If a malfunction occurs which is traced to the transmitter, it should be removed for 
inspection and tested. If the transmitter has been subjected to excess pressure, 
vibration, shock or extreme supply voltage (as in the case of a lightning strike), 
damage may be indicated by a constant output, irrespective of the applied pressure. 
Overpressure may also cause high or unstable readings.
Blocked pressure ports or pipes may cause a similar symptom and should be rectified 
before carrying out further tests.
The transmitter can withstand pressure of 150% of its rated range without calibration 
change. Pressures above this may cause irreparable damage. Frequent causes of such 
overpressures are high transient pressures, which may not be easy to detect during 
normal operation.