March 2011 / BULLETIN 30-10 Solenoid Valves
Page 3 / Bulletin 30-10 Discharge Gas and Suction Capacities n Molded coil for most sizes. n Class “F” temperature rating — Coil types MKC-1, MKC-2, and OMKC-2. n Extremely rugged, simple design — few parts. n “E” Series may be brazed without disassembly. n Tight closing through use of synthetic seating material. n n 22, 134a, 401A, 402A Can be used with most commercially available CFC, HCFC and HFC refrigerants because of high MOPD ratings.
Page 2 / Bulletin 30-10 Contents Sporlan Solenoid Valves SELECTION.................................................................................................... 3 CAPACITIES Liquid Line................................................................................................. 4 Suction Line.............................................................................................. 6 Air & Water.............................................................................................
Bulletin 30-10 / Page 3 Features Sporlan Solenoid Valves Experience Unsurpassed Reliability For more than sixty-five years Sporlan has provided sound engineering principles and craftsmanship to produce top quality solenoid valves and other flow control devices for the air conditioning and refrigeration industry. A combination of top quality materials used in both the internal and external construction ensures unsurpassed product reliability. This is verified by periodic accelerated life tests.
With Manual Lift Stem "E" Series Extended Connections With Without Manual Manual Lift Stem Lift Stem TYPE NUMBER OB25S2 --- B9P2 B9F2 --B9S2 B10F2 --B10S2 B14P2 B14S2 B19S2 B19P2 B19S2 B25P2 B25S2 --- --- MB25S2 MB9P2 MB9F2 --MB9S2 MB10F2 --MB10S2 MB14P2 MB14S2 MB19S2 MB19P2 MB19S2 MB25P2 MB6S1 ------------MB6P1 MB6F1 ----E3S120 E3S130 E5S120 E5S130 ----E6S130 E6S140 ----E9S230 E9S240 --E10S240 E10S250 --E14S250 E19S250 --E19S270 --E25S270 E25S290 E35S190 E35S1110 E42S2130 E42S2170 -----------
--------------------OB9P2 OB9F2 --OB9S2 OB10F2 --OB10S2 OB14P2 OB14S2 OB19S2 OB19P2 OB19S2 OB25P2 OB25S2 --- ----- B9P2 B9F2 --B9S2 B10F2 --B10S2 B14P2 B14S2 B19S2 B19P2 B19S2 B25P2 B25S2 --- ----- ----- --- MB25S2 MB9P2 MB9F2 --MB9S2 MB10F2 --MB10S2 MB14P2 MB14S2 MB19S2 MB19P2 MB19S2 MB25P2 MB6S1 ----E3S120 E3S130 E5S120 E5S130 ----E6S130 E6S140 ----E9S230 E9S240 --E10S240 E10S250 --E14S250 E19S250 --E19S270 --E25S270 E25S290 E35S190 E35S1110 E42S2130 E42S2170 ------------------------OE9S230
Page 6 / Bulletin 30-10 Discharge Gas and Suction Capacities VALVE SERIES DISCHARGE GAS CAPACITIES — TONS Pressure Drop Across Valve — psi 2 A3 & E3 E5 B6 & E6 B9 & E9 B10 & E10 B14 & E14 B19 & E19 B25 & E25 E35 E42 0.24 0.45 0.84 1.35 1.83 2.62 3.93 6.74 9.90 21.0 A3 & E3 E5 B6 & E6 B9 & E9 B10 & E10 B14 & E14 B19 & E19 B25 & E25 E35 E42 0.20 0.37 0.70 1.12 1.52 2.17 3.26 5.60 8.1 17.4 A3 & E3 E5 B6 & E6 B9 & E9 B10 & E10 B14 & E14 B19 & E19 B25 & E25 E35 E42 0.20 0.38 0.72 1.15 1.56 2.23 3.35 5.
Bulletin 30-10 / Page 7 Discharge Gas and Suction Capacities 404A, 407C, 502, 507 VALVE SERIES DISCHARGE GAS CAPACITIES — TONS Pressure Drop Across Valve — psi 2 A3 & E3 E5 B6 & E6 B9 & E9 B10 & E10 B14 & E14 B19 & E19 B25 & E25 E35 E42 0.22 0.40 0.75 1.21 1.64 2.34 3.53 6.04 9.03 18.8 A3 & E3 E5 B6 & E6 B9 & E9 B10 & E10 B14 & E14 B19 & E19 B25 & E25 E35 E42 0.24 0.44 0.83 1.34 1.81 2.59 3.88 6.66 9.79 20.7 A3 & E3 E5 B6 & E6 B9 & E9 B10 & E10 B14 & E14 B19 & E19 B25 & E25 E35 E42 0.19 0.36 0.
