0.52 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 48 C B.C.D. B A E D Air Flow Max. Motor Frame: 284T Shaft Size: 1-7/16" Housing Gauge: 10 Approximate Weight: 600 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized .436 Dia. A B C D E B.C.D. 48-1/2 53 33 38-3/8 45 50-3/4 A: ID B: OD C: Length E: Max. Height Side View D Front View Static Pressure (Inches W.G.) HP RPM 0 CFM 460 1 1/2 2 3 5 7 1/2 10 0.125 BHP CFM BHP 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 54 Max. Motor Frame: 284T Shaft Size: 2-3/16" Housing Gauge: 10 Approximate Weight: 730 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized C B.C.D. B A E D Air Flow .436 Dia. A B C D E B.C.D. 55 59-1/2 38 43 48 57-1/4 A: ID B: OD C: Length E: Max. Height Side View D Front View Static Pressure (Inches W.G.) HP RPM 0 CFM 3 5 7 1/2 10 15 0.125 BHP CFM BHP 0.25 CFM BHP 0.375 CFM 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 60 C B.C.D. B A E D Air Flow Max. Motor Frame: 286T Shaft Size: 2-3/16" Housing Gauge: 10 Approximate Weight: 798 lbs. Flange Holes: 8 Diameter Flange Holes: 7/16” Finish: Epoxy Coated Galvanized .436 Dia. A B C 61 65-1/2 40 D E 47-1/4 54-1/2 A: ID B: OD C: Length E: Max. Height B.C.D. 63-1/4 Side View D Front View Static Pressure (Inches W.G.) HP RPM 0 CFM 7 1/2 10 15 20* CFM BHP 0.25 CFM BHP 0.375 CFM BHP 0.5 0.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN SOUND CHARACTERISTICS Size 12 Sound Performance Sones / LwA (Inches w.g.) RPM 0 0.125 0.25 0.375 0.5 1550 18.1 / 80 16.3 / 78 - - - 1600 18.9 / 80 17.1 / 79 15.7 / 78 - - 1650 19.8 / 81 18.1 / 80 16.7 / 79 - - 1700 21 / 82 19 / 81 17.6 / 80 - - 1725 21 / 83 19.5 / 81 18.1 / 80 - - 1775 22 / 83 20 / 82 19.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 18 RPM Sound Performance Sones / LwA (Inches w.g.) 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1000 11.4 / 72 11 / 70 - - - - - - - 1050 12.3 / 73 11.9 / 72 12.1 / 72 - - - - - - 1100 13.2 / 74 12.7 / 73 12.7 / 73 - - - - - - 1125 13.7 / 75 13.2 / 74 13 / 73 - - - - - - 1150 14.1 / 75 13.7 / 74 13.4 / 74 - - - - - - 1200 15.1 / 77 14.6 / 75 14.2 / 74 15.2 / 77 - - - - - 1225 15.6 / 77 15.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 20 RPM 1050 Sound Performance Sones / LwA (Inches w.g.) 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.125 13.6 / 76 12.8 / 75 - - - - - - - - 1100 14.9 / 77 14.2 / 77 - - - - - - - - 1125 15.6 / 78 14.9 / 77 13.9 / 77 - - - - - - - 1150 16.2 / 79 15.6 / 78 14.7 / 77 - - - - - - - 1175 16.9 / 79 16.2 / 79 15.4 / 78 - - - - - - - 1225 18.2 / 81 17.6 / 80 16.9 / 79 - - - - - - - 1275 19.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 24 RPM 800 Sound Performance Sones / LwA (Inches w.g.) 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 12.8 / 75 11.9 / 74 - - - - - - - 850 14.3 / 77 13.4 / 76 12.6 / 75 - - - - - - 900 15.8 / 78 14.9 / 77 14 / 77 - - - - - - 950 17.3 / 80 16.5 / 79 15.5 / 78 - - - - - - 975 18.1 / 81 17.3 / 80 16.3 / 79 16.1 / 79 - - - - - 1025 19.6 / 82 18.8 / 81 18 / 81 17.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 30 RPM Sound Performance Sones / LwA (Inches w.g.) 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 600 11.8 / 73 10.1 / 71 - - - - - - - - 650 13.5 / 75 12 / 74 - - - - - - - - 700 15.2 / 77 13.9 / 76 12.8 / 75 - - - - - - - 750 16.9 / 79 15.9 / 78 14.8 / 77 - - - - - - - 775 17.8 / 80 16.9 / 79 15.8 / 78 - - - - - - - 800 18.6 / 81 17.8 / 80 16.8 / 79 - - - - - - - 825 19.6 / 82 18.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 34 RPM 0 Sound Performance Sones / LwA (Inches w.g.) 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 600 15.1 / 78 15.4 / 78 - - - - - - - - - 625 16.2 / 79 16.4 / 79 - - - - - - - - - 650 17.4 / 80 17.5 / 80 17.8 / 81 - - - - - - - - 675 18.5 / 81 18.6 / 81 19 / 82 - - - - - - - - 700 19.7 / 82 19.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 36 RPM Sound Performance Sones / LwA (Inches w.g.) 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 650 18.3 / 80 17.2 / 80 - - - - - - - - - 675 19.5 / 81 18.3 / 81 17.6 / 81 - - - - - - - - 700 21 / 82 19.5 / 82 18.7 / 82 - - - - - - - - 725 22 / 83 21 / 83 19.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 42 RPM Sound Performance Sones / LwA (Inches w.g.) 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 480 17 / 80 16.5 / 79 - - - - - - - - - 520 19.4 / 82 18.9 / 82 17.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 48 RPM Sound Performance Sones / LwA (Inches w.g.) 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.25 1.5 460 21 / 82 20 / 82 19.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 54 RPM Sound Performance Sones / LwA (Inches w.g.) 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.125 1.
