Brochure

Page 4 — BULLETIN 10-10
t
AIR CONDITIONING, HEAT PUMP and COMMERCIAL REFRIGERATION APPLICATIONS
THERMOSTATIC EXPANSION VALVE
CAPACITIES for REFRIGERANTS - TONS OF REFRIGERATION
22, 422D, 407C
VALVE TYPES
NOMINAL
CAPACITY
REFRIGERANT
22 422D
Q
407C
RECOMMENDED THERMOSTATIC CHARGE
VC, VCP100, VGA VZ, VZP40 VC, VCP100, VGA VZ, VZP40 NC, NCP100, NGA
EVAPORATOR TEMPERATURE °F
40° 20° 0° -10° -20° -40° 40° 20° -10° -20° -40° 40° 20° 0°
F-EF-G-EG 1/5
0.20 0.22 0.19 0.17 0.15 0.11 0.14 0.15 0.13 0.11 0.10 0.07 0.18 0.20 0.17
F-EF-G-EG 1/3
0.35 0.38 0.33 0.27 0.24 0.18 0.25 0.26 0.22 0.18 0.16 0.11 0.32 0.35 0.30
F-EF-G-EG 1/2
0.45 0.49 0.43 0.35 0.31 0.23 0.36 0.34 0.29 0.23 0.20 0.15 0.41 0.44 0.38
G-EG 3/4
0.75 0.82 0.71 0.68 0.61 0.45 0.54 0.57 0.48 0.45 0.40 0.28 0.69 0.74 0.64
F-EF-G-EG 1
1.00 1.09 0.95 0.86 0.77 0.57 0.71 0.76 0.64 0.57 0.50 0.36 0.92 0.99 0.85
F-EF-G-EG 1-1/2
1.60 1.74 1.52 1.22 1.09 0.81 1.14 1.21 1.02 0.81 0.71 0.51 1.47 1.58 1.36
F&EF(Ext)-G&EG(Ext)-S 2
2.00 2.18 1.91 1.96 1.75 1.31 1.43 1.51 1.28 1.30 1.14 0.82 1.84 1.97 1.70
F&EF (Int)-G&EG(Int) 2-1/2
2.50 2.72 2.38 2.20 1.97 1.47 1.78 1.89 1.60 1.45 1.28 0.92 2.30 2.46 2.12
F&EF (Ext)-G&EG (Ext)-S 3
3.20 3.49 3.05 2.33 2.09 1.56 2.28 2.42 2.05 1.54 1.36 0.97 2.94 3.16 2.71
S 4
4.50 4.90 4.29 3.43 3.07 2.29 3.21 3.40 2.88 2.27 1.99 1.43 4.14 4.44 3.81
S 5
5.20 5.67 4.96 4.04 3.62 2.70 3.71 3.93 3.33 2.67 2.35 1.69 4.78 5.13 4.41
S(Ext) 8
8.00 8.72 7.04 5.82 4.87 3.59 5.70 6.04 4.73 3.85 3.16 2.24 7.35 7.89 6.25
S(Ext) 10
10.0 10.9 8.80 7.27 6.08 4.48 7.13 7.56 5.91 4.81 3.95 2.80 9.19 9.86 7.82
H 5-1/2
5.60 5.98 5.34 4.59 3.39 2.73 3.99 4.15 3.59 3.03 2.20 1.71 5.15 5.41 4.75
H 7
7.00 7.48 6.67 5.14 3.79 3.06 4.99 5.18 4.48 3.40 2.46 1.91 6.43 6.76 5.93
H 11
10.5 11.2 10.0 7.00 5.17 4.17 7.49 7.77 6.73 4.63 3.36 2.61 9.65 10.1 8.90
H 16
15.2 16.2 14.5 10.0 7.38 5.96 10.8 11.3 9.74 6.61 4.79 3.72 14.0 14.7 12.9
H 20
22.2 23.7 21.2 16.3 12.0 9.71 15.8 16.4 14.2 10.8 7.81 6.07 20.4 21.5 18.8
M 21
21.5 23.4 22.5 18.4 16.3 13.2 15.3 16.2 15.1 12.2 10.6 8.27 19.8 21.2 20.0
M 26
26.5 28.9 27.8 26.0 23.0 18.7 18.9 20.0 18.7 17.2 15.0 11.7 24.4 26.1 24.7
