Instructions / Assembly

Duct Sealant Instructions
Recommended Uses
Sealing joints, seams, and duct wall penetrations on metal air duct.
Sealing connections on flexible duct or fiberglass duct board.
Will handle up to 15 inches of water column pressure.
Directions For Use
Surfaces should be clean, dry and free of dirt, oil and any foreign matter.
For sheet metal duct sealant should be applied according to SMACNA standards.
Apply to all connections or penetrations in the duct wall including sheet metal screw heads
and tie rods. Make sure to brush sealant into seams.
For round and oval spiral duct apply to male section of fitting and apply a 2” band around
outside of joint, covering all screws.
For rigid fiberglass duct assemble per manufacturers recommendations and apply a 3” by
20 mil band of sealant to the joint, embed a fiberglass scrim (5 mil, 20 x 10 plain weave,
1.75 oz. per sq. yd.) in the sealant, then apply another 20 mil coat of sealant over the scrim.
For flexible duct apply a 2” by 20-40 mil band of sealant between the end of the duct and
collar on all connections.
Pressure Testing
Allow at least 48 hours before pressure testing.
In some environments in make take longer for the mastic to cure, adjust accordingly.
Clean Up
Use warm water and soap.
NOTE: DO NOT APPLY WHEN RAIN OR FREEZING TEMPERATURES WILL OCCUR
WITHIN 36 HOURS. DO NOT THIN.