1.7 Compliance with standards
The analyzer is designed to meet the requirements of the following standards.
Standards valid for measuring network parameters:
IEC 61000-4-30:2011 – Electromagnetic compatibility (EMC) - Testing and measurement
techniques - Power quality measurement methods,
IEC 61000-4-7:2007 – Electromagnetic compatibility (EMC) – Testing and Measurement
Techniques - General Guide on Harmonics and Interharmonics Measurements and
Instrumentation for Power Supply Systems and Equipment Connected to them,
IEC 61000-4-15:2011 – Electromagnetic compatibility (EMC) – Testing and Measurement
Techniques - Flickermeter - Functional and Design Specifications,
EN 50160:2010 – Voltage characteristics of electricity supplied by public distribution networks.
Safety standards:
IEC 61010-1 – Safety requirements for electrical equipment for measurement control and
laboratory use. Part 1: General requirements
Standards for electromagnetic compatibility:
IEC 61326 – Electrical equipment for measurement, control and laboratory use. Requirements
for electromagnetic compatibility (EMC).
The device meets all the requirements of Class A as defined in IEC 61000-4-30. The summary
of the requirements is presented in the table below.
Tab. 2. Summary of selected parameters in terms of their compliance with the standards
Aggregation of measure-
ments at different inter-
vals
IEC 61000-4-30 Class A:
Basic measurement time for parameters (voltage, current, harmonics, unbal-
ance) is a 10-cycle interval for 50 Hz power supply system and 12-cycle inter-
val for 60 Hz system,
Interval of 3 s (150 cycles for the nominal frequency of 50 Hz and 180 cycles
for 60 Hz),
Interval of 10 minutes,
Interval of 2 h (basing on 12 intervals of 10 min.)
Synchronization of aggregation intervals
Real-time clock (RTC)
uncertainty
IEC 61000-4-30 Class A:
Clock synchronization to GPS time using the built-in GPS receiver with inter-
nal or external antenna,
Built-in real time clock, which is set from "Sonel Analysis 2",
RTC accuracy after GPS signal loss - better than ±0.3 s/day
Frequency
Compliant with IEC 61000-4-30 Class A of the measurement method and uncer-
tainty
Power supply voltage
Compliant with IEC 61000-4-30 Class A of the measurement method and uncer-
tainty
Voltage fluctuations
(flicker)
The measurement method and uncertainty meets the requirements of IEC
61000-4-15 standard.
Dips, interruptions and
surges of supply voltage
Compliant with IEC 61000-4-30 Class A of the measurement method and uncer-
tainty
Supply voltage unbal-
ance
Compliant with IEC 61000-4-30 Class A of the measurement method and uncer-
tainty
Voltage and current har-
monics
Compliant with IEC 61000-4-30 Class A of the measurement method and uncer-
tainty (IEC 61000-4-7 Class I)
Voltage and current
interharmonics
Compliant with IEC 61000-4-30 Class A of the measurement method and uncer-
tainty (IEC 61000-4-7 Class I)
Mains signalling voltage
on the supply voltage
Compliant with IEC 61000-4-30 Class A of the measurement method and uncer-
tainty