Page 8 / Bulletin 30-10 Types A3, E3 and E5 Series Application Ordering Instructions Types A3 and E3 series are hermetic, direct-acting type solenoid valves primarily for refrigeration and air conditioning applications. The flow rate of the E3 and A3 are identical, therefore, the E3 may be freely substituted for the A3. When ordering complete valves, specify Valve Type, Connections, Voltage and Cycles. The E5 series are compact solenoid valves with pilot operated disc construction and are rated at 2.
Bulletin 30-10 / Page 9 Types B6 and E6 Series 22, 134a, 401A, 402A, 404A, 407C, 502, 507 When ordering Body Assembly, specify Valve Type and Connections. When ordering Coil Assembly ONLY, specify Coil Type, Voltage and Cycles. Example: MKC-1 120/50-60. Dimensions – Inches The MKC-l coil is Class “F” temperature rated and is provided as standard, therefore a high temperature coil is not required for discharge service. B6 1.56 Coil Removal B6P1 1.94 B6S1 *B 3/8 ODF 1/2 ODF 2.50 – C 0.44 0.
Page 10 / Bulletin 30-10 Types B9 and E9 Series 22, 134a, 401A, 402A, 404A, 407C, 502, 507 Type MB9S2 Normally Closed The MKC-2 and OMKC-2 coils are Class “F” temperature rated and are provided as standard, therefore a high temperature coil is not required for discharge service. When ordering complete valves, specify Valve Type, Connections, Voltage and Cycles. Type E9S240 Normally Closed Dimensions – Inches B9 TYPE A B9P2 2.06 B9S2 2.88 B9F2 2.88 *B 2.75 3.36 – 0.50 – 0.81 2.65 3.
Bulletin 30-10 / Page 11 Types B10 and E10 Series 22, 134a, 401A, 402A, 404A, 407C, 502, 507 Application When ordering Body Assembly, specify Valve Type and Connections. Types B10 and E10 Series are compact solenoid valves with pilot operated disc construction for refrigeration and air conditioning. These valves may be mounted horizontally, on their side or in a vertical line. They are suitable for suction line service because very low pressure differential, 1 psi, is required for full operation.
Page 12 / Bulletin 30-10 Types B14 and E14 Series Application Ordering Instructions Types B14 and E14 Series are compact solenoid valves with pilot operated disc construction for refrigeration and air conditioning. These valves may be mounted horizontally, on their side or in a vertical line. These valves are also suitable for suction line service because very low pressure differential, 1 psi, is required for full operation.
Bulletin 30-10 / Page 13 Types B19 and E19 Series 22, 134a, 401A, 402A, 404A, 407C, 502, 507 Application When ordering Body Assembly, specify Valve Type and Connections. Types B19 and E19 Series are pilot operated solenoid valves for refrigeration and air conditioning applications. They are suitable for suction service because very low pressure differential, 1 psi, is required for full operation. These valves may be mounted horizontally, on their side or in a vertical line.
Page 14 / Bulletin 30-10 Types B25 and E25 Series 22, 134a, 401A, 402A, 404A, 407C, 502, 507 Type E25S290 Normally Closed The Type E25 series solenoid valves feature extended solder type connections as standard. One important benefit to the user is that all valves in the “E25” series can be installed without disassembly using either low or no silver content brazing alloy.
Bulletin 30-10 / Page 15 Types E35 Series 22, 134a, 401A, 402A, 404A, 407C, 502, 507 The MKC-1 and OMKC-1 coils are Class “F” temperature rated and are provided as standard, therefore a high temperature coil is not required for discharge service. W 1-5/8” ODM Type L tubing may be slipped over 1-3/8” fitting, without the use of a coupling. When ordering Coil Assembly ONLY, specify Coil Type, Voltage and Cycles. Example: MKC-1 120/50-60; OMKC-1 120/50-60.
Page 16 / Bulletin 30-10 Type E42 Series Approved When ordering complete valves, specify Valve Type, Connections, Voltage and Cycles. The Type E42 series may be brazed into line without disassembly as valves contain extended solder type connections. Use caution to place wet rag or chills on extensions at body to prevent excessive overheating. When ordering Coil Assembly ONLY, specify Coil Type, Voltage and Cycles. Example: MKC-2 120/50-60; OMKC-2 120/50-60.
Bulletin 30-10 / Page 17 Built-In Check Valve Series 22, 134a, 401A, 402A, 404A, 407C, 502, 507 For Supermarkets Application A solenoid valve with a built-in check valve is designed to replace a liquid line solenoid valve in parallel with a check valve for reverse flow. This valve may be applied in the liquid line of a supermarket case for positive shutoff during pumpdown control, while allowing full flow in the reverse direction during reverse gas defrost.
