Solis RHI-HV Series Hybrid Inverter Instruction Manual (For USA) Ver 1.1 Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: +86 (0)574 6578 1806 Fax: +86 (0)574 6578 1606 Please adhere to the actual products in case of any discrepancies in this user manual. If you encounter any problem on the inverter, please find out the inverter S/N and contact us, we will try to respond to your question ASAP.
Contents 1. Introduction ………………………………………………………………………………………………………………… 1.1 Product Description 1.2 Packaging ………………………………………………………………………………………………………… ………………………………………………………………………………………………………………………… 2. Safety & Warning 2.1 Safety ……………………………………………………………………………………………………… ……………………………………………………………………………………………………………………………… 2.2 General Safety Instructions 2.3 Notice For Use 3. Overview ………………………………………………………………………………………………………………………… ………………………………………………………………………………………………………………………… 3.1 Screen 3.
1. Introduction 1. Introduction 1.2 Packaging 1.1 Product Description The Solis RHI-HV 5G series is designed for residential hybrid systems, which can work with high voltage lithium ion batteries to maximize self-consumption rate. This product can operate in both ON-Grid and OFF-Grid modes. The Solis RHI-HV series hybrid inverters contain 3 different models which are grid support transformerless utility interactive inverters: RHI-1P5K-HVES-5G, RHI-1P7.
2. Safety & Warning 2. Safety & Warning 2.1 Safety The following types of safety instructions and general information appear in this document as described below: WARNING: DANGER: “Danger” indicates a hazardous situation which if not avoided, will result in death or serious injury. Electrical installations must be done in accordance with the local and national electrical safety standards.
2. Safety & Warning 3. Overview 3.1 Screen Solis RHI-HV series adopts a 7 inch color screen. It displays the status, operating information, and settings of the inverter. WARNING: Operations below must be accomplished by licensed technician or Solis authorized person. 3.2 Keypad There are four keys in the front panel of the inverter (from left to right): ESC, UP, DOWN and ENTER keys. The keypad is used for: WARNING: AC-BACKUP of RHI-HV series is forbidden to connect to the grid.
4. Installation 4. Installation 4.1 Select a Location for the Inverter To select a location for the inverter, the following criteria should be considered: WARNING: Risk of fire Despite careful construction, electrical devices can cause fires. Do not install the inverter in areas containing highly flammable materials or gases. Do not install the inverter in potentially explosive atmospheres. Install on a wall or strong structure capable of bearing the weight of the machine (30kg).
4. Installation 4. Installation 4.2 Mounting the Inverter 2.Lift up the inverter (be careful to avoid body strain) and align the back bracket on the inverter with the convex section of the mounting bracket. Hang the inverter on the mounting bracket and ensure the inverter is secure (see Figure 4.5) Dimensions of mounting bracket: Figure 4.3 Inverter wall mounting Once a suitable location has been found according to 4.1 using figures 4.3 and 4.4 mount the wall bracket to the wall.
4. Installation 4. Installation 4.3 PV Terminals Please ensure the following before connecting the inverter: NOTE: The installation shall meet the National Electrical Code, ANSI/NFPA 70 and Canadian Electrical Code wiring methods. Ensure the voltage of the PV string will not exceed the max DC input voltage (500Vdc). Violating this condition will void the warranty. Ensure the polarity of the PV terminals are correct. Ensure the DC-switch, battery, AC-BACKUP, and AC-Grid are all in their off-states.
4. Installation 4. Installation 2. Lead the AC cable through the cable gland and the housing. Over-Current Protection Device (OCPD) for the AC side 3. Remove a length of 40mm of the cable jacket and strip the wire insulation to a length of 18 – 19mm. To protect the inverter's AC connection line, we recommend installing a device for protection against over-current and leakage, with the following characteristics noted in Table 4.2: 4. Each of the terminals are labeled.
4. Installation 4. Installation Note: The battery fuses in the wiring box are replaceable. The replacement must be done by Solis authorized technicians only. Fuse specification: 600V, 30A. Note: Before connecting the battery, please carefully read the user manual of the battery and perform the installation exactly as the battery manufacturer requests. Cable connection steps: 1. Use slot type screwdriver to press the block on the top. 2. Insert the exposed copper part of the cable into the terminal. 4.6.
