Application Manual and System Selection Guide
5
Total Exp wall:  On  this  line,  ll  in  the  total  square 
footage of exposed wall. Simply multiply linear feet of 
exposed wall by ceiling height in each room.
FACTORS: For this column, select and enter the 
applicable factors, as shown in Figure 1.4, which 
correspond to the construction of the structure and the 
application: cooling-only or heating (see Figure 1.3). 
These factors are also available in Table 1 on the back 
of the Kwik-Way sheet.
For cooling-only installation, select factors for Lines 1, 4, 
5, 6, 7, 8 and 9. For heating installations, select factors 
for Lines 2, 3, 4, 5, 6, 7, 8 and 9. 
Example (cooling-only): Based on example house 
construction, the following factors would be selected:
DESCRIPTION  FACTORS
Double-Hung Windows With Blinds
 North ........................................................20
  East & West .............................................50
 South .......................................................25
Storm Doors (at 90°F) .........................................9
Masonry Partition w/o Insulation (at 90°F) ........ 2.3
Frame Walls w/3-1/2" Insulation (at 90°F) ......... 2.0
Ceiling w/3-1/2" Insulation (at 90°F) .................. 2.5
Floors Over Basement, R-11 (at 90°F) ................5
Inltration (at 90°F) ............................................ 1.2 
FIGURE 1.4: HEAT GAIN (LOSS) FACTORS