/ Marley MC Fluid Cooler / Engineering Data & Specifications
Marley / MC Fluid Cooler / Table of Contents Engineering Data Schematic Support Hoisting Info Noise Attenuator Option Freeze Protection Water Quality 5 11 12 13 14 15 Specifications / Base Base Thermal Performance Performance Warranty Coil Design Loading Construction Mechanical Equipment Drift Eliminators Hot Water Distribution System Casing Access Collection Basin Warranty 16 16 16 17 17 17 18 19 19 19 19 19 19 Specifications / Options Stainless Steel Options Stainless Steel Collection Basin All Stain
Marley / MC Fluid Cooler / ■ Air Movement Package Forward-curved centrifugal fans are dynamically balanced and mounted on tubular steel shafts. Fans are supported by roller-bearings mounted at both ends with heavy-guage steel supports. Spherical roller bearings are rated at an L10 life of 50,000 hours. Fan guard / Air-inlet screens are 16 gauge galvanized steel. TEFC Fan Motor—1.15 service factor, variable torque, and specially insulated for fluid cooler duty.
Marley / MC Fluid Cooler / The Marley MC Fluid Cooler is particularly suited to the urban environment, reducing noise while increasing energy efficiency and performance. By keeping the process fluid in a clean, closed loop, and combining the function of a cooling tower and heat exchanger into one system, they provide superior operational and maintenance benefits.
Marley / MC Fluid Cooler / Engineering Data : Schematic 5 Use this data for preliminary layouts only. Obtain current drawing from your Marley sales representative. The UPDATE web-based selection software —available at www.spxcooling.com—provides MC Fluid Cooler model recommendations based on customer's specific design requirements.
Marley / MC Fluid Cooler / Engineering Data : Schematic Dimensions Model H C Motor kW 2832 813 3.7 7012H081 5.6 7012D101 2.2 7012F101 3061 1041 3.7 7012H101 5.6 7012D121 2.2 7012F121 3289 1270 7012H121 3.7 813 5.6 7.5 7013F101 3.7 3061 1041 5.6 7013J101 7.5 7013F121 3.7 7013H121 3289 1270 7013J121 813 5.6 7.5 1041 7.5 11.2 7014H121 5.6 NOTE 1412 977 .4 1854 1583 1148 .4 2037 1754 1320 .6 2207 1830 1278 .6 2448 2060 1509 .6 2696 2290 1739 .
Marley / MC Fluid Cooler / Engineering Data : Schematic 7 Use this data for preliminary layouts only. Obtain current drawing from your Marley sales representative. The UPDATE web-based selection software —available at www.spxcooling.com—provides MC Fluid Cooler model recommendations based on customer's specific design requirements.
Marley / MC Fluid Cooler / Engineering Data : Schematic Dimensions Model H C Motor kW 7054L081 15 7054M081 18.6 7054N081 4172 813 22.4 7054P081 29.8 7054Q081 37.3 7054L101 15 7054M101 18.6 7054N101 4400 1041 22.4 7054P101 29.8 7054Q101 37.3 7054L121 15 7054M121 18.6 7054N121 4629 1270 7054P121 22.4 37.3 7055P081 15 x 2 4172 813 7055R081 1041 NOTE Heaviest Section 2.2 5749 4105 2920 2.2 6351 4658 3472 2.2 6868 5128 3942 18.6 x 2 3.
Marley / MC Fluid Cooler / Engineering Data : Schematic 9 Use this data for preliminary layouts only. Obtain current drawing from your Marley sales representative. The UPDATE web-based selection software —available at www.spxcooling.com—provides MC Fluid Cooler model recommendations based on customer's specific design requirements.
Marley / MC Fluid Cooler / Engineering Data : Schematic Dimensions Model H C 4174 813 22.4 7073P081 29.8 7073M101 18.6 7073N101 4402 1041 7073P101 22.4 1270 22.4 29.8 7074N081 22.4 4174 813 29.8 7074Q081 37.3 7074N101 22.4 7074P101 4402 1041 29.8 7074Q101 37.3 7074N121 22.4 7074P121 4613 1270 29.8 7074Q121 37.3 7075Q081 18.6 x 2 7075R081 4174 813 7075T081 1041 6190 4541 2930 2.2 6769 5074 3463 2.2 7351 5608 3997 3.7 7855 5619 3549 3.
Marley / MC Fluid Cooler / Engineering Data: Support 11 LENGTH C A 21 C ANCHORCL BOLT CL ANCHOR BOLT ANCHOR CL BOLT A HOLES FOR DIA.
Marley / MC Fluid Cooler / Engineering Data : Hoisting B A 80°MAX D C Lower Module Model 12 Upper Module A B Weight kg C D Weight kg 7012 1422 1143 435 1600 1143 1320 7013 2337 1143 549 2515 1143 1740 7014 3302 1143 699 3429 1143 2175 7054 1245 2057 1186 3327 2438 3942 7055 3073 2057 1640 1753 2438 5450 7073 2515 2794 1610 2515 2794 3996 7074 1295 2642 2071 3531 2794 4908 7075 2743 2642 2905 5207 2794 6545 NOTE 1 Hoisting operations can
Marley / MC Fluid Cooler / Engineering Data : Schematic : Attenuators E A D C SIDE ELEVATION AIR INLET ELEVATION ALL MODELS B Dimensions Model Depth A 7012 7013 7014 7054 7055 7073 7074 7075 B C D E 610 1824 1100 1113 1126 1251 1220 1824 1700 1113 1726 1251 610 2735 1100 1113 1126 1251 1220 2735 1700 1113 1726 1251 610 3648 1100 1113 1126 1251 1220 3648 1700 1113 1726 1251 610 3550 1100 2121 1126 2400 1220 3550 1700 2121 1726 2400 610 5
Marley / MC Fluid Cooler/ Engineering Data: Freeze Prevention Fluid Cooler Coil Fluid Cooling Recirculating Water When the ambient temperature falls below 0°C, heat loss from the coil can be substantial even without recirculating water flowing over the coil. The process fluid, without an applied heat load, may be prone to freezing. There are various methods to protect against coil freezing. When the ambient air temperature falls below 0°C, the recirculating water within the fluid cooler can freeze.