MODEL TDB BELT DRIVE TUBEAXIAL DUCT FAN Size 60 RPM Sound Performance Sones / LwA (Inches w.g.) 0 0.125 0.25 0.375 0.5 0.625 0.75 0.875 1 1.
MODEL TDD DIRECT DRIVE TUBEAXIAL DUCT FAN MODEL FEATURES • Rated up to 39,000 CFM in static pressure applications up to 1-1/4” w.g. • Direct drive units have low sound levels and quiet operation • Smaller sizes for areas with reduced airflow needs • Require practically no maintenance • AMCA Air Licensed MODEL OVERVIEW S&P’s tubeaxial line offers the widest range of sizes, horsepower and performance in the industry.
MODEL TDD DIRECT DRIVE TUBEAXIAL DUCT FAN CONSTRUCTION/SPECIFICATION CHECKLIST Fan Housing • Heavy-gauge rolled galvanized steel construction. • Integral inlet and outlet flanges with mounting holes. • Continuous welded and epoxy coated. • Eight mounting supports welded to each fan. • Rolled steel flange reinforcement on each end. Propeller (Sizes 12 - 18) • Polypropylene blades. • Steel bushing. • Blades are pitched for optimum efficiency. • Statically and dynamically balanced.
MODEL TDD DIRECT DRIVE TUBEAXIAL DUCT FAN OPTIONS/ACCESSORIES Hanging Brackets (4) Outlet Guard Companion Flange (outlet) Companion Flange (inlet) Inlet Guard Floor Brackets (4) Mounting Rails Inspection Door (See location options below) Floor or Hanging Isolator Options Inspection Door Location Options 10 o’clock 2 o’clock Rubber Isolator (Floor) Spring Isolator (Floor) Rubber Isolator (Hanging) Spring Isolator (Hanging) 421
MODEL TDD DIRECT DRIVE TUBEAXIAL DUCT FAN OPTIONS/ACCESSORIES Hanging & Floor Brackets: For base or ceiling mounting. Neoprene and spring isolators are available. Mounting Rails: Designed for vertical and horizontal mounting. Rail kits include mounting brackets. Vertical mounting available by special quote on sizes 34-48”. Inlet/Outlet Guard: Prevents objects from entering the fan inlet or outlet. Includes companion flange. Inspection Door: For inspection and blade service/cleaning. Bolted.
MODEL TDD DIRECT DRIVE TUBEAXIAL DUCT FAN PERFORMANCE & DIMENSIONS Sizes 12 and 16 B.C.D. A C B 12 16 18 20 24 Max. Motor Frame: 56 56 145T 145T 213T Housing Gauge: 16 16 14 14 12 Approx. Weight: 90 108 150 178 273 6 8 8 8 8 Flange Holes: .438 Front View Diameter Flange Holes: 7/16" Finish: Epoxy Coated Galvanized Size 12 16 18 20 24 Side View Sizes 18, 20 and 24 C B.C.D.
MODEL TDD DIRECT DRIVE TUBEAXIAL DUCT FAN Sizes 30, 34 and 36 C B.C.D. A Max. Motor Frame: Housing Gauge: Approximate Weight: Flange Holes: Diameter Flange Holes: Finish: B .438 Front View 215T 30” & 34” = 12 36” = 10 30" = 320 lbs. 34” = 457 lbs 36" = 532 lbs. 8 7/16" Epoxy Coated Galvanized Size A B C* B.C.D.
