Fan Installation & Operating Instructions Please Read and Save These Instructions. DO NOT CONNECT POWER SUPPLY UNTIL FAN IS COMPLETELY INSTALLED. MAKE SURE ELECTRICAL SERVICE TO FAN IS LOCKED IN “OFF” POSITION. DISCONNECT POWER BEFORE SERVICING FAN. 1. WARNING! For General Ventilating Use Only. Do Not Use to Exhaust Hazardous, Corrosive or Explosive Materials, Gases or Vapors. See Vapor Intrusion Application Note #AN001 for important information on VI Applications. See RadonAway.com/vapor-intrusion. 2.
Fan Installation & Operating Instructions Fan Series RV100 p/n 28040 RV125 p/n 28042 RV150 p/n 28041 RV200 p/n 28049 1.0 MOUNTING The Spruce RV Series fans may be mounted at any angle without affecting performance although the vertical mounting position shown in Fig. 1 is highly recommended. If the vertical mounting position is not possible, care should be taken to avoid creating a low spot in the fan/duct system where condensation might accumulate in the fan housing as shown in Fig. 2.
.0 BACKDRAFT DAMPERS Backdraft dampers allow airflow in only one direction preventing cold/hot drafts from entering the vented area and minimize possible condensation and icing within the system while the fan is not operating. Backdraft dampers are highly recommended at each intake grille for bathroom ventilation in all cold climate installations. Installation instructions are included with Spruce backdraft dampers. 5.
Fig. 4 7.0 INSTALLATION Step 1: Install Mounting Bracket as shown (Fig. 4). Insert Grommets into slots in Mounting Bracket. Orient the Electrical Box relative to Mounting Bracket as required. Attach the fan to the Mounting Bracket with 3 #10 selftapping screws, provided. Avoid over tightening screws. Step 2: Select location for fan mounting. A location 2/3 along the ducting, a minimum of 10 feet away from the inlet vent to the fan or the Y/T of a multiintake system- will provide the quietest operation.
RV SERIES PRODUCT SPECIFICATIONS The following chart shows fan performance for RV Series Commercial/Residential Fans: Typical CFM vs. Static Pressure "WC 0" .2" .5" .75" 1.0" 1.25" 1.5" Max Static Pressure RV100 113 100 71 46 18 - - 1.06" WC RV125 115 110 98 87 71 57 43 2.08" WC RV150 150 140 119 98 76 50 24 1.77" WC RV200 187 170 144 121 87 47 1 1.45" WC Power Consumption @ 120 VAC, 60Hz (1.
IN009 Rev PageN60120 of 7 3 Saber Way, Ward Hill, MA 01835 | spruce.
IMPORTANT INSTRUCTIONS TO INSTALLER Inspect the RV Series Fan for shipping damage within 15 days of receipt. Notify Spruce of any damages immediately. Spruce is not responsible for damages incurred during shipping. However, for your benefit, Spruce does insure shipments. There are no user serviceable parts inside the fan. Do not attempt to open. Return unit to factory for service. Install the RV Series Fan in accordance with all state and local building codes and state regulations.