4. Installation 4. Installation 4.6.2 Battery Communication 4.6.3 RS485 Communication Communication Terminals: CANL,CANH,ENABLE,GND,BMS485B,BMS485A Different battery types have different communication requirements. Communication Terminals: RS485B and RS485A. BYD Battery For BYD Battery-BoxH, CANL and CANH are used. The detailed connection is shown in the following figure. BYD Battery-BoxH 1 3 5 7 9 2 4 6 8 10 1 3 5 7 9 2 4 6 8 10 Solis-RHI-1P(5-10)K-HVES Figure 4.
4. Installation 5. Operation 4.7 External Ground Connection An external ground connection is provided at the right side of inverter. Prepare OT terminals: M4. Use proper tooling to crimp the lug to the terminal. Pressing the ESC key calls back the previous menu Connect the OT terminal with ground cable to the right side of inverter. The torque is 2N.m. main menu information UP/DOWN settings ESC Monthly Energy ENTER UP/DOWN Main interface ESC advanced info.
5. Operation 5. Operation 5.2 Main Menu After setting the language, press "ESC" to access the main page. There are four submenus in the Main Menu: 1. Information 2. Settings 3. Advanced Information Settings Menu 4. Advanced Settings 2015-02-23 19 35 Information 2.526 KWH Settings COM OK Advanced Information Advanced Settings Figure 5.3 Main Page Figure 5.4 Main Menu On the main page, Press "ESC" : View the yield data on monthly bar charts.
5. Operation 5. Operation Settings General Info 2015-02-23 19 35 Inverter SN: 000F80017A20515 DRM NO.: 08 Device Status: Waiting Model NO.: 00 Battery Status: Waiting Software Ver.:040000 Backup Status: Waiting Grid Status: Off Grid Mode Wakeup Status: Undone ESC Settings Energy Records Total Energy: 0000008kWh Today: 0000.0kWh Yesterday: 0000.0kWh This Month: Last Month: This Year: Last Year: 0000kWh 0000kWh 0000000kWh 0000008kWh ESC Figure 5.6 General Info System Info Settings Figure 5.
5. Operation 5. Operation 5.4 Settings Settings Meter Info 2015-02-23 19 35 External: Meter VoltageL1:000.0V Meter CurrentL1:00.00A Meter VoltageL2:000.0V Meter CurrentL2:00.00A Meter Power: +000000W Meter Energy: 0000000.00kWh Output Energy: 0000000.00kWh Internal: Meter Voltage: Meter Current: Meter Power: Meter Energy: Output Energy: In the "Settings" section, Time/Date, Slave address and language can be modified. Settings 2015-02-23 19 35 000.0V 00.00A +000000W 0000000.00kWh 0000000.
5. Operation 5. Operation 5.5 Advanced Information 5.4.2 Set Address Set the slave address of the inverter. The default address is 01. Settings Set Address 2015-02-23 19 35 Slave Address:01 Detailed information can be viewed in this section: 1. Alarm Message 2. Warning Message 3. Running Status 4. Communication Data 5.
5. Operation 5. Operation 5.5.2 Warning Message 10 pages of latest warning messages (5 per page). Settings General Status 2015-02-23 19 35 Warning message shows the warning that is abnormal but will not lead to inverter shutdown. Settings Message Warning 2015-02-23 19 35 Message Data Date/Time DC Bus Voltage: 000.0V Power Factor: -0.00 Power Limit: 000% Inverter Temperature: +000.0degC Grid Standard: NO message. ESC Figure 5.19 General Status ESC UP DOWN ENT Figure 5.
5. Operation 5. Operation 5.6 Advanced Settings - Technicians Only 5.5.4 Communication Data Internal communication data can be viewed in this section. For maintenance person only. Values are for reference only.
5. Operation 5. Operation 5.6.1 Select Standard This function is used to select corresponding grid standards. Please refer to the actual LCD setting for the grid standard options. Press the UP/DOWN keys to select the standard (UL-240V, UL-208V, R21P3-240, R21P3-208, ISONE240, ISONE208, MEX-CFE , User-Def, etc.). Press the ENTER key to confirm the setting. Press the ESC key to cancel changes and return to previous menu.
5. Operation 5. Operation SettingsSelect Battery Battery Module: 2015-02-23 19 35 ForceCharge SOC: 005% B-BOX HV YES= NO= UP ESC Figure 5.28 Battery Select DOWN ENT Figure 5.30 ForceCharge SOC 5.6.3.2 Battery Wakeup SettingsSelect Battery 2015-02-23 19 35 Settings Battery Control 2015-02-23 19 35 OverDischg SOC: 020% Battery Select Battery Wakeup YES= NO= ESC UP DOWN Figure 5.29 Over Discharge SOC. YES= NO= ENT Figure 5.