MODEL TDD DIRECT DRIVE TUBEAXIAL DUCT FAN Sizes 42 and 48 C B.C.D. A Max. Motor Frame: Housing Gauge: Approximate Weight: Flange Holes: Diameter Flange Holes: Finish: B 256T 10 42" = 738 lbs. 48" = 834 lbs. 8 7/16" Epoxy Coated Galvanized .438 Front View Side View Size A B C* B.C.D 42 42-1/2 46-3/4 30 44-1/4 48 48-1/2 52-3/4 33 50-3/4 A: ID B: OD C: Length (*motor may extend past unit) Model 42 48 Static Pressure (Inches W.G.) HP Nominal RPM Max Watts 0 0.
MODEL DA COMPACT DUCT AXIAL FAN MODEL FEATURES • Exhaust air up to 4,750 CFM with static pressure capabilities to .35” w.g.
MODEL DA COMPACT DUCT AXIAL FAN CONSTRUCTION/SPECIFICATION CHECKLIST Motor • All models include asynchronous induction capacitor run and start motors. • Constructed from die cast aluminum and finished in a black polyester paint coating. • 100% Speed controllable. • Totally enclosed IP/65 protection. • Class F insulation. • Suitable working temperatures -40°C (-40°F) up to 60°C (140°F). • All models include a Safety Auto Reset Thermal Overload Protection.
MODEL DA COMPACT DUCT AXIAL FAN DIMENSIONS IN INCHES/MM B E Model A DA 12 153/16 386 14 DA 16 DA 18 A C DA 20 AIR & SOUND PERFORMANCE *Technical Specification Input Watts Peak BHP RPM DA 12 TCGB/4-12/G-B 132 - DA 16 TCGB/4-16/G-B 320 DA 18 TCGB/4-18/G-B 540 DA 20 TCGB/4-20/G-B 770 Model D 356 611/16 170 127/16 316 3/8 193/16 487 173/4 451 611/16 170 153/4 400 1/2 21 19 7 17 1/2 1/8 537 11/16 1/8 500 22 237/16 595 1/16 71/8 560 Weight (lbs) E 3/4 181 45
MODEL CM BELT DRIVEN UTILITY VENT SET OVERVIEW The CM Series belt driven backward inclined Utility Vent Set fans from S&P offer an excellent choice of product for all medium and high pressure exhaust or supply applications for commercial, institutional or light industrial air moving projects. Both models are supplied complete with motor mounted on an adjustable base; v-belt drives; heavy duty ball bearings and integral mounting platform.
Models CMI are available by special quote only and at longer delivery schedules than regular CM units. Please contact the factory for pricing and size availability. CMI Heavy Duty Suitable for corrosive airstream exhaust applications. Standard Features: • AMCA Air & Sound Certified • Performance: 500-25,000 CFM with Static Pressures up to 5.5 in. W.G. • Backward inclined CW or CCW orientation non-overloading wheels. • Stainless Steel construction.
MODEL CM MODEL FEATURES BELT DRIVEN UTILITY VENT SET • Exhaust air to over 21,000 CFM in static pressure capabilities to 5.5” • Belt drives permit easy performance adjustments when needed • Backward inclined CW or CCW orientation non-overloading wheels, sizes 10 - 36 ins.
MODEL CM BELT DRIVEN UTILITY VENT SET STANDARD CONSTRUCTION FEATURES Inlet/L-Flange (Standard): This standard feature allows for easy duct attachment. The inlet collar allows the fan to be removed with minimal disconnecting of the duct work. Weather cover (Standard): Sheet metal ventilated enclosure for the motor, shaft, belts and drives for safety and weather protection. Access door (Standard): This standard feature is a bolted access door that allows inspection or cleaning of the wheel compartment.
MODEL CM BELT DRIVEN UTILITY VENT SET CONSTRUCTION/SPECIFICATION CHECKLIST Type: UTILITY VENT SET Type of Wheel: Backward Inclined Rotation: CW and CCW Sizes: 10, 12, 14, 16, 18, 20, 22, 24, 27, 30, 36 Construction Housing & Drive Frame Structure The unit is solidly built, housing joints are welded intervals (continuous welding on request, contact factory for availability and delivery schedules), this provides greater strength, accuracy on the boards and makes a robust unit, which is an added value.
