Owner manual

TM 40/40U, Rev (7) July 2013
Configuring your Detector 29
The Fault output is N.C. energized SPST relay. The contacts are closed
when the Detector is in its normal operational condition in options 1, 2
and 4, and available as N.O. energized in options 3 and 5.
The Auxiliary output is N.O. energized (SPST) relay. The Auxiliary Relay
may act in parallel with the ALARM relay to activate another external
device or it may provide a warning signal, depending on the function
configuration.
2.8 Configuring your Detector
You can reprogram the function setup using the RS-485 connection or using
the HART protocol as follows:
Mini Laptop Kit (P/N 777820): The mini laptop, pre-loaded with the
Spectrex host software, enables you to re-configure settings or perform
diagnostics on all 40/40 series flame detectors.
Refer to manual TM777070 for programming instructions when using the
Mini Laptop Kit.
USB RS485 Harness Kit (P/N 794079-5): The USB RS485 Harness Kit
with RS485/USB converter, used with the Spectrex host software,
enables you to connect to any available PC or laptop to re-configure
settings or perform diagnostics on all 40/40 series flame detectors.
Refer to manual TM777050 for programming instructions when using the
USB RS485 Harness Kit.
HART Protocol: Refer to Manual TM 777030 for programming
instructions.
These functions enable you to set:
Alarm Delay
Address Setup
Mode of Operation
Heated Optics Operation
The factory Default settings listed for each function are:
Alarm Delay 3 Sec.
Alarm Latch No
Auxiliary Relay No
Automatic BIT Yes
Alarm BIT No
Auxiliary BIT No
EOL No
Heated Optics Auto
Temperature 41°F (5°C)