M 34
34.0 37.1 35.6 30.6 27.1 22.0 24.2 25.7 24.0 20.2 17.6 13.8 31.3 33.5 31.7
M 42
42.0 45.8 44.0 39.6 32.7 25.2 29.9 31.7 29.6 26.2 21.3 15.8 38.6 41.4 39.2
BALANCED PORT THERMOSTATIC EXPANSION VALVES
BF-EBF-SBF
AAA
0.35 0.38 0.33 0.27 0.24 0.18 0.25 0.26 0.22 0.18 0.16 0.11 0.32 0.34 0.30
BF-EBF-SBF AA
0.75 0.82 0.71 0.68 0.61 0.45 0.54 0.57 0.48 0.45 0.40 0.28 0.69 0.74 0.64
BF-EBF-SBF A
1.60 1.74 1.52 1.22 1.09 0.81 1.14 1.21 1.02 0.81 0.71 0.51 1.47 1.58 1.36
BF-EBF-SBF B
2.80 3.05 2.67 2.25 2.01 1.50 2.00 2.12 1.79 1.49 1.31 0.94 2.57 2.76 2.37
BF-EBF-SBF C
5.20 5.67 4.96 4.04 3.62 2.70 3.71 3.93 3.33 2.67 2.35 1.69 4.78 5.13 4.41
EBS 8
8.51 8.81 7.30 6.15 5.15 3.79 6.06 6.10 4.90 4.06 3.34 2.37 7.81 7.96 6.48
EBS 11
11.5 11.9 9.86 8.32 6.96 5.13 8.20 8.25 6.63 5.50 4.52 3.21 10.6 10.8 8.77
EBS 15
15.5 16.3 12.2 11.1 8.88 6.85 11.0 11.3 8.19 7.33 5.77 4.28 14.2 14.7 10.8
EBS 20
22.3 22.8 16.9 15.4 12.4 8.66 15.9 15.8 11.4 10.2 8.02 5.42 20.5 20.6 15.0
O 15
15.0 15.5 13.0 9.20 8.15 6.14 10.7 10.8 8.75 6.08 5.29 3.84 13.8 14.1 11.6
O 20
22.2 23.0 19.3 16.3 12.0 9.71 15.8 15.9 13.0 10.8 7.81 6.07 20.4 20.8 17.1
O 30
30.5 31.6 26.5 19.4 17.1 14.4 21.7 21.9 17.8 12.8 11.1 8.97 28.0 28.6 23.6
O 40
40.3 43.5 32.0 29.5 26.1 21.8 28.7 30.1 21.5 19.5 17.0 13.6 37.0 39.3 28.5
O 55
55.0 59.3 43.7 39.4 29.9 24.3 39.2 41.1 29.4 26.0 19.4 15.2 50.6 53.7 38.9
O 70
73.0 78.8 58.0 51.5 34.0 26.4 52.0 54.6 39.0 34.0 22.1 16.5 67.1 71.3 51.6
V 52
52.0 56.1 54.0 52.2 37.0 29.5 37.1 38.9 36.3 34.5 24.0 18.4 47.8 50.8 48.0
V 70
73.0 78.8 75.8 71.6 50.7 40.4 52.0 54.6 50.9 47.3 32.9 25.3 67.1 71.3 67.4
V 100
100 108 104 92.2 65.3 52.1 71.3 74.8 69.8 60.9 42.4 32.6 91.9 97.6 92.3
W 135
143 154 148 132 93.5 74.5 102 107 99.7 87.3 60.7 46.6 131 140 132
W 180
180 128 165
VALVE TYPES CARTRIDGE NO. REPLACEABLE CARTRIDGE THERMOSTATIC EXPANSION VALVES
Q-EQ-SQ 0 1/3
0.35 0.38 0.33 0.27 0.24 0.18 0.25 0.26 0.22 0.18 0.16 0.11 0.32 0.35 0.30
Q-EQ-SQ 1 3/4
0.75 0.82 0.72 0.68 0.61 0.45 0.54 0.57 0.48 0.45 0.40 0.28 0.69 0.74 0.64
Q-EQ-SQ 2 1
1.00 1.09 0.95 0.86 0.77 0.57 0.71 0.76 0.64 0.57 0.50 0.36 0.92 0.99 0.85
