User Manual

Form 1588 (09.14) ©SOR Inc. 
3/24
NAMEPLATE AREA
SET SCREW
ANNUNCIATION PATH
EXTERNAL GROUND
PROVISION
Electrical Termination - 4-20 mA Output
Drawing 
0091546
Formula for determining 
maximum loop resistance
R
L
 (MAX) = V
Supply 
- 10V
   20mA
NOTE: An external ground screw is included for additional 
earth ground connection.
72” flying leads are provided for connection 
to a terminal strip within a cabinet or a splice 
within an outlet box:
  Red (+)  Loop Voltage: 10 to 36 VDC
  Black (–)  Output: 4 to 20 mA
 Orange Switch Contacts:
  Yellow  Normally Open Solid-State Relay
 Brown  RS-485 (A)
 White  RS-485 (B)
  Blue  (Used for 1-5 VDC Output)
  Green  Earth Ground
  Bare  Drain Wire - Connected to 
    Earth Ground (trimmed at factory)
}
}
}
Horizontal Installation
 
The following figure depicts the proper horizontal installation profile; with the external 
ground provision and set screw (annunciation path) oriented downward.
 
The nameplate (tag) should not cover the set screw. 
  Align the nameplate slot with the set 
  screw; i.e., the set 
  screw should be 
  visible in the 
 nameplate slot.
Drawing 
0091555