Sec t ion 3.2
Power
Requirements
The module receives p ower through the b us interface from the +5V dc/ +24V dc system
power supply. The maximum current drawn by the module is shown in the table below.
Module Current Draw at 5V dc at 24V dc
175 mA 60 mA
Section 3.3 General
Considerations
Compact I/O is suitable for use in an industrial environment when installed in accordance
with these instructions. Specifically, this equipment is intended for use in clean, dry
environments (Pol lutio n degree 2
1
and to circuits not exceeding Over Voltage Category
II
2
(IEC 60664-1)
3
3.3.1 Hazardous Location Considerations
This equipment is suit able for use i n Cl ass I , Div ision 2, Groups A, B , C, D or non-
hazardous locations only. The following WARNING statement applies to use in
hazardous locations.
!
Attention
· EXPLOSION HAZARD
· Substitution of co mponents may impair suitability for Class I,
Division2.
· Do not replace components or disconnect equipment unless power has
been switched off or the area is known t o be non-hazardous.
· Do not connect or disconnect components unless po wer has been
switched off or the area is know n to be non-ha zardous.
· This product must be installed in an enclosure.
· All wiring must comply with N.E.C. article 501-4(b).
3.3.2 Prevent Electrostatic Discharge
!
Attention
Electrostatic discharge can damage integrated circuits or
semiconducto rs if you to uch analog I/O module bus connecto r pins or
the terminal block on the input module. Follow these guidelines when
you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist - strap gr ounding device.
Do not touch the bus connector or connecto r pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When it is not in use, keep the module in its st atic-shield bag.
1
Pollution Degree 2 is an environment where, normally, onl y non-co nductive pol luti on occurs exc ept that
occasionally a temporary conductivity caused by condensation shall be expected.
2
Over Voltage Categor y II is t he load level section of the ele c tr ical distribution s ystem. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’s insulatio n.
3
Pollution Degree 2 and Over Voltage Cate gory II are International Electrotechnical Commission (IEC)
designations.