MODEL CM BELT DRIVEN UTILITY VENT SET PHYSICAL DATA CM Model Wheel Diameter (in.) Wheel Weight (lbs.) WR2 (lbs-ft2) Max. Wheel RPM Max. Motor Frame Size Fan Weight* (lbs.) 62 10 10-1/16 4 0.600 3850 145T 12 12-11/16 11 1.90 3200 184T 89 14 14-7/8 13 3.56 2800 184T 102 16 16 18 5.22 2500 184T 119 18 17-15/16 24 9.73 2200 213T 160 20 20-3/16 31 16.85 1950 213T 188 22 22-7/16 42 26.10 1800 215T 269 24 25-3/16 59 41.
MODELS CM BELT DRIVEN UTILITY VENT SET PERFORMANCE/DIMENSIONS CM 10 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: 10-1/16” 0.625 Sq. Ft. CM - 62 lbs 3/4” 2.64 x RPM=FPM 2,998 RPM 3/4 HP Static Pressure (Inches W.G.) CFM OV 0.5 1 1.5 2 2.5 3 3.5 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 499 800 1316 0.07 1655 0.12 1939 0.18 - - - - - - - - 531 850 1353 0.07 1682 0.13 1962 0.
MODELS CM BELT DRIVEN UTILITY VENT SET CM 12 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: CFM 778 875 972 1069 1118 1166 1215 1264 1312 1361 1409 1458 1507 1555 1604 1652 1701 1750 1798 1847 1895 1944 1993 2090 2138 2187 2236 2284 2333 2381 2430 2479 2527 2576 2673 2722 2770 2819 2867 2916 2965 3013 3110 OV 800 900 1000 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 2050 2150 2200 2250 2300 2350 240
MODELS CM BELT DRIVEN UTILITY VENT SET CM 14 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: CFM 960 1080 1200 1320 1380 1440 1500 1560 1620 1680 1740 1800 1860 1920 1980 2040 2100 2160 2220 2340 2400 2460 2520 2580 2640 2700 2760 2880 3000 3060 3120 3180 3240 3300 3360 3420 3480 3540 3600 3720 3840 3960 4020 4080 OV 800 900 1000 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1950 2000 2050 2100 2150 2200 2250 2300 2
MODELS CM BELT DRIVEN UTILITY VENT SET CM 16 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: CFM 1192 1341 1416 1490 1639 1788 1863 1937 2012 2086 2161 2235 2310 2384 2459 2533 2608 2682 2757 2831 2906 2980 3055 3129 3204 3278 3353 3427 3502 3576 3651 3725 3800 3874 3949 4023 4098 4172 4247 4321 4470 4545 4619 4694 OV 800 900 950 1000 1100 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 2050 2100 2150 2200 2250 2
MODELS CM BELT DRIVEN UTILITY VENT SET CM 18 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: CFM 1504 1692 1786 1880 1974 2162 2350 2444 2538 2632 2726 2820 3008 3102 3196 3290 3384 3572 3666 3760 3948 4042 4136 4324 4418 4512 4606 4700 4794 4888 4982 5076 5264 5358 5452 5546 5640 5828 6016 6204 6298 6392 6486 OV 800 900 950 1000 1050 1150 1250 1300 1350 1400 1450 1500 1600 1650 1700 1750 1800 1900 1950 2000 2100 2150 2200 2300 2350 2400 2450 2500 2
MODELS CM BELT DRIVEN UTILITY VENT SET CM 20 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: 20-3/16” 2.33 Sq. Ft. CM - 188 lbs 1-1/2” 5.26 x RPM=FPM 1,823 RPM 5 HP 80 Static Pressure (Inches W.G.) 0.5 1 1.5 2 2.5 3 3.5 4 4.5 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1864 800 635 0.22 804 0.42 950 0.64 2097 900 669 0.27 828 0.48 967 0.71 2330 1000 706 0.31 856 0.54 989 0.79 1110 1.05 2563 1100 744 0.37 887 0.61 1014 0.
