ALM3-C1D2, ALM3-C1D2-DPDT
Installation, Operation & Maintenance Instructions
ALARM SYSTEM
DESCRIPTION
Emergency equipment alarm with electro-mechanical vibrating horn and flashing LED light activated by a
vapor proof flow switch. Unit is also equipped with a silencing pushbutton to shut horn off during usage.
Alarm unit meets indoor/outdoor hazardous location requirements for Class 1 Division 2, Groups B,C,D, T4,
NEMA 4 electrical classification. (ALM3-C1D2-DPDT) product is supplied with double-pole, double-throw flow
switch for remote location signaling.
SPECIFICATIONS
ACTIVATOR: ¾” Vapor Proof Flow Switch.
- ALM3-C1D2: (SPDT) Single-Pole Double Throw.
- ALM3-C1D2-DPDT: (DPDT) Double-Pole Double Throw
HORN: 100dB @ 10 Ft.
LIGHT: 65 fpm, LED Light
INLET: 1” NPT Female
OUTLET: 1-1/4” NPT Female
SHIPPING WEIGHT: 21 lb.
ELECTRICAL DATA
ELECTRICAL SUPPLY: 120 VAC, 60 Cycle, Single Phase.
ELECTRICAL RATING: 3.9 Amps @ 120 VAC.
COMPLIANCE: Unit rated for NEMA 4 Indoor/Outdoor Hazardous Locations
Class 1 Division 2, Groups B,C,D, T4, NEMA 4
*Power supply to be in compliance with (N.E.C.) National Electric Code.
*Installation of this unit shall be in compliance with all (NEC) National Electric Code, and any other applicable
state or local.
OPTIONS
ALM-MTG BRACKET
Retro-Kit for Fixed Post Mount
INSTALLATION
To avoid electric shock, make sure power supply is shut off before doing any electrical maintenance to this
unit. Power supply requirement is 120 VAC, 60 cycle, single phase. Ground-fault protection should be GFPD
with a nominal 30 milliampere trip level to prevent nuisance tripping. Minimum 15 AMP breaker is required.
Make sure power supply and installation is in compliance with all local codes and the National Electric Code
(N.E.C.).
120V Power Supply Wiring Diagram: (See Next Page)
1. Connect HOT (labeled below as Red) wire into Contact Block #1,
2. Connect Neutral (White) wire into Contact Block labeled #2.
3. Connect Ground (Green) wire into Ground Contact Block, left of Contact Block #1