User Manual

Chapter 9: Diagnostics and Troubleshooting
User’s Manual 03 00217-03 Rev. A
9-5
Section 9.7
Error Codes
The table below explains the extended error code.
Table 9-4 (Extended Fault Codes)
Error Type He x Equivale nt Module Error Code Exte nded Error
In f o rm a t ion Co de
Error De s cription
No error X000 000 0 0000 0000 No error
X216 001 0 0001 0110 Watc hdog reset er ror
X220 001 0 0010 0000 Cr itical c ode f ailure
X221 001 0 0010 0001 Failed c alibration/c ritic al EEPRO M f a ilu r e
X401 010 0 0000 0001 Channel 0 Invalid Output Range
X402 010 0 0000 0010 Channel 1 Invalid Output Range
X403 010 0 0000 0011 Channel 2 Invalid Output Range
X404 010 0 0000 0100 Channel 3 Invalid Output Range
X405 010 0 0000 0101 Channel 0 Invalid Data For mat
X406 010 0 0000 0110 Channel 1 Invalid Data For mat
X407 010 0 0000 0111 Channel 2 Invalid Data For mat
X408 010 0 0000 1000 Channel 3 Invalid Data For mat
X409 010 0 0000 1001 Channel 0 Inv alid Fault V alue.
X40A 010 0 0000 1010 Channel 1 Invalid Fault V alue.
X40B 010 0 0000 1011 Channel 2 Invalid Fault V alue.
X40C 010 0 0000 1100 Channel 3 Inv alid Fault V alu e.
X40D 010 0 0000 1101 Channel 0 Inv alid Idle Value.
X40E 010 0 0000 1110 Channel 1 Invalid Idle Value.
X40F 010 0 0000 1111 Channel 2 Invalid Idle Value.
X410 010 0 0001 0000 Channel 3 Inv alid Idle Valu e.
X411 010 0 0001 0001 Channel 0 Inv alid Clamps.
X412 010 0 0001 0010 Channel 1 Inv alid Clamps.
X413 010 0 0001 0011 Channel 2 Inv alid Clamps.
X414 010 0 0001 0100 Channel 3 Inv alid Clamps.
X415 010 0 0001 0101 Channel 0 Inv alid Ramp Ra te.
X416 010 0 0001 0110 Channel 1 Inv alid Ramp Ra te.
X417 010 0 0001 0111 Channel 2 Inv alid Ramp Ra te.
X418 010 0 0001 1000 Channel 3 Inv alid Ramp Ra te.
X419 010 0 0001 1001 Channel 0 Config w ord 0 Illegal bits s et
X41A 010 0 0001 1010 Channel 1 Config w ord 0 Illegal bits s et
X41B 010 0 0001 1011 Channel 2 Config w ord 0 Illegal bits s et
X41C 010 0 0001 1100 Channel 3 Conf ig w ord 0 Illegal bits s et
X41D 010 0 0001 1101 Channel 0 Conf ig w ord 1 Illegal bits s et
X41E 010 0 0001 1110 Channel 1 Config w ord 1 Illegal bits s et
X41F 010 0 0001 1111 Channel 2 Config w ord 1 Illegal bits s et
X420 010 0 0010 0000 Channel 3 Config w ord 1 Illegal bits s et
X421 010 0 0010 0001 Channel 0 Illegal HART Pas sthrou gh rate.
X422 010 0 0010 0010 Channel 1 Illegal HART Pas sthrou gh rate.
X423 010 0 0010 0011 Channel 2 Illegal HART Pas sthrou gh rate.
X424 010 0 0010 0100 Channel 3 Illegal HART Pas sthrou gh rate.
Hardw are-
Sp ec if ic Err or
Module-Spec if ic
Conf igur ation
Error
Section 9.8
Module
Inhibit Function
Some controllers support the module inhibit function. See your controller manual for
details.
Whenever the 1769sc-OF4IH module is inhibited, the module continues to provide
information about changes at its outputs to the 1769 CompactBus master (for example, a
CompactLogix controller).