5. Operation 5. Operation 5.6.4 Backup Control 5.5.4.2 Backup Settings This section is used to set the configuration of the backup port. Settings Backup Control 2015-02-23 19 35 This section shows the parameter of the backup port. Settings Backup Settings 2015-02-23 19 35 Backup Voltage: 230.00V Backup Frequency:50.0Hz Voltage Droop: Disable Backup ON/OFF Backup Settings SELECT= DONE= YES= NO= Figure 5.34 Backup Settings Figure 5.32 Backup Control 5.6.4.
5. Operation 5. Operation 5.6.5.1 Meter Select The setting is used to select the meter type based on the actual configuration. Settings Mode Select Storage 2015-02-23 19 35 NOTE: Select "1Ph Meter" to be compatible with the meter that comes with the inverter package. The "3Ph Meter" is not available yet which is reserved for future development. Settings Meter Select Mode: Time Charging 2015-02-23 19 35 Meter Type: 1Ph Meter Figure 5.
5. Operation 5. Operation 5.6.6.1 Working Mode Set Off Grid Mode: There are TWO situations with different grid standards selected. Enable the mode for off-grid systems. 5.6.6.1.1 With UL Standard selected The AC Grid Port must be physically disconnected. Settings Off Grid Mode NOTE: 2015-02-23 19 35 The following modes are for "UL-240V", "UL-240V-A". ON NOTE: OFF Parameter Accuracy: Voltage:1%; Current:1%; Frequency:0.06Hz; Power:4%; Time:0.12s; PF:0.01.
5. Operation 5. Operation Default Settings for UL1741SA: Q1: (0-60%) Default +30% II under-excited Q4: (-60%-0%) Default -30% Rated 240V Grid V1:(192-240V) Default 210V V2: (192-240V) Default 236V V3:(240-288V) Default 243V V4: (240-288V) Default 264V -1,0 V2: (166-208V) Default 205V V3:(208-240V) Default 211V V4: (208-240V) Default 229V Volt-Var Voltage1: Voltage2: Voltage3: Voltage4: Leading: Leading: 1,0 -0,2 P/P n 0,6 III over-excited 2015-02-23 19 35 210.0V 236.0V 243.0V 264.
5. Operation 5. Operation 5.6.6.1.2 With Rule21 Standard selected Default Settings for UL1741SA: Rated 240V Grid NOTE: V1:less than V2 The following modes are for "R21P3-240", "R21P3-24A". V2:less than Vstart V3 (Vstart): (240-288V) Default264V NOTE: V4 (Vstop): (264-312V) Default 288V Parameter Accuracy: Voltage:1%; Current:1%; Frequency:0.06Hz; Power:4%; Time:0.12s; PF:0.01.
5. Operation 5. Operation 4.Fixed-PF 3. Volt-Var Description: Inverter will change the reactive output power based on voltage change. Description: Inverter will output power with fixed power factor. Setting Range: -0.8 to +0.8 Default value is PF = 1 Q1,cap Fixed-PF 2015-02-23 19 35 Q2=Q3=0 V1 V2 Vnom V3 V4 Power Factor: Q4,ind +1.00 Figure 5.
5. Operation 5. Operation 6. P-Factor (Not Required) To set both modes (Volt-watt in high priority) Description: Inverter will change power factor based on changing output power. Step 1: Select and set Volt-var mode at first. Note: This Setting is NOT required by Rule21 Standards. Step 2: Enter "Working Mode" again and select and set Volt-watt mode then. Step 3: To check the priority, a new mode will appear as "V-P & V-Q" which NOTE: indicates (P) Volt-watt is in high priority.
5. Operation 5. Operation 5.6.6.2 Ramp Rate Limit 5.6.6.4 10mins Voltage Set This function is used for changing power ramp up rate. This function is disabled and not used for the US. When the inverter initializes or string MPPT changes, the ramp up rate is limited. NOTE: The default setting is stop (disable). The setting range is from 10% to 600%, This will change the power change rate per minute.
5. Operation 5. Operation 5.6.8.1 Backflow Power 5.6.7 Software Update The software update includes the HMI and DSP. Corresponding firmware version can be checked in this setting. Press “ENT” to enter the upgrading mode. Determine the allowed backfeed power. (System export to the grid) Settings Power Backflow Settings Software Update 2015-02-23 19 35 2015-02-23 19 35 B ackflow Power:+ 1200W HMI Update DSP Update YES= NO= ESC YES= NO= UP DOWN ENT Figure 5.