MODELS CM BELT DRIVEN UTILITY VENT SET CM 22 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: CFM 2360 2655 2950 3245 3540 3688 3835 3983 4130 4278 4425 4720 4868 5015 5163 5310 5605 5753 5900 6195 6343 6490 6638 6785 7080 7375 7523 7670 7818 7965 8260 8555 8703 8850 8998 9145 9293 9440 9735 9883 10030 10325 10473 10620 OV 800 900 1000 1100 1200 1250 1300 1350 1400 1450 1500 1600 1650 1700 1750 1800 1900 1950 2000 2100 2150 2200 2250 2300 2400 2500 2
MODELS CM BELT DRIVEN UTILITY VENT SET CM 24 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: CFM 2960 3330 3700 4070 4440 4625 4810 4995 5180 5365 5550 5735 5920 6290 6475 6660 6845 7030 7215 7400 7585 7770 8140 8325 8510 8695 8880 9250 9620 9990 10360 10545 10730 10915 11100 11470 11840 12025 12210 12395 12580 12765 12950 13320 13505 OV 800 900 1000 1100 1200 1250 1300 1350 1400 1450 1500 1550 1600 1700 1750 1800 1850 1900 1950 2000 2050 2100 2200
MODELS CM BELT DRIVEN UTILITY VENT SET CM 27 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: CFM 3760 4230 4700 5170 5405 5640 5875 6110 6345 6580 6815 7050 7520 7755 7990 8460 8695 8930 9165 9400 9635 9870 10105 10340 10575 10810 11280 11750 11985 12220 12455 12690 12925 13160 13630 14100 14335 14570 14805 15040 15275 15510 15745 15980 OV 800 900 1000 1100 1150 1200 1250 1300 1350 1400 1450 1500 1600 1650 1700 1800 1850 1900 1950 2000 2050 2100 215
MODELS CM BELT DRIVEN UTILITY VENT SET CM 30 Wheel Diameter: Outlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: CFM 4608 5184 5760 6048 6336 6624 6912 7200 7488 7776 8064 8352 8640 8928 9216 9504 9792 10080 10368 10656 10944 11232 11520 11808 12096 12384 12672 13248 13536 13824 14112 14400 14688 14976 15552 15840 16128 16416 16704 16992 17280 17568 17856 18144 OV 800 900 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 195
MODEL CM BELT DRIVEN UTILITY VENT SET CM 36 Wheel Diameter: Outlet Area: Inlet Area: Average Weight: Shaft Diameter: Tip Speed: Max Fan RPM: Max Motor HP: FEG: CFM 5808 6534 7260 7623 7986 8349 8712 9075 9438 9801 10164 10527 10890 11253 11616 12342 12705 13068 13431 13794 14157 14520 15246 15609 15972 16335 16698 17061 17424 18150 18513 18876 19239 19602 19965 20328 21054 21417 21780 22143 22506 22869 23232 23958 OV 800 900 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1700 1750 1800
MODELS CM BELT DRIVEN UTILITY VENT SET SOUND CHARACTERISTICS CM 10 Sound Performance Sones / LwA (Inches w.g.) RPM 0.5 1 1.5 2 2.5 3 3.5 1325 4.4 / 60.1 - - - - - - 1500 5.7 / 64.2 - - - - - - 1700 7.5 / 68.6 6.6 / 65.9 - - - - - 1875 9.5 / 72.1 8.2 / 69.5 - - - - - 2050 11.7 / 75.4 9.9 / 72.6 9.3 / 70.9 - - - - 2250 14.4 / 78.7 12.2 / 76.0 11.4 / 74.6 11.1 / 73.2 - - - 2450 17.0 / 81.5 14.5 / 78.9 13.5 / 77.5 13.1 / 76.6 - - - 2625 19.
MODELS CM BELT DRIVEN UTILITY VENT SET CM 16 Sound Performance Sones / LwA (Inches w.g.) RPM 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 800 5.0 / 61.1 - - - - - - - - - 1000 8.6 / 70.3 - - - - - - - - - 1150 11.6 / 75.3 9.4 / 71.6 - - - - - - - - 1300 15.2 / 79.7 12.4 / 76.4 10.7 / 73.7 - - - - - - - 1450 19.3 / 83.5 16.1 / 80.7 14.2 / 78.5 12.4 / 75.9 - - - - - - 1625 24 / 87.0 21 / 85.0 18.6 / 83.0 17.1 / 81.5 15.3 / 79.
MODELS CM BELT DRIVEN UTILITY VENT SET CM 22 Sound Performance Sones / LwA (Inches w.g.) RPM 575 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.7 / 62.7 - - - - - - - - - - 700 9.0 / 70.3 825 13.1 / 76.4 10.6 / 72.9 - - - - - - - - - - - - - - - - 950 18.1 / 81.5 14.9 / 78.4 13.4 / 76.1 - - - - - - - 1075 23 / 85.7 - - - - - - 1225 30 / 89.7 19.9 / 83.2 17.8 / 81.1 16.5 / 79.3 27 / 88.2 24 / 86.4 22 / 84.9 21 / 83.3 19.8 / 82.1 - - - - 1350 35 / 92.
