Operating Instructions and Installation Instructions

– 23
t
General information
¾ As delivered, DIP switches are set to the “OFF” position, all additional
functions are switched off.
¾ Cable length max. 10 m (at the terminal): 9 + 10, 11 + 12
¾ Cable length max. 30 m (at the terminal): 5 + 6, 7 + 8
Obstacle detection (DIP 1, 2 + 3)
Drive behavior when opening the door
If the door encounters an obstacle (power cut-off) or a safety input is
interrupted (e.g. someone passes through the photo eye), the drive detects
this and reacts according to the setting of DIP switch 1.
DIP switch 1
OFF No reaction during an interruption of a safety input. The door
stops during a power cut-off.
ON The drive stops the door.
Drive behavior when closing the door
If the door encounters an obstacle (power cut-off) or a safety input is
interrupted (e.g. someone passes through the photo eye), the drive detects
this and reacts according to the setting of DIP switches 2 + 3.
DIP switch 2: Function: safety connection
OFF NC contact for photo eye.
ON Button connection for button 2
(partial opening, dened opening and closing).
DIP switch 3: behavior of drive when the door closes.
OFF Drive stops and opens the gate slightly, reversion.
ON The drive stops and opens the door completely.
Connecting photo eyes
¾ Permissible cable gauge: max. 0.75 mm².
8
9
10 11
12
7
2
1
ON
DIP
3
4
5
6
8
7
Terminals 7 + 8 Safety connection, only if DIP switch 2 “OFF”.
Terminals 9 + 10 Regulated DC 24 V, max. 0.1 A
Terminal 9: DC 24 V
Terminal 10: ground
Settings: Refer to the chapter “Functions and connections - obstacle
detection (DIP 1, 2 + 3)”
Connect button 2 (DIP 2)
¾ Permissible cable gauge: max. 0.75 mm².
ATTENTION!
Only use the connection for potential-free closer contacts.
External voltage can damage or destroy the controller.
Button 2 can be used as needed for the following functions:
Dened opening and closing
Partial opening
ALWAYS OBSERVE!
If button 2 is used, a safety connection is no longer available.
8
9
10 11
12
7
2
1
ON
DIP
3
4
5
6
8
7
Terminals 7 + 8 Connection for button 2 only if DIP switch 2 ON
Connect warning light (DIP 4)
¾ Permissible cable gauge: max. 0.75 mm².
8
9
10 11
12
7
2
1
ON
DIP
3
4
5
6
8
7
Terminals 11 + 12 Unregulated DC 24 V (max. 34 V), max. 1 A
DIP switch 4
OFF
Connected warning light is blinking (controller generates blinking).
ON Door status display
Lights up if the door is not closed
Is off if the door is closed
Functions and connections