Page 18 / Bulletin 30-10 Built-In Check Valve Series 22, 134a, 401A, 402A, 404A, 407C, 502, 507 Dimensions – Inches D A B C C(M)E9S230 C(M)E9S240 C(M)E10S250 CB14S2 CE14S250 C(M)E19S270 4.63 5.00 6.50 3.00 6.88 7.13 0.81 0.75 0.88 0.56 0.48 0.81 2.65 2.70 3.13 3.28 3.25 3.31 ODF TYPE ODM Ordering Instructions D' FITTING DEPTH When ordering complete valves, specify Valve Type, Connections, Voltage and Cycles. When ordering Body Assembly, specify Valve Type and Connections.
Bulletin 30-10 / Page 19 Industrial Solenoid Valves for Air, Water, Steam and Light Oil Application These valves are suitable for most types of industrial applications. Ideal for water, glycol, most refrigerant oils and heat transfer fluids, air lines to chucking devices, steam lines, etc. Use the disc type valves for high temperature and steam applications up to 25 psia. Use the teflon diaphragm type valve for high temperature and steam applications over 5 psig (225°F) but do not exceed 10 psig (240°F).
Page 20 / Bulletin 30-10 Industrial Solenoid Valves for Air, Water, Steam and Light Oil Ordering Instructions Dimensions – Inches When ordering complete valves, specify Valve Type, Connections, Voltage and Cycles. TYPE When ordering Body Assembly, specify Valve Type and Connections. W3P1 1/4 1.88 W6P1 3/8 1.94 When ordering Coil Assembly ONLY, specify Coil Type, Voltage and Cycles. Example: MKC-1 208-240/50-60; MKC-2 120/50-60.
Bulletin 30-10 / Page 21 General Sporlan Solenoid Valves Purpose The primary purpose of an electrically operated solenoid valve is to control automatically the flow of fluids, liquid, or gas. Sporlan Solenoid Valves may be applied on a wide variety of applications. Basic Types There are two basic types of solenoid valves. The most common is the normally-closed type, in which the valve opens when the coil is energized, and closes when the coil is de-energized.
Page 22 / Bulletin 30-10 General Sporlan Solenoid Valves open, the disc is held off the seat by the pressure difference across the port. When the coil is de-energized, the stem and plunger assembly drops, due to gravity or the kick off spring, and closes the pilot port. As shown in D the pressure above the disc is no longer vented to the downstream side of the valve. Fluid flow and pressure drop causes the pressure above the disc to be higher than below the disc, and the disc drops, closing the main port.
Bulletin 30-10 / Page 23 Construction Details Sporlan Solenoid Valves VALVE SERIES PORT TYPE OF SIZE OPERATION Inches COIL KIT *BODY MATERIAL A3P1 A3F1 A3S1 .101 MAIN PORT PILOT PORT Synthetic to Metal Direct Acting E3 TYPE OF SEATING MKC-1 Brass STEM AND PLUNGER ASSEMBLY PISTON DISC OR DIAPHRAGM --- Metal to Metal --- .
Page 24 / Bulletin 30-10 Construction Details Sporlan Solenoid Valves Sporlan Solenoid Valves are constructed to ensure long, trouble-free life. They employ proven design features for reliable performance on all applications. By using modern production equipment, Sporlan consistently provides top quality solenoid valves for air conditioning, refrigeration and other uses.
Bulletin 30-10 / Page 25 Electrical Specifications Sporlan Solenoid Valves Listed by Underwriters’ Laboratories Inc., Canadian Standard Association and CE Approved. Conversion from AC to DC Coils — The con- version of a solenoid valve from AC to DC service varies with the valves construction and its principle of operation.
Page 26 / Bulletin 30-10 Identification * S Overall Length Spade Coil S 2 1 2 Coil Size M Connections P - Pipe F - SAE Flare S - ODF Solder Disc Type D - Direct Connected C - Built-In Check Valve 25 Port Size in 1/32” Normally Open B Design or Series A, B & W Series D Manual Lift Stem O Normally open valves available in B9, E9 through E42 series only, and require OMKC-2 Coil Assembly. Add prefix D for direct connected assembly in MA32 and MA17A3 series. Example: DMA32P3.
Bulletin 30-10 / Page 27 Application Sporlan Solenoid Valves They are equally suitable for many other less common forms of refrigerant control. These applications and other related topics are discussed in the following section. For applications not covered, consult Sporlan, Washington, MO. Suction Line Service Liquid Line Service The primary purpose of a solenoid valve in a refrigerant liquid line is to prevent flow into the evaporator during the off-cycle.
Page 28 / Bulletin 30-10 Application Sporlan Solenoid Valves There are several piping arrangements used for hot gas defrost systems, one of which is shown in Figure 9. A portion of the compressor discharge gas is passed through the solenoid valve into the evaporator. The solenoid valve may be controlled either manually or automatically for this duty. for refrigeration and air conditioning controls.
OFFER OF SALE The items described in this document and other documents and descriptions provided by Parker Hannifin Corporation, its subsidiaries and its authorized distributors (“Seller”) are hereby offered for sale at prices to be established by Seller. This offer and its acceptance by any customer (“Buyer”) shall be governed by all of the following Terms and Conditions.