Brochure
Pendant Stations
Type SKYP General Information
14
07/2013 © 2013 Schneider Electric
All Rights Reserved
™
Type SKYP General Information
This line of pendant stations consists of polymeric enclosures (2–10 units),
push button units (1–5 speed), and laminated legend plates. All enclosures
have an extra single-unit space near the top that permits the installation of a
toggle switch, a Type SK operator or pilot light, or a warning label (see
Table 29 on page 15). All enclosures come standard with a stainless-steel
hanger bracket and internal strain-relief post. The enclosures are yellow
with a threaded opening in the top. The complete line is UL Listed and CSA
certified, with NEMA Type environmental ratings 1, 2, 3, 3R, 4, 4X, and 12
(NEMA 4 only with legend plates installed). To ensure Type 4X and 13
integrity, use only Type 4X and 13 operators or closing plates.
Type SKYP Specifications
There is a 10% charge for assembly. To place a custom pendant order,
use the worksheet on 18 as a guide. Orders must be placed through the
Product Selector in Quote to Cash.
Table 24: Type SKYP Specifications
Electrical
Ratings
Types SKRU2–SKRU5: AC = NEMA / UL B300; DC = NEMA / UL P600
Types SKRU1, 10, 11: AC = NEMA / UL A600: DC = NEMA / UL P600
Enclosure Type UL Type 1, 2, 3, 3R, 4, 4X, 12, and 13
Operating
Temperature
-30 C to +60 C (-13 F to +140 F)
Storage
Temperature
-40 C to +70 C (-40 F to +158 F)
Housing Material Polycarbonate
Cable Entry 1/2” NPT
Approvals
File E78403
CCN NKCR
File LR 25490
Class 3211 03
Lifetime
Enclosure
Warranty
®
Table 25: Electrical Contact Ratings (Types SKRU2 through SKRU5)
AC—NEMA / UL Type B300
Volts
[1]
1
OSHA Regulation, Section 1910.170 Overhead and Gantry Cranes, limits the voltage at pendant push buttons to 150 Vac or 300 Vdc.
Inductive, 35% Power Factor Resistive, 75% Power Factor
Make Break
Continuous Carrying Amperes
Make, Break, and
Continuous Carrying Amperes
AVAAVA
120 30 3600 3 360 5 5
240 15 3600 1.5 360 5 5
Table 26: Electrical Contact Ratings (Types SKRU1, 10, and 11)
AC—NEMA / UL Type A600 DC—Standard Duty, NEMA / UL Type P600
Volts
[1]
1
OSHA Regulation, Section 1910.170 Overhead and Gantry Cranes, limits the voltage at pendant push buttons to 150 Vac or 300 Vdc.
Inductive, 35% Power Factor
Resistive,
75% Power Factor
Volts
Inductive and Resistive
Make
Amperes
Break
Amperes
Continuous
Carrying Amperes
Make, Break, and Continuous
Carrying Amperes
Make and
Break Amperes
Continuous
Carrying
Amperes
120 60 6 10 10 120 1.1 10
240 30 3 10 10 240 0.55 10
480 15 1.5 10 10 — — —
600 12 1.2 10 10 600 0.2 10