Application Manual and System Selection Guide
systems.  The  four  and  ve  ton  system  should  be 
considered and handled as two separate smaller 
units. This necessitates the installation of the plenum 
tee a minimum of 18" from the unit (see Figure 3.1). 
No supply runs should be installed between unit outlet 
and tee. 
All tees and elbows must be a minimum of 18" from 
the fan coil unit or any other tee or elbow. Keep all tees 
and elbows to a minimum.
SUPPLY TUBING
In the case of two-story or split-level applications, supply 
tubing may run from one story to another. It is small 
enough to  go in  stud spaces,  but this  is often  difcult 
in older homes because of hidden obstructions in stud 
spaces. It is more common to run the supply tubing from 
the attic down through second story closets to the rst 
story terminators. Supply tubing runs in the corners of 
the second story rooms can be boxed in and are hardly 
noticeable since overall diameter is only 3-1/4". 
At the plenum, all supply tubing connections must be a
minimum of 18" from any plenum tee, plenum elbow or
the fan coil unit. 
Individual supply tubing runs must be a minimum 
of 6 feet, even if the distance between the sound 
attenuating tubing and plenum is less than 6 feet.
ROOM TERMINATORS
Terminators  should  be  located  in  the  ceiling  or  oor 
for vertical discharge. However, ceiling locations are 
not recommended for heating where ceiling height is 
10 feet or more due to possible stratication and short 
circuiting of air ow.
Horizontal discharge is acceptable for cooling-only 
systems, but is sometimes more difcult to install. Two 
excellent spots for horizontal discharge are in the soft
area above kitchen cabinets and in the top portion of 
closets. Horizontal discharge is not recommended for 
heating systems, as it will not maintain a proper oor-
to-ceiling temperature difference.
Terminators  should  always  be  out  of  normal  trafc 
patterns to prevent discharge air from blowing directly 
on occupants. And they should not be located directly 
above shelves or large pieces of furniture. Outside 
wall or corner locations are recommended if the room 
has more than one outside wall. Locating terminators 
away from interior doors prevents short cycling of air 
to the return air box.
NOTE:
The Kwik-Way method is appropriate for calculating the 
cooling loads of most buildings or normal structures but it 
might not be appropriate when calculating loads for sun 
rooms and buildings that do not comply with data and 
factors in this application manual and Kwik-Way form. If 
in doubt, calculate the actual cooling load using the long 
form manual “J”.
Some factors may vary state to state and your design 
temps may be greater. SpacePak assumes no liability for 
incorrect interpretation of this manual.
260 NORTH ELM STREET • WESTFIELD, MA 01085 • TEL: (413) 564-5530 • FAX (413) 564-5818
7555 TRANMERE DRIVE • MISSISSAUGA, ONTARIO L5S 1L4 CANADA • TEL: (905) 670-5888 • FAX (905) 670-5782