CM 30 Sound Performance Sones / LwA (Inches w.g.) RPM 400 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.6 / 62.2 - - - - - - - - - 475 8.8 / 69.9 - - - - - - - - - 550 12.7 / 75.7 9.5 / 70.8 - - - - - - - - 625 16.8 / 80.4 13.3 / 76.5 11.1 / 73.1 - - - - - - - 13.5 / 76 - 700 21 / 84.2 775 26 / 87.5 17.6 / 81.3 14.9 / 78.3 22 / 85.3 875 32 / 91.2 29 / 89.8 - - - - - - - - - - 20 / 82.8 - - - - 19.4 / 82.8 17.2 / 80.5 16.3 / 78.9 26 / 87.
MODEL CM BELT DRIVEN UTILITY VENT SET Dimensional Data MODEL CM H E B I A C D V F J G K J K L O S M Q N 450 T U P Model A B C D E F G H I J K 10 12 5/8 7 1/16 9 13/16 23 7/8 17 3/16 1/2 16 7/8 25 3/8 15 1/2 1 10 13/16 12 15 7/8 8 3/4 12 3/8 29 3/16 21 3/8 1/2 19 5/8 28 11/16 17 1/16 1 12 1/2 14 17 7/8 9 3/4 14 32 3/4 22 3/4 1/2 19 5/8 30 3/4 17 13/16 1 13 5/16 16 19 15/16 10 13/16 15 3/4 36 3/4 25 1/4 1/2 21 7/8 31 9/16 17 15/16
GRAVITY VENTILATORS SIZING RCXII (sizes 6-20) RCXII (sizes 24-36) RCXII-SF BGH RLX Sizing The tables shown offer quick selections at common static pressure points. Selection choices vary widely due to field conditions and size choices.
MODELS RCXII/RCXII-SF RELIEF/INTAKE GRAVITY VENTILATORS RCXII (sizes 6-20) RCXII (sizes 24-36) RCXII-SF MODEL FEATURES • Exhaust or Supply air up to 10,400 CFM in static pressure applications up to .35” w.g. • All heavy-gauge aluminum construction • Integral galvanized birdscreen • Curb mounted or Self-flashing models MODEL OVERVIEW Model RCXII and RCXII-SF relief or intake ventilators feature low contour spun aluminum hoods for an attractive appearance.
MODELS RCXII/RCXII-SF RELIEF/INTAKE GRAVITY VENTILATORS CONSTRUCTION/SPECIFICATION CHECKLIST • Five year warranty. • Low contour spun aluminum hood for attractive appearance. • All heavy-gauge aluminum construction. • Weather resistance design for long life and maintenance free operation. • Galvanized birdscreen is standard. • Available in 13 sizes for a wide range of performance capabilities. • RCXII has one-piece curb cap with spun inlet for maximum efficiency. • RCXII-SF is self flashing.
MODELS RCXII/RCXII-SF RELIEF/INTAKE GRAVITY VENTILATORS DIMENSIONS RCXII (sizes 6-20) D E C Size A B C D E 06 7 16.5 10 14 5.75 08 9 16.5 12 14 5.75 10 11 24 14 20 6.75 12 13 24 16 20 6.75 14 15 24 18 27 8.75 16 17 24 20 27 8.75 18 19 29.5 22 27 8.75 20 21 29.5 22 30 10.25 2.00 A B RCXII (sizes 24-36) RCXII-SF Neck Area sq. ft. 24 3.30 26 30 Dimensions (Inches) A B D E 1 2 43-3/4 12-1/2 35-1/2 24-5/8 2 0.063 0.063 3.
MODELS RCXII/RCXII-SF RELIEF/INTAKE GRAVITY VENTILATORS PERFORMANCE DATA Models RCXII (sizes 6-20) and Models RCXII-SF Relief Throat Area Ft2 .025 .050 .100 .125 .150 .200 .250 .300 .350 BDD O.D Sq. (RCXII) Prefab Curb Recom. O.D (RCXII) 6 0.3 93 131 185 207 227 262 293 320 346 8 14-3/4 8 0.4 221 313 442 494 541 625 699 766 827 8 14-3/4 10 0.7 297 420 594 664 727 840 939 1029 1111 12 22-1/4 12 0.
