Operating Instructions and Installation Instructions

Functions and connections
t
– 24
Direct connector (button 1)
NOTE!
Reverse the connections (terminals 3 + 4) when using the
drive for a hinged double door.
¾ Permissible cable gauge: max. 1.5 mm².
2
3
4 5
6
1
Terminals 1 + 2 Transformer
Terminal 3 C-rail
Terminal 4 Chain
Terminals 5 + 6 Button connection (button 1)
ATTENTION!
Only use the connection (terminals 5 + 6) for potential-free
closer contacts. External voltage can damage or destroy the
controller.
Prewarning time (DIP 5)
Before the drive starts, a warning light blinks for 3 seconds after the button
or the hand-held transmitter is pressed. The prewarning time is cancelled
if the button or hand-held remote control is actuated again within this
timeframe.
The prewarning time affects both the internal illumination and a connected
warning light.
DIP switch 5
OFF Deactivated
ON Activated, internal lighting and warning light blink for 3 seconds.
Backjump (DIP 6)
NOTE!
You can set DIP switch 6 to ON for sectional doors or
doors with ceiling guides; this relieves the drive and door
mechanisms. Simpler actuation of the emergency release.
Serves to relieve the door and drive mechanical system. After reaching the
door CLOSE end position, the drive moves in the direction of door OPEN,
relieving the mechanical system.
DIP switch 6
OFF Deactivated
ON Activated
Dened opening and closing
(DIP 7)
NOTE!
With this function, only button 1/radio channel 1 opens the
door and button 2/radio channel 2 closes the door.
1
2
Button 1/channel 1 opens and button 2/channel 2 closes the door.
This function can also be used with only 2 buttons or just with hand-held
remote controls.
Requirement:
DIP switch 8 “OFF”
2 buttons connected (DIP switch 2 ON) or 2 hand-held transmitter
buttons programmed.
2
1
ON
DIP
3
4
5
6
8
7
6
DIP switch 7
OFF Deactivated
ON Activated