User Guide

S1A73476 - 04/2019 1/2
Annex to the Quick Start
Guide ATV212
Short-Circuit Current Ratings (SCCR) and Branch Circuit Protection
The combinations in the table below have been tested per UL508C (Reference UL file E116875). These ratings allow proper
coordination of short circuit protection. All the ratings of the product have a 100 kA interrupt rating at the output as per UL508C
testing.
The opening of the branch circuit protective device may be an indication that a fault current has been interrupted.
75°C (167°F) copper conductor with the AWG wire size shown on nameplate for all sizes.
Suitable for use on a circuit capable of delivering not more than __X__ rms symmetrical kiloAmperes, __Y__ Volts maximum, when protected by
__Z1__ with a maximum rating of __Z2_.
ATV212 AC Drive Containment Short Circuit Current Rating (a)
Input Voltage
60 Hz
(Y)
Power Ratings
Catalog Number
Output
interrupt
Rating
With Circuit Breaker With GVxP With Fuses
PowerPact
Catalog
Number
SCCR
(X) (b)
SCCR
(X) (c) GV2P/3P
Type E (d)
SCCR
(b) (c)
Fuses (A)
600 V
class J (e)
(Z1, Z2)
SCCR
(b) (c)
(kW) (HP)
(kAIC)
(kA) (kA) (kA) (kA)
208 V,
3 phase
0.75 1 ATV212H075M3X 100 HDL36015 22 22 GV2P10 22 10 100
1.5 2 ATV212HU15M3X 100 HDL36015 22 22 GV2P14 22 15 100
2.2 3 ATV212HU22M3X 100 HDL36020 22 22 GV2P16 22 30 100
3 ATV212HU30M3X 100 HDL36030 22 22 GV2P20 22 35 100
4 5 ATV212HU40M3X 100 HDL36040 22 22 GV2P20 22 35 100
5.5 7.5 ATV212HU55M3X 100 HDL36050 22 22 GV2P22 22 50 100
7.5 10 ATV212HU75M3X 100 HDL36070 22 22 GV2P32 22 60 100
11 15 ATV212HD11M3X 100 HDL36100 22 22 GV3P50 22 100 100
15 20 ATV212HD15M3X 100 HDL36125 22 22 GV3P65 22 125 100
18.5 25 ATV212HD18M3X 100 JDL36175 22 22 - - 150 100
22 30 ATV212HD22M3X 100 JDL36200 22 22 - - 175 100
30 40 ATV212HD30M3X 100 JDL36250 22 22 - - 200 100
230 V,
3 phase
0.75 1 ATV212H075M3X 100 HDL36015 22 22 GV2P10 22 10 100
1.5 2 ATV212HU15M3X 100 HDL36015 22 22 GV2P10 22 15 100
2.2 3 ATV212HU22M3X 100 HDL36020 22 22 GV2P14 22 30 100
3 ATV212HU30M3X 100 HDL36030 22 22 GV2P20 22 35 100
4 5 ATV212HU40M3X 100 HDL36035 22 22 GV2P20 22 35 100
5.5 7.5 ATV212HU55M3X 100 HDL36045 22 22 GV2P21 22 45 100
7.5 10 ATV212HU75M3X 100 HDL36060 22 22 GV2P32 22 60 100
11 15 ATV212HD11M3X 100 HDL36090 22 22 GV3P40 22 90 100
15 20 ATV212HD15M3X 100 HDL36125 22 22 GV3P50 22 110 100
18.5 25 ATV212HD18M3X 100 HDL36150 22 22 - - 150 100
22 30 ATV212HD22M3X 100 JDL36175 22 22 - - 175 100
30 40 ATV212HD30M3X 100 JDL36225 22 22 - - 200 100
480 V,
3 phase
0.75 1 ATV212H075N4 100 HDL36015 - 22 GV2P07 22 5 100
1.5 2 ATV212HU15N4 100 HDL36015 - 22 GV2P08 22 7.5 100
2.2 3 ATV212HU22N4 100 HDL36015 - 22 GV2P10 22 10 100
3 ATV212HU30N4 100 HDL36020 - 22 GV2P14 22 15 100
4 5 ATV212HU40N4 100 HDL36020 - 22 GV2P14 22 15 100
5.5 7.5 ATV212HU55N4 100 HDL36025 - 22 GV2P16 22 20 100
7.5 10 ATV212HU75N4 100 HDL36030 - 22 GV2P20 22 30 100
11 15 ATV212HD11N4 100 HDL36045 - 22 GV2P21 22 45 100
15 20 ATV212HD15N4 100 HDL36060 10 22 GV2P22 22 60 100
18.5 25 ATV212HD18N4 100 HDL36070 10 22 GV2P32 22 80 100
22 30 ATV212HD22N4S 100 HDL36090 10 22 GV3P40 22 90 100
22 30 ATV212HD22N4 100 HDL36090 - 22 - - 90 100
30 40 ATV212HD30N4 100 HDL36125 - 22 - - 110 100
37 50 ATV212HD37N4 100 HDL36125 10 10 - - 125 100
45 60 ATV212HD45N4 100 HDL36150 10 10 - - 150 100
55 75 ATV212HD55N4 100 JDL36175 10 10 - - 200 100
75 100 ATV212HD75N4 100 JDL36225 10 10 - - 250 100
ANNEX
S1A7347604
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Current-carrying parts and other components of the controller should be examined and replaced if damaged.
If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced.
Failure to follow these instructions will result in death or serious injury.