Owner manual

Technical Specifications 43
A Specifications
In this appendix…
Technical Specifications
page 43
Electrical Specifications
page 44
Outputs
page 44
Approvals
page 46
Mechanical Specifications
page 46
Environmental Specifications
page 47
A.1 Technical Specifications
Spectral Response
UV 0.185-0.260 µm
Detection Range
(at highest Sensitivity
Setting for 1ft
2
(0.1m
2
) pan
fire)
Fuel
ft. / m
Fuel
ft. / m
n-Heptane
50 / 15
Kerosene
37 / 11
Gasoline
50 / 15
Ethanol 95%
37 / 11
Diesel Fuel
37 / 11
Methanol
37 / 11
JP5
37 / 11
IPA (Isopropyl
Alcohol)
37 / 11
Hydrogen*
33 / 10
Polypropylene
Pellets
18 / 5
Methane*
40 / 12
Silane*
22 / 7
Office Paper
20 / 6
LPG*
40 / 12
* 20" (0.5m) high, 8" (0.2m) width plume fire
Response Time
Typically 3 seconds
200 msec response to flash fire
Adjustable Time Delay
Up to 30 seconds
Sensitivity Ranges
1 ft
2
(0.1m
2
) n-heptane pan fire from 50 ft. (15m)
Fields of View
Horizontal 100, Vertical 95
Built-In-Test (BIT)
Automatic (and Manual)