Datasheet

33
Shielded connectors
1. Put all the parts over the cable as
shown on the picture.
2. Keep about 10mm of the shielding
(dim A)
3. The total strip length (dim B) of
the outer jacket has to be defined
practically. This length is defined by
the length of the adaptor, the cable
gland body, type of contacts, the
gender of the plug connector and the
dim. L as shown on picture 2.
4. The strip length of the individual wires
is defined in the different contact
sections.
How to assemble shielded connectors…
5. Put the contacts in the corresponding
cavities
6. Screw / tighten the adaptor and the
cable gland body. The max tightening
torque is indicated in the table below.
7. Make sure the dim L is kept after the
assembly of the adaptor and the cable
gland body. This dimension is needed
to allow repair of the harnessing. It will
also release the stress on the contacts
when the assembly of the cable clamp
is finished.
8. Carefully slide the shielding ferrule
until is positioned over the shielding
and as close as possible to the cable
jacket.
9. Make sure that the shielding ferrule is
correctly polarised. This polarisation is
a feature to avoid twisting of the cable
during the tightening of the cable
gland.
Cable gland body
Adaptor
Shielding ferrule
B
A
