4. Installation4. Installation
2. Lead the AC cable through the cable gland and the housing.
3. Remove a length of 40mm of the cable jacket and strip the wire insulation to a length of
18 – 19mm.
4. Each of the terminals are labeled. Ensure that the correct conductor is fastened
(2 N.m. torque) to the correct terminal.
5. Ensure the rib of the terminal block and the groove on the housing engage correctly
and a “click” is heard or feltt.
BL1 BL2 L2L1
AC-BACKUP AC-GRID
Figure 4.7 AC output terminals
40 mm
18 mm - 19 mm
N
L1
L2
40 mm
18 mm - 19 mm
L2
L1
Over-Current Protection Device (OCPD) for the AC side
To protect the inverter's AC connection line, we recommend installing a device for protection
against over-current and leakage, with the following characteristics noted in Table 4.2:
RHI-1P5K-HVES-5G
RHI-1P7.6K-HVES-5G
RHI-1P10K-HVES-5G
Table 4.2 Rating of grid OCPD
Inverter
Rated
voltage(V)
Rated output
current (Amps)
Current for protection
device (A)
24/21
36.5/31.7
48/41.7
208/240
208/240
208/240
30/30
50/40
60/60
Note:
AC Grid and AC Backup output 240V L1-L2.
For 120V load, auto-transformer is required in the system.
For detailed information about the autotransformer please refer to
Solis auto-transformer quick installation guide.
4.5 Battery Fuse Terminals
Battery power cables should be connected to the battery fuse terminals in the wiring
box through the BAT conduit.
Figure 4.8 Connected to the battery fuse terminals
Exposure length
10~8 AWG
12 mm
2~4N.m
Cross sectional area
Torque
Table 4.3 Battery power cable requirement