Specific Requirements for the Canadian Market 
Installation and Product Standards
The installation standard in Canada is the Canadian Electrical Code (CEC). The 
CEC and the NEC are similar but not 100% equivalent. 
The same is true for the CSA standards and corresponding UL standards (see 
Table 73). Some of the major differences are detailed below.
Certification Process
As in the U.S., nationally recognized testing laboratories (such as: CSA, ETL, TUV, 
and UL) are able to certify equipment according to these CSA standards. Refer to 
“Acceptance of Electrical Equipment in the U.S.” on page 5.
Technical Differences between Canadian and U.S. Standards
Some examples of differences between the Canadian and U.S. standards that 
currently apply to motor starters are listed below in Table 73. The TeSys™ product 
line is designed for compliance and compatibility with both the UL and the CSA 
requirements.
• Type E combination motors starters are recognized in Canada, however, the 
Type F combination starters are not currently accepted in Canada.
• Type E applications don't require the use of large spacing adapters when used 
in Canada.
• Group installation is recognized but the rules to define the common branch-
circuit protection setting is quite different.
• Industrial control panels must meet CSA C22.2 No. 14
• Elevator equipment appliances must comply with the specific CSA Nr. B44.1 
standard. 
• Product marking requirements differ slightly.
Table 73 –  Comparison of CSA and UL Standards
 Standard Name   CSA Standard   UL Standard 
Enclosed and Dead-Front Switches   CSA C22.2 No. 4   UL 98 
Low-Voltage Fuses: Part 1: General Requirements   CSA C22.2 No. 248   UL 248 
Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker 
Enclosures 
 CSA C22.2 No. 5   UL 489 
Industrial Control Equipment   CSA C22.2 No. 14   UL 508 
Elevator Equipment   CSA No. B44.1   Partially UL 508 