Q-EQ-SQ 3 1-1/2
1.50
1.64 1.43 1.10 0.99 0.73 1.07 1.13 0.96 0.73 0.64 0.46 1.38 1.48 1.27
Q-EQ-SQ 4 2-1/2
2.50 2.73 2.38 2.20 1.97 1.47 1.78 1.89 1.60 1.45 1.28 0.92 2.30 2.46 2.12
Q-EQ-SQ 5 3-1/2
3.50 3.82 3.34 3.00 2.69 2.00 2.50 2.64 2.24 1.98 1.74 1.25 3.22 3.45 2.97
Q-EQ-SQ 6 5
4.80 5.24 4.58 3.65 3.27 2.44 3.42 3.63 3.07 2.41 2.12 1.52 4.41 4.73 4.07
BQ-EBQ-SBQ
Balanced port replaceable cartridges, AAA, AA, A, B and C, have the same capacities as the matching nominal capacity of the
standard balanced port valves above.
REFRIGERANT
LIQUID TEMPERATURE ENTERING TEV °F
0° 10° 2 30° 40° 50° 60° 70° 80° 90° 100° 110° 120° 130° 140°
CORRECTION FACTOR, CF LIQUID TEMPERATURE
22
1.56 1.51 1.45 1.40 1.34 1.29 1.23 1.17 1.12 1.06 1.00 0.94 0.88 0.82 0.76
422D
1.99 1.90 1.80 1.70 1.60 1.50 1.41 1.31 1.20 1.10 1.00 0.90 0.79 0.68 0.57
407C
1.69 1.62 1.55 1.49 1.42 1.35 1.28 1.21 1.14 1.07 1.00 0.93 0.85 0.77 0.69
EVAPORATOR
TEMPERATURE
°F
PRESSURE DROP ACROSS TEV (psi)
30 50 75 100 125 150 175 200 225 250 275 300
CORRECTION FACTOR, CF PRESSURE DROP
40°
0.55 0.71 0.87 1.00 1.12 1.22 1.32 1.41 1.50 1.58 1.66 1.73
20° & 0°
0.49 0.63 0.77 0.89 1.00 1.10 1.18 1.26 1.34 1.41 1.48 1.55
-10° & -20°
0.45 0.58 0.71 0.82 0.91 1.00 1.08 1.15 1.22 1.29 1.35 1.41
-4
0.41 0.53 0.65 0.76 0.85 0.93 1.00 1.07 1.13 1.20 1.25 1.31
These factors include corrections for liquid refrigerant
density and net refrigerating effect and are based on an
evaporator temperature of 0°F. However, they may be
used for any evaporator temperature from -40°F to 40°F
since the variation in the actual factors across this range
is insignificant.
TEV Capacity = TEV Rating x CF Liquid Temperature x CF Pressure
Drop Example: Actual capacity of a nominal 2 ton R-22 Type S valve
at 20°F evaporator, 100 psi pressure drop across the TEV, and 90°F
liquid temperature entering the TEV = 2.18 (from rating chart) x 1.06
(CF liquid temperature) x 0.89 (CF pressure drop) = 2.06 tons.
Q R-422D can be used in a system with R-22 valves, but the TEV capacity will be reduced. Please verify valve capacity will handle system load.