MODEL BGH FABRICATED GRAVITY RELIEF/INTAKE VENTILATOR MODEL FEATURES • Exhaust or Supply air up to 90,000 CFM in static pressure applications up to .25” w.g. • Constructed of .050” aluminum • Assembled with standing seams and snap-lock seams that are secured with spot welds • Modern, low silhouette design that blends roof lines and other equipment MODEL OVERVIEW Model BGH gravity ventilator offers a modern low silhouette design that blends with roof lines and other equipment.
MODEL BGH FABRICATED GRAVITY RELIEF/INTAKE VENTILATORS OPTIONS/ACCESSORIES Aluminum Birdscreens: Consists of .060” thick 1/2” x 1” diamond shape expanded aluminum. Attached to the full perimeter opening of the hood with stainless or zinc plated fasteners. Hinged Hood: For easy access to backdraft dampers and to service filters and screens. Insulated Hood: To reduce condensation drip. Offered in rubberized anti-condensate undercoating or as 1” thick fiberglass insulation.
MODEL BGH FABRICATED GRAVITY RELIEF/INTAKE VENTILATORS PERFORMANCE/DIMENSIONS Gravity Relief 1:1 Ratio Dimensional Data Throat Velocity in FPM @ Static Pressure - Relief 536 Hood Size 758 848 1073 Throat Size AxB C D E .050 .100 .125 .200 .250 1.00 12 x 12 18 18 7 536 758 848 1073 1200 1.50 12 x18 19 25 7 804 1137 1272 1610 1800 2.00 12 x 24 20 32 7 1072 1516 1696 2146 2400 2.50 12 x 30 20 38 7 1340 1895 2120 2683 3000 3.
MODEL BGH FABRICATED GRAVITY RELIEF/INTAKE VENTILATORS Gravity Relief 1:1 Ratio Cont. Dimensional Data 536 Hood Size Throat Velocity in FPM @ Static Pressure - Relief 758 848 1073 1200 CFM @ Static Pressure - Relief Throat Area Throat Size AxB C D E .050 .100 .125 .200 .250 7.50 8.33 9.17 10.00 10.83 11.67 4.00 5.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00 6.25 7.50 8.75 10.00 11.25 12.50 13.75 15.00 16.25 17.50 18.75 9.00 10.50 12.00 13.50 15.00 16.50 18.00 19.50 21.00 22.
MODEL BGH FABRICATED GRAVITY RELIEF/INTAKE VENTILATORS Gravity Relief 1:1 Ratio Cont. Dimensional Data Throat Velocity in FPM @ Static Pressure - Relief 536 Hood Size 758 848 1073 Throat Size AxB C D E .050 .100 .125 .200 .250 24.00 48 x 72 73 97 17 12864 18192 20352 25752 28800 CFM @ Static Pressure - Relief 26.00 48 x 78 74 103 17 13936 19708 22048 27898 31200 28.00 48 x 84 75 111 17 15008 21224 23744 30044 33600 30.
MODEL BGH FABRICATED GRAVITY RELIEF/INTAKE VENTILATORS Gravity Intake 2:1 Ratio Dimensional Data Throat Velocity in FPM @ Static Pressure - Intake Hood Size 312/625 441/883 592/998 592/1185 625/1250 Throat Area Throat Size AxB C D E .050 .100 .125 .180 .200 1.00 12 x 12 21 21 7 625 883 988 1185 1250 CFM @ Static Pressure - Intake 1.50 12 x 18 23 29 7 938 1325 1482 1778 1875 2.00 12 x 24 25 37 7 1250 1766 1976 2370 2500 2.
MODEL BGH FABRICATED GRAVITY RELIEF/INTAKE VENTILATORS Gravity Intake 2:1 Ratio Cont. Dimensional Data Throat Velocity in FPM @ Static Pressure - Intake 312/625 Hood Size 441/883 592/998 592/1185 Throat Size AxB C D E .050 .100 .125 .180 .200 7.50 20 x 54 43 77 11 4688 6623 7410 8888 9375 10417 CFM @ Static Pressure - Intake 8.33 20 x 60 44 84 11 5208 7358 8233 9875 9.17 20 x 66 45 91 11 5729 8094 9057 10863 11458 10.
MODEL BGH FABRICATED GRAVITY RELIEF/INTAKE VENTILATORS Gravity Intake 2:1 Ratio Cont. Dimensional Data Throat Velocity in FPM @ Static Pressure - Intake 312/625 Hood Size 441/883 592/998 592/1185 625/1250 Throat Area Throat Size AxB C D E .050 .100 .125 .180 .200 24.00 48 x 72 92 116 20 15000 21192 23712 28440 30000 26.00 48 x 78 94 126 20 16250 22958 25688 30810 32500 28.00 48 x 84 95 131 20 17500 24724 27664 33180 35000 30.
