Instruction Manual
Form 925 (08.13) ©SOR Inc. 
1/16
The RF Two-Wire Level Control produces a 7.5 mA (± 1.5 mA) or 
14.5 mA (± 2 mA) current to indicate liquid presence/absence at the 
sensor. A sensor attached to the control acts as an antenna to 
transmit the process material level to the electronics.
The Failsafe Select switch determines the output of the unit when the 
process is touching the probe. A green LED on the control indicates 
7.5 mA (±1.5 mA) output. A yellow LED on the control indicates 
14.5 mA (± 2 mA) output.
The RF Two-Wire level Control can be mounted with the sensor in 
the process (integral units K housing), or up to 150’ (45m) from the 
sensor in the remote configuration (R housing). 
The RF Two-Wire level Control constantly monitors sensor integrity. 
In the unlikely event of a sensor failure or remote electronic sensor 
module failure, the red LED is lit and indicates 25.5 mA (±1.5 mA) output.
An optional timer (DT accessory) is available to delay the current change 
from 0 seconds to 10 minutes. The delay timer provides added process 
control, valuable for use in turbulent conditions. An optional adjustable 
differential circuit (AD accessory) allows the user to select on and off at 
different level points for the control.
DT and AD accessories may not be used on the same control unit.
 General Instructions
Registered Quality System to ISO 9001
Design and 
specifications are 
subject to change 
without notice. 
For latest revision, go to 
sorinc.com
 Table of Contents 
Pre-Installation Test ............................2
Installation ....................................... 3
Remote Cable Connection .....................4
Electrical Connection ...........................5
SOR RF Probe Grounding Scheme ...........6
Set Point and Sensor Monitor Calibration ..7
Adjustable Differential Calibration ...........9
Delay Timer Operation .........................9
Sensor Replacement ......................... 10
Circuit Board Replacement .................. 10
Troubleshooting ............................... 11
Dimensions ................................ 12-14
p
ut
.
g
e 
s
e
a
t 
NOTE: If you suspect that a product is 
defective, contact the factory or the 
SOR
®
 Representative in your area for 
a return authorization number (RMA). 
This product should only be installed 
by trained and competent personnel.
 RF Two-Wire Level Control 
with Sensor Monitor