Owner manual
Form 841 (08.13) ©SOR Inc. 
3/16
Remote Cable Connection
Bracket
Open Sump or Basin
Do not suspend the unit by rigid conduit 
installed in the electrical hub. When installing 
the unit over an open sump or basin, use a 
suitable bracket to support the instrument.
NOTE: The instrument must be positioned so that
over ow does not  ood electrical housing. (See 
)
Conduit must be installed 
between the sensor base 
and the electronics housing 
to provide a raceway for 
sensor extension cables. 
(See
) The sensor base 
and the electronics hous-
ing are suitable for use in 
Class I Group C & D; Class 
II Groups E, F & G; Division 
1 & 2 Hazardous Locations. 
All conduit and fittings used 
for the installation must 
equal or exceed this rating to 
maintain the explosion proof 
integrity of the assembly.
Fishing the sensor 
extension cables
Two sensor extension cables 
are supplied. Both ends of the 
cables are terminated and labeled 
at the factory. Use care to avoid 
damaging the factory installed 
coax connectors while fishing the 
sensor extension cables through 
the conduit. Pull cables from the 
electronics housing so that the 
free ends follow the fish through 
the conduit. (See
)
Control Board 
See Figures 
,
, &
Remote 
Interconnect 
Board 
See
Conduit must meet 
Class I Group C & D; Class II 
Groups E, F & G; Div 1 & 2
Sensor Base
Electronics 
Housing
Protect factory 
installed plugs
Connect Extension 
Lead T to 
OUT 2
Connect 
Extension 
Lead A to 
OUT 1
Remote Interconnect 
Board located inside 
sensor base
Connect Sensor 
Lead (T) 
to IN 2
Connect  
Sensor Lead 
(A) to IN 1
OUT connections are located on the opposite side 
of the board from the IN connections. Do not use 
positions 3 and 4 to connect wires.