Installation
SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
06/12/17 speakman.com 92-SE-236-PR-02
SE-236 ROUGH-IN
TESTING PROGRAM
The American National Standards
Institute (ANSI) states that all
safety emergency equipment shall
be activated on a weekly basis
to flush the line and verify proper
operation. Speakman Company
furnishes a testing record tag
(91-0635) with each unit. On this
tag the date of inspection and the
inspector’s initials should be noted.
MAINTENANCE
Should you need parts to repair this
unit, please reference the parts
listing below for correct part
numbers. Reference additional
technical sheet (supplied) for
information on the SE-911 stay-open
valve. Before any maintenance is
done be sure to shut the water
supply off.
WARNING: Use only genuine
Speakman parts when repairing
or replacing components. To
order parts call 1-800-537-2107.
REPLACEMENT/REPAIR PARTS
ITEM PART/GROUP # DESCRIPTION
1 SE-911-CR 1” Stay-Open Valve With Chain and Ring
2 SE-830 10” Flanged Shower Head With Face Plate
FLOW DATA
SHOWER:
NOTE: This unit should be connected to an uninterrupted
source of potable water, with a minimum flowing pressure
of 20 PSI and a maximum static pressure of 125 PSI.
FLOW PRESSURE PSI (BAR) 20 (1.38) 60 (4.14)
FLOW RATE GPM (LPM) 20 (75) 25 (94)
Note: All units meet existing
ANSI Z358.1 Standards and
OSHA Rules. Product
improvements may cause
specification and dimensional
changes without notice.