User manual

PQM-702, PQM-703 Operating Manual
100
6.6.1 Event detection hysteresis
Event detection hysteresis
Range
Calculation method
Hysteresis
0..10%
For each of the parameters calculated as a per-
centage of maximum threshold value (for ex-
ceptions see 3.12)
6.7 Recording
Recorder
Averaging time
(1)
200 ms, 1 s, 3 s, 5 s, 10 s, 15 s, 30 s, 1 min, 3 min, 5 min, 10 min, 15 min,
30 min, 60 min, 120 min.
Special Mode: ½ period (recording only U
RMS(1/2)
and I
RMS(1/2)
)
(2)
Averaging min / max for U
RMS
½ period, period, 200 ms, 1 s, 3 s, 5 s
(3)
Averaging min / max for I
RMS
½ period, period, 200 ms, 1 s, 3 s, 5 s
(3)
Waveforms
Option to record three periods of waveforms for active channels, after
each averaging period
Recording activation mode
manual
starting at the first detected event
scheduled (four defined time intervals)
Measurement Points
4 independent user configurations, defined memory allocation space on
the memory card, the option to allocate the whole space to a given point
Recording time
Depending on the configuration (see 2.7.3)
Memory
Built-in 8 GB memory card
Memory Model
Linear
Security
Key lock to prevent unauthorized access, data read-out lock with PIN
(1) Averaging times shorter than 10 sec. are in fact equal to a multiple of the mains cycle:
200 ms 10/12 cycles, 1 s 50/60 cycles, 3 s 150/180 cycles, 5 s 250/300 cycles.
(2) U
RMS(1/2)
and I
RMS(1/2)
are effective values for one cycle, refreshed every half-cycle.
(3) Averaging periods min./max. 200 ms, 1 s, 3 s, 5 s are in fact equal to a multiple of the mains cycle: 200 ms
10/12 cycles, 1 s 50/60 cycles, 3 s 150/180 cycles, 5 s 250/300 cycles
Recorded parameters
Mean
value
Minimum
value
Maximum
value
Instanta-
neous
value
RMS phase/phase-to-phase voltage (depending on
the type of system) U
RMS
RMS phase-to-phase voltage (only 3-phase wye
system with N and 2-phase system) U
RMS
RMS current I
RMS
Frequency f
Voltage crest factor CF U
Current crest factor CF I
Unbalance factors for negative and positive se-
quence, symmetrical components: negative, posi-
tive, zero (voltage) U
0
, U
1
, U
2
, u
0
, u
2
Unbalance factors for negative and positive se-
quence, symmetrical components: negative, posi-
tive, zero (current) I
0
, I
1
, I
2
, i
0
, i
2
Flicker severity P
st
and P
lt
Active power (consumed and supplied) P
+
, P
-
Reactive power (consumed and supplied) Q
1+
, Q
1-
/
Q
B+
, Q
B-
Apparent power S
Distortion power D / Apparent distortion power S
N
Power Factor PF
Displacement power factor cosφ/DPF
Tanφ factor
Active energy (consumed and supplied) E
P+
, E
P-
Reactive energy (consumed and supplied) E
Q+
, E
Q-