Specification Sheet

79
Specications
Polypropylene HRV Core: cross-ow that transfers sensible heat
Typical Airow Range: 30-100 CFM
Duct Connections: Four (4) 5” oval ISF double collar system
Number Motors: Two (2) PSC variable speed backward curved
V Hz Phase Amperage
120 60 Single 0.85 A / 66 watts
Exchange surface: 63.5 ft
2
Defrost type: Evacuation
Filters: Two (2) Fiberbond washable
Drain Connection: 1/2”
DuoTrol: Integrated Balancing System
Weight: 33.5 lbs (unit), 41 lbs (in carton)
Dimensions: 22” W x 19-13/16” L x 14-19/32” H
Options:
HRT-3 - Push Button Timer
HRRD-1 - Dehumidistat
HRRD-3P - Dehumidistat
Dimensions
9.8"
247.9 mm
1.1"
27.9 mm
5" oval
127 mm
14.6"
371 mm
17.1"
448.8 mm
1.1"
28.5 mm
20"
507 mm
2.1"
52.5 mm
Front View
Top View
12"
305 mm
15"
381 mm
2"
50.8 mm
3"
76.2 mm
2"
50.8 mm
Minimum clearance
for balancing
Ceiling
Wall
Wall
Minimum clearance for drain fitting
Recomended minimum clearance
for “P” trap of 10" (254 mm)
Minimum door clearance
Front View
Top View
Minimum Clearance Data
Supply
Temperature
Net Air Flow
Power
Consumed
(Watts)
Sensible
Recovery
Efciency
Apparent
Sensible
Effectiveness
°F °C CFM L/s
32 0 40 19 28 64 72
32 0 65 30 40 59 66
-13 -25 37 18 30 55 73
Energy Performance (Heating)
External Static
Pressure
Net
Air Flow
Gross Air
Flow
Supply
Gross
Air Flow
Exhaust
Pa in. w.g. L/s CFM L/s CFM L/s CFM
25 0.1 47 99 48 100 48 102
50 0.2 44 93 45 94 43 92
75 0.3 39 83 40 84 38 80
100 0.4 35 75 35 75 36 78
125 0.5 30 65 30 66 32 68
150 0.6 27 56 27 57 25 52
175 0.7 22 46 22 47 19 41
Ventilation Performance
HR100V
MODEL HR
HEAT RECOVERY VENTILATORS