Instructions / Assembly

Installation
Instructions
Type “B” Gas Vent
Model E/R 3" – 8"
ECCO TYPE “B” GAS VENT AND ACCESSORIES
ARE FOR USE ONLY WITH LISTED CATEGORY 1
GASFIRED APPLIANCES OR APPLIANCES
LISTED FOR USE WITH TYPE “B” GAS VENT.
TEMPERATURE AT THE OUTLET OF THE
APPLIANCE SHALL NOT EXCEED 245°C 470°F.
ECCO Type B Gas Vent and accessories are for venting
listed Natural Gas or Liquid Propane Category 1
appliances only. ECCO Type B Gas Vent Systems may be
used on other gas-burning appliances, providing the
appliance is certified for use with Type B Gas Vent, the
installation conforms to the appliance manufacturers
certified installation instructions, and the installation is
acceptable to the requirements of the local authority
having jurisdiction. Type B Gas Vent shall not be used to
vent flue products from incinerators, combination gas/
oil appliances, oil-fired, or wood-burning appliances. If
there is a question about the use of Type B Gas Vents,
contact the appliance manufacturer, the authority
having jurisdiction, or ECCO Manufacturing™ for further
information.
www.eccomfg.com
MH-12111
Vent sizing and installation are to be made in accordance with the
applicable codes shown below.
In USA
Connection to appliance and vent sizing to be
in accordance with the NATURAL FUEL GAS
CODE, ANSI Z223.1 (NFPA 54), NFPA 211, GAMA
VENTING TABLES, and/or the requirements of the
local authorities having jurisdiction.
In Canada
Connection to appliance and vent sizing to
be in accordance with the NATURAL GAS
INSTALLATION CODE, CAN/CGA-B149.1 or
the PROPANE INSTALLATION CODE,
CAN/CGA-B149.2, and/or the requirements
of the local authorities having jurisdiction.
Tested to UL441 “Gas Vent” basic standard.

Summary of content (8 pages)