5. Operation 5. Operation 5.6.8.3 FailSafe ON/OFF When this Failsafe function is ON, the inverter will shutdown once it loses Total Energy communication with the meter in case of any backflow power exceeds the limit. Total Energy: 56 kWhpower Adjusting total00000 generating Settings ON/OFF FailSafe 2015-02-23 19 35 2015-02-23 19 35 ON OFF YES= NO= UP ESC DOWN ENT Figure 5.62 Total Energy YES= NO= Figure 5.60 FailSafe ON/OFF 5.6.
6. Commissioning 5. Operation 5.6.10 Reset Password 6.1 Preparation of Commissioning Reset Password: In this menu, user can reset the inverter password, but the admin password is always valid. Settings Reset Password 2015-02-23 19 35 Please Input New Password X X X X Ensure all the devices are accessible for operation, maintenance, and service. Check and confirm that the inverter is firmly installed. Space for ventilation is sufficient for one inverter or multiple inverters.
7. Troubleshooting 7. Troubleshooting heatsink will help the inverter dissipate heat and increase the lifetime of inverter. The dirt on the When faults occur, the “Fault” state will be shown on the main screen. Follow the steps below to determine which fault has occurred. inverter can be cleaned with a soft brush. Steps: Enter → Down → Advanced Information→ Enter →Alarm Message. Solis RHI Series inverter does not require any regular maintenance.
7. Troubleshooting 7. Troubleshooting Step3: Press DOWN to select Alarm Message, then press ENTER. Advanced Information Settings 2015-02-23 19 35 Alarm Message Warning Message Running Status Alarm Message Failure description Solution ARC-FAULT ARC detected in DC circuit 1. Check if there is an arc in the PV connection and restart inverter. AFCI Check FAULT AFCI module self check fault 1. Restart inverter or contact installer. DCinj-FAULT High DC injection current 1.
7. Troubleshooting 7. Troubleshooting Alarm Message Failure description Solution Alarm Message Failure description Solution OV-DC01/02/03/04 Over DC voltage 1. Reduce the module number in series. UN-BUS01/02 Under DC bus voltage 1. Check inverter inductor connection. 2. Check driver connection. UN-G-F01/02 Under grid frequency DC input overcurrent 1. Restart inverter. 2. Identify and remove the string of the faulted MPPT. 3. Change power board. UN-G-V01/02 Under grid voltage 1.
8. Specifications Technical Data 8. Specifications RHI-1P5K-HVES-5G RHI-1P7.6K-HVES-5G 7000W 10600W Input DC (PV side) Recommended max. PV power Output AC(Grid side) Rated output power 5kW 7.6kW Max. apparent output power 5kVA 7.6kVA Max. input voltage 500V Operation phase Rated voltage 330V Rated grid voltage Start-up voltage 120V The grid voltage range 90-450V Rating grid frequency MPPT voltage range Full load MPPT voltage range Max. input current Max.
8. Specifications 8. Specifications General data Dimensions(W/H/D) Technical Data 20.2*28.1*8.18 in (539*717*250 mm) RHI-1P10K-HVES-5G Input DC (PV side) Weight 66.1 lbs (30 kg) Recommended max. PV power Topology Transformerless Max. input voltage 500V Rated voltage 330V Operation temperature range Ingress protection -25~+60 ℃/-13~+140 ℉ NEMA 4X Noise emission <30 dB (A) Cooling concept Natural convection Max.
8. Specifications 8. Specifications Output AC(Grid side) General data Rated output power 10kW Dimensions(W/H/D) Max. apparent output power 10kVA Weight 66.1 lbs (30 kg) 1Ф/PE Topology Transformerless Operation phase Rated grid voltage 208V / 240 V Operation temperature range Ingress protection 20.2*28.1*8.
9. Appendix 9. Appendix 9.1 Solutions for different grid topology This product is designed for the following two types of grid topology. Type 1: Grid with Neutral grounded Please follow the below circuit diagram to configure the connection: .72. Type 2: Grid without Neutral Please follow the below circuit diagram to configure the connection (Use the central tap N of the auto-transformer to ground the neutral): .73.
9. Appendix Type 3: Special grid topology For the following grid topology, the standard hybrid inverter is NOT applicable. Please contact Solis to purchase necessary accessories to be compatible with them. Requirements: 1. A special contactor box (Automatic change-over switch box) 2.