User manual
2 Operation of the analyzer
33
To change the main settings of the measurement point, single-click Measurement point 1 at
'Local' panel. The screen should look as sown in Fig. 23.
Set the following items:
mains system (element as in Fig. 23) as a single-phase,
nominal voltage at 230/400 V,
nominal frequency at 50 Hz,
averaging period at 1 s,
triggering at Immediate,
event detection hysteresis at 1.5%,
clamp type set to None,
voltage transducers and N-PE voltage (in section Additional measurements ) set
as unchecked,
In the upper part of the window select the second tab Additional, where sliders may be used
to set the required time of recording waveforms and RMS
1/2
graphs for events and recording times
for transient graphs. These times should be set according to individual preferences.
Then select Standard card from the tree with settings and ensure that "Enable logging
according to Standard" box is not checked.
Adjust settings at Voltage card and Basic tab, as shown in Fig. 24.
Fig. 24. Settings for 'Voltage' card in scenario 1.
At Additional card select only the average value for the frequency, and uncheck other boxes.