MODEL RLX MODEL FEATURES LOUVERED PENTHOUSE • Exhaust or Supply air up to 69,500 CFM in static pressure applications up to .23” w.g. • All aluminum construction • Louvered penthouse design provides a low silhouette and modern design • Corners are miter cut and heliarch welded for strength and weather protection MODEL OVERVIEW Model RLX aluminum louvered penthouse provides a low silhouette and modern design for fresh air intake, pressure relief and gravity applications.
MODEL RLX LOUVERED PENTHOUSE OPTIONS/ACCESSORIES Roof Curb: Prefabricated heavy-gauge galvanized steel, welded construction, 8” high (other heights are also available) with 1-1/2” wood nailer. Assures perfect fit of ventilator to roof opening. Options include burglar bars, single or double pitch construction and hinged curbs for easy duct access. Motor Operated Damper: Motor operated aluminum damper for positive closure against backdraft.
MODEL RLX LOUVERED PENTHOUSE PERFORMANCE/DIMENSIONS Gravity Relief & Intake Throat Size AxB CFM at SP = 0.15 Number of Tiers and Height in Inches (C) 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 10.5 14 17.5 21 24.5 28 31.5 35 38.5 42 45.5 49 52.5 56 59.5 63 66.
MODEL RLX LOUVERED PENTHOUSE Gravity Relief & Intake Cont. Throat Size AxB CFM at SP = 0.15 Number of Tiers and Height in Inches (C) 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 10.5 14 17.5 21 24.5 28 31.5 35 38.5 42 45.5 49 52.5 56 59.5 63 66.
MODEL RLX LOUVERED PENTHOUSE Gravity Relief & Intake Cont. Throat Size AxB CFM at SP = 0.15 Number of Tiers and Height in Inches (C) 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 10.5 14 17.5 21 24.5 28 31.5 35 38.5 42 45.5 49 52.5 56 59.5 63 66.
MODEL RLX LOUVERED PENTHOUSE Gravity Relief & Intake Throat Size AxB CFM at SP = 0.05 Number of Tiers and Height in Inches (C) 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 10.5 14 17.5 21 24.5 28 31.5 35 38.5 42 45.5 49 52.5 56 59.5 63 66.
MODEL RLX LOUVERED PENTHOUSE Gravity Relief & Intake Cont. Throat Size AxB CFM at SP = 0.05 Number of Tiers and Height in Inches (C) 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 10.5 14 17.5 21 24.5 28 31.5 35 38.5 42 45.5 49 52.5 56 59.5 63 66.
MODEL RLX LOUVERED PENTHOUSE Gravity Relief & Intake Cont. Throat Size AxB CFM at SP = 0.05 Number of Tiers and Height in Inches (C) 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 10.5 14 17.5 21 24.5 28 31.5 35 38.5 42 45.5 49 52.5 56 59.5 63 66.
COMPETITOR CROSS REFERENCE S&P DESCRIPTION GREENHECK COOK PENN CARNES ACME FANTECH LPD SDBD/ RED SDB/DB Low Profile Direct Drive Roof Downblast G ACED DX VEDK PRN 5BDD Direct Drive Roof Downblast G ACED DX VEDX PRN 5DDD Belt Drive Roof Downblast GB DX,KB,JB,MB VEBX PNN 5BDD STXB/TXB Centrifugal Upblast Roof Exhauster - Belt CUBE ACEB ACRUB/ VCR FMX/FX VUBK PNU-RF 5BDU Centrifugal Upblast Roof Exhaust - High Pressure CUBE-HP ACRUB FX VUBK PV 5BDU-762 Centrifugal W
CHEMICAL RESISTANCE CHART 140oF MAXIMUM TEMPERATURE PHENOLIC (HERESITE) 300oF SYNTHETIC RESIN (EISENHEISS) 250oF BAKED EPOXY PHENOLIC (HERESITE) 200oF AIR DRIED ALKYD ENAMEL SYNTHETIC RESIN (EISENHEISS) 300oF REAGENT INVOLVED NON-COATED 3003 ALLOY ALUMINUM BAKED EPOXY MAXIMUM TEMPERATURE AIR DRIED ALKYD ENAMEL REAGENT INVOLVED PAINT SYSTEM NON-COATED 3003 ALLOY ALUMINUM PAINT SYSTEM 300oF 200oF 250oF 300oF 140oF ABRASION (DRY) U S S F F FORMALDEHYDE F N S N F MOISTURE
19