Datasheet

UTS Series
|
Connector
19
Standardisation of European Cable - DIN VDE 0281/DIN VDE 0282/DIN VDE 0292
1.
Basic type
2.
Working
voltage
3.
Insulating
4.
Sheath-
cladding
material
5.
Special
features
6.
Conductor
types
7.
Number of
conductors
8.
Protective
conductor
9.
Conductor
cross-
sectional
H:
Harmonized
Type
03:
300/300V
V:
PVC
V:
PVC
H:
Ribbon cable,
separable
U:
Single wire
X:
Without
protective
conductor
Area specied
in mm
2
A:
National Type
05:
300/500V
R:
Rubber
R:
Rubber
H2: Ribbon
cable
non-separable
R:
Multi-wire
G:
With
protective
conductor
07:
450/750V
S:
Silicone
Rubber
N:
Cloroprene
Rubber
K:
Fine wire
(permanently
installed)
J:
Glass-lament
braiding
F:
Fine wire
(exible)
T:
Textile
braiding
H:
Super ne wire
Y:
Tinsel strand
1 32 4 5 6 7 8 9
Harmonized wire coding system
Example: Harmonized type, 300/500V, PVC insulating, PVC sheath- cladding, Fine wire, 3x1.5 cross-sectional: H05VVF3x1.5
Cable Information
Rangeoftemperature: Occasional exing: -5°C up to +70°C
Fixed installation: -40°C up to +80°C
Ratedvoltage: U0/U: 300/500V
Wiresection: Layouts with #16 contact: wire section 1.5 mm²
Layouts with #20 contact: wire section 0.5 mm²
Harmonizedreference: H05 VV - F XX
Connector