User Manual

Chapter 6: Module Data, St at us, and C on fig urat i o n
User’s Manual 03 00217-03 Rev. A
6-5
Table 6-2b (Module Configuration)
1514131211109876543210
26
Ch3 Fault V alue
27
Ch3 Progr am Idle V alue
28
Ch3 Low Clamp Value
29
Ch3 High Clamp V alue
30
Ch3 Ra mp Ra te V a lue
31
Not Us ed ( S e t to Z ero )
32
Pad (16 B it Allignment)
33
EH3 EH2 EH1 EH0
HART Conf ig uration
Word
34
Defines Slot V ariables
35
Defines Slot V ariables
36
Defines Slot V ariables
37
Defines Slot V ariables
38
Defines Slot V ariables
39
Defines Slot V ariables
40
Defines Slot V ariables
41
Defines Slot V ariables
Word
Bit
Function
Channel 0 HA R T S lot V ariables 2 & 3
Channel 0 HA R T S lot V ariables 0 & 1
Channel 3 Ram p Rate V alue
Reserved
S et to Zero
Handle Tim eoutPA
Channel 1 HA R T S lot V ariables 0 & 1
Channel 3 HA R T S lot V ariables 2 & 3
Channel 1 HA R T S lot V ariables 2 & 3
Channel 2 HA R T S lot V ariables 0 & 1
Channel 2 HA R T S lot V ariables 2 & 3
Channel 3 HA R T S lot V ariables 0 & 1
Reserved
Channel 3 F ault V alue
Channel 3 P rogram Idle V alue
Channel 3 Low Clam p V alue
Channel 3 High Clam p V alue
6.3.12 Channel X
1
General Settings (Words 0, 8, 16, 24)
Allows the user to enable or disable channels, set the analog output level for each channel
in the event of a PLC fault, or enable HART slot variables for a given channel.
Table 6-3 (Channel General Settings)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Disable 0
E nable 1
Disable 0
E nable 1
Hold Last Stat e 0
Us er D efined 1
Hold Last Stat e 0
Us er D efined 1
Disable 0
E nable 1
Disable 0
E nable 1
Disable 0
E nable 1
Disable 0
E nable 1
Disable 0
E nable 1
Disable 0
E nable 1
Disable 0
E nable 1
Disable 0
E nable 1
Reserved
S et to Zero 0 0 0
Disable 0
E nable 1
PM (Program M ode)
FM (Fau lt M o de )
ER (Enable Ram ping)
LA (L atch Alarm s )
To S e le c t
M ak e these bit s ettings
PFE (Pr ogram /Idle to Fault
En a b le )
HI (Hold for Initialization)
En a b le Slot V a r iable 2
En a b le Slot V a r iable 3
Channel Enable
SIO (Syste m Inte rr u p t Hig h
Clam p, Ove r Range Alarm)
SIU (System Inter rupt Low
Clam p, Unde r Range Alarm )
En a b le Slot V a r iable 0
En a b le Slot V a r iable 1
PFE (Program/Idle to Fault Enable)
If a system currently in program/idle mode faults, this setting determines whether the
program/idle or fault value is applied to the output. If the selection is enabled [the bit is
set (1)], the module applies the fault value. If the selection is disabled [the bit is reset (0)],
1
Where X is the channel number
2
Entering a value of zero allows the module to automatically select the fastest allowed RTS rate.