Specification Sheet

212
MODEL KSF
BELT DRIVE CENTRIFUGAL FILTERED SUPPLY FAN
KSF20
GC_KSF_0313 March 2013
MODEL
KSF
CFM OV
Static Pressure in Inches w.g.
1/8 1/4 3/8 1/2 5/8 3/4 1 1 1/4 1 1/2 2
20
2600 652
RPM 245 307 359 - - - - - - -
BHP 0.14 0.23 0.32 - - - - - - -
Sones 4.1 5.8 7.4 - - - - - - -
3000 752
RPM 263 321 371 415 455 - - - - -
BHP 0.19 0.28 0.38 0.49 0.59 - - - - -
Sones 4.8 6.3 7.9 9.4 11.1 - - - - -
3400 852
RPM 282 336 384 426 465 501 - - - -
BHP 0.25 0.35 0.46 0.57 0.69 0.81 - - - -
Sones 5.6 6.9 8.4 9.9 11.5 12.9 - - - -
3800 952
RPM 302 352 398 439 477 512 575 632 684 776
BHP 0.33 0.44 0.55 0.68 0.8 0.93 1.2 1.48 1.77 2.37
Sones 6.4 7.6 9.1 10.5 12.1 13.4 16.1 18.7 21 26
4600 1153
RPM 346 389 429 467 502 536 597 652 703 795
BHP 0.53 0.65 0.79 0.92 1.07 1.22 1.53 1.85 2.18 2.86
Sones 8.3 9.4 10.5 11.8 13.1 14.5 17.1 19.7 22 27
5000 1253
RPM 368 409 447 483 517 549 609 663 714 804
BHP 0.66 0.79 0.93 1.08 1.23 1.39 1.72 2.06 2.41 3.13
Sones 9.3 10.3 11.4 12.7 13.8 15.2 17.8 21 23 27
5400 1353
RPM 391 429 465 499 532 563 621 675 724 814
BHP 0.8 0.94 1.09 1.25 1.41 1.58 1.93 2.28 2.66 3.42
Sones 10.4 11.3 12.4 13.5 14.6 15.7 18.4 21 23 28
5800 1454
RPM 415 450 484 517 548 578 635 687 736 825
BHP 0.97 1.12 1.28 1.44 1.61 1.79 2.15 2.53 2.92 3.73
Sones 11.6 12.5 13.4 14.5 15.5 16.5 19.1 22 24 29
6600 1654
RPM 462 494 525 555 583 611 664 714 760 847
BHP 1.39 1.55 1.72 1.9 2.09 2.28 2.68 3.1 3.53 4.41
Sones 14.1 14.9 15.7 16.7 17.6 18.6 21 23 25 30
7000 1754
RPM 486 517 546 574 602 629 680 728 774 859
BHP 1.64 1.81 1.99 2.18 2.37 2.57 2.99 3.42 3.87 4.79
Sones 15.4 16.1 16.9 17.8 18.8 19.7 22 24 26 31
7400 1855
RPM 511 539 567 595 621 647 696 743 788 871
BHP 1.91 2.09 2.28 2.48 2.68 2.89 3.32 3.77 4.23 5.19
Sones 16.7 17.5 18.2 19.1 19.9 21 23 25 27 31
8200 2055
RPM 560 586 612 637 661 685 731 775 818 897
BHP 2.56 2.75 2.96 3.17 3.39 3.61 4.08 4.56 5.06 6.09
Sones 19.6 21 21 22 23 24 25 27 29 33
8600 2155
RPM 585 610 634 658 682 705 749 792 834 912
BHP 2.93 3.13 3.35 3.57 3.79 4.03 4.51 5.01 5.52 6.59
Sones 21 22 23 23 24 25 27 28 30 34
9200 2306
RPM 622 646 669 691 714 735 778 819 858 934
BHP 3.56 3.77 4 4.23 4.47 4.71 5.22 5.74 6.28 7.4
Sones 24 24 25 26 26 27 29 30 32 35
9600 2406
RPM 647 670 692 714 735 756 797 837 876 949
BHP 4.02 4.25 4.48 4.72 4.97 5.22 5.74 6.28 6.83 7.99
Sones 26 26 27 27 28 29 30 32 33 36
10000 2506
RPM 672 694 715 736 757 777 817 856 893 965
BHP 4.52 4.76 5 5.25 5.5 5.76 6.3 6.85 7.43 8.61
Sones 27 28 28 29 29 30 32 33 35 38
10800 2707
RPM 722 743 763 782 802 821 858 895 930 999
BHP 5.66 5.91 6.17 6.43 6.7 6.98 7.55 8.13 8.74 9.99
Sones 30 31 32 32 33 34 35 36 38 41
11200 2807
RPM 748 767 787 806 824 843 879 915 949 -
BHP 6.29 6.55 6.82 7.09 7.37 7.65 8.24 8.84 9.46 -
Sones 32 33 33 34 35 35 37 38 39 -
11600 2907
RPM 773 792 811 829 847 865 901 935 - -
BHP 6.97 7.24 7.51 7.79 8.08 8.37 8.97 9.59 - -
Sones 34 35 35 36 36 37 39 40 - -
12000 3008
RPM 798 817 835 853 870 888 922 - - -
BHP 7.7 7.97 8.26 8.55 8.84 9.14 9.76 - - -
Sones 36 37 37 38 38 39 40 - - -
12200 3058
RPM 811 829 847 865 882 899 - - - -
BHP 8.08 8.36 8.65 8.94 9.24 9.54 - - - -
Sones 37 38 38 39 40 40 - - - -
R
®
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
AIR
PERFORMANCE
SOUND
and
S&P USA Ventilation Systems, LLC., Div. of Soler &
Palau Ventilation Group, certies that the Models KSF
shown herein are licensed to bear the AMCA Seal.
The ratings shown are based on test and procedures
performed in accordance with AMCA Publication
211 and AMCA Publication 311 and comply with the
requirement of the AMCA Certied Ratings Program.
STANDARD
705
Performance certied is for installation type B: free inlet, ducted
outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances
(accessories). The sound ratings shown are loudness values in
fan sones at a distance of 1.5 m (5 ft) in a hemispherical free
eld calculated per AMCA International Standard 301. Values
shown are for installation type B: ducted outlet hemispherical
sone levels. Ratings do not include the effect of duct end
correction.