Marley / MC Fluid Cooler / Engineering Data: Water Quality The MC Fluid Cooler can be a very effective air washer. Atmospheric dust able to pass through the relatively small louver openings will enter the recirculating water system. Increased concentrations can intensify systems maintenance by clogging screens and strainers—and smaller particulates can coat system heat transfer surfaces.
Marley / MC Fluid Cooler / Specifications: Base Specifications Specification Value 1.0 Base: 1.1 Furnish and install a forced-draft, counterflow-type, factory assembled, film fill, industrial duty, galvanized steel, closed circuit fluid cooler. Unit shall consist of _____ cell(s), as shown on plans. The limiting overall dimensions of the fluid cooler shall be _____ wide, _____ long, and _____ high. Total operating kW of all fans shall not exceed _____ kW, consisting of_____ @ _____ kW motor(s).
Marley / MC Fluid Cooler / Specifications: Base Specifications Specification Value the test and will make such corrections as are appropriate and agreeable to the owner to compensate for the performance deficiency. 4.0 Coil: 4.1 Coil(s) shall consist of fully welded box headers with serpentine coils and hot-dip galvanized after fabrication. Coils shall be tested to 2757 kPa air pressure while immersed in water. Maximum operating design pressure shall be 1551 kPa.
Marley / MC Fluid Cooler / Specifications: Base Specifications Specification Value take the above water quality and load carrying capabilities into account in the selection of their materials of manufacture. 7.0 Mechanical Equipment: 7.1 Fan(s) shall be forward curved centrifugal-type, which are statically and dynamically balanced.
Marley / MC Fluid Cooler / Specifications: Base Specifications 8.0 Drift Eliminators: 8.1 Drift eliminators shall be PVC, triple pass and shall limit drift losses to no more than 0.005% of the design water flow rate. 9.0 Hot Water Distribution System: 9.1 A pressured spray system shall distribute water evenly over the fill.
Marley / MC Fluid Cooler / Specifications: Options Specifications Specification Value Stainless Steel Options Stainless Steel Collection Basin: 12.1: Replace paragraph 12.1 with the following: The collection basin shall be heavy-gauge Series 300 stainless steel. Suction connections shall be equipped with stainless steel debris screens. A factory installed, float operated, mechanical make-up valve shall be included. An overflow and drain connection shall be provided in each cell of the fluid cooler.
Marley / MC Fluid Cooler / Specifications: Options Specifications Specification Value Convenience and Safety Options Top Access Platform: 11.2 Add the following paragraph in the Access section: There shall be an access platform at the top of the fluid cooler to allow access to the drift eliminators and distribution system. The platform shall be free-standing galvanized steel bar grating, supported by galvanized steel framework.
Marley / MC Fluid Cooler / Specifications: Options Specifications Access Door Platform: 11.4 Add the following paragraph in the Access section: There shall be an access platform at the base of the fluid cooler extending across the width of the casing. The platform shall be galvanized steel bar grating, supported by galvanized steel framework attached to the fluid cooler. The platform shall be surrounded by a handrail, kneerail, and toeboard. Distribution System Access Door Platform: 10.
Marley / MC Fluid Cooler / Specifications: Options Specification Value Specifications temperature at the coil and the other for set point. Process temperature input shall be obtained using a thermal sensing device on the process coil and wired back to the solid state temperature controller in the control panel. Staging of multiple motors and speeds will be accomplished with an integral PLC. Vibration Limit Switch: 6.
Marley / MC Fluid Cooler / Specifications: Options Specifications in the off position for safety. The VFD system shall receive a speed reference signal from the Building Management System monitoring the tower fluid temperature. As an option to receiving the speed reference signal from a building management system, the drive must have the capability to receive a 4-20 ma temperature signal from an RTD transmitter.
Marley / MC Fluid Cooler / Specifications: Options Specifications teeth or drive shafts. The VFD shall catch a fan spinning in the reverse direction without tripping. The panel shall include a main disconnect with short circuit protection and external operating handle, lockable in the off position for safety. The system shall include a solid state, PI temperature controller to adjust frequency output of the drive in response to the tower fluid temperature.
Marley / MC Fluid Cooler / Specifications: Options Specifications Specification Value Miscellaneous Options Sound Control 1.2 Add the following paragraph under Base: The fluid cooler shall be quiet operation, and shall produce an overall level of sound not higher than _______ dB(A) measured at the critical location indicated on the plans.
Marley / MC Fluid Cooler / Specifications: Options Specifications Discharge Hood: 6.4 Add the following paragraph to the Mechanical Equipment Section: There shall be a galvanized steel tapered duct on the discharge side of the fluid cooler. Drift eliminators shall be repositioned into the lower section of the duct.