General Characteristics
Environmental
Characteristics
Conforming to standards UL 508, UL 60950, IED 60950, 60947-6-2
Certification cULus, EAC, FCC, CE
Ambient temperature
Storage: -40 to +185°F (-40 to +85°C)
Operation: -13 to +158°F (-25 to +70°C)
Protective Treatment ULVO, conforming to IEC 60068-2-30
Pollution Level 3
Mechanical
Characteristics
Shock resistance
Conforming to IEC 60068-2-27 15g/11ms,
1/2 sinusoidal
Resistance to sinusoidal vibrations Conforming to IEC 60068-2-6
Electrical
Characteristics
Power Supply 24 Vdc, -20%/+10% (19.2 to 26.4 Vdc)
Consumption
Typical: 24 Vdc, 165 mA at 20°C
Maximum with gateway: 26.4 Vdc, 420 mA at 60°C
Physical
Characteristics
Dimensions 2.83 x 4.52 X 2.79 in. (72 x 115 x 71 mm)
Mounting DIN rail
Weight 0.51 lb. (229.5 g)
Degree of protection of the installed
I/O application module
On the front panel (wall mounted enclosure): IP4x
I/O parts: IP3x
Connectors: IP2x
Connections Screw type terminal blocks
Technical
Characteristics
24 Vdc power
supply
Power supply type Regulated switch type
Rated power 72 W
Input voltage
100–120 Vac for single phase
200–500 Vac phase-to-phase maximum
PFC filter With IEC 61000-3-2
Output voltage 24 Vdc
Power supply out current 3 A
NOTE: It is recommended to use an UL listed/UL listed recognized limited voltage/limited
current or a class 2 power supply with a 24 Vdc, 3 A maximum.
Digital Inputs
Digital input type
Self powered digital input with current limitations as
per IEC 61131-2 type 2 standards (7 mA)
Input limit values at state 1 (close) 19.8–25.2 Vdc, 6.1–8.8 mA
Input limit values at state 0 (open 0–19.8 Vdc, 0 mA
Maximum cable length 33 ft (10 m)
NOTE: For a length greater than 10 m (33 ft) and up to 300 m (1,000 ft), it is mandatory to
use a shielded twisted cable. The shield cable is connected to the I/O functional ground of
the I/O application module.
Digital Outputs
Digital output type Bistable relay
Rated load 5 A at 250 Vac
Rated carry current 5 A
Maximum switching voltage 380 Vac, 125 Vdc
Maximum switch current 5 A
Maximum switching power 1250 VA, 150 W
Minimum permissible load 10 mA at 5 Vdc
Contact resistance 30 mȍ
Maximum operating frequency
•18000 operations/hr (Mechanical)
•1800 operations/hr (Electrical)
Digital output relay protection by an
external fuse
External fuse of 5 A or less
Maximum cable length 10 m (33 ft)
Analog Inputs
The I/O application module analog input can be connected to a Pt100 temperature sensor
Range -22 to 392°F (-30 to 200°C)
Accuracy
-22 to 6
8°F (-30 to 20°C): ±3.6°F (2°C)
68 to 284°F (20 to 140°C): ±1.8°F (1°C)
284 to 392°F (140 to 200°C): ±3.6°F (2°C)
Refresh interval 5 s
13 14 23 24 33 34 T1
1
2
T2
1
APP
2
3
4
5
6
7
8
9
13
O1 O2 O3 A1
I1 I2 I3 I4 I5 I6CCC
14 23 24 33 34 T1 T2
I1
AI
O1
O2
O3
I2
I3
I4
I5
I6
LV434063
IO
1
APP
2
3
4
5
6
7
8
9
I
1
A
I
O
1
O
2
O3
I
2
I
3
I4
I5
I
6
LV434063
I
O
T
I1 I2 I3 I4 I5 I6CCC
A
C
E
F
G
HI
J
K
L
M
NO
D
B
24VDC
A. 24 Vdc power supply terminal block.
B. Digital input terminal block:
6 inputs, 3 commons and 1 shield.
C. 6 input status LEDs.
D. Analog input status LED.
E. 3 output status LEDs.
F. I/O application module identification labels.
G. Sealable transparent cover.
H. Analog input terminal block.
I. Digital output terminal blocks.
J. ULP status LED.
K. Test/reset button (accessible with cover closed).
L. Setting locking pad.
M. Application rotary switch: 1 to 9.
N. Switch for I/O addressing (IO 1 or IO 2).
O. ULP connectors.
L
M
G
F
E
D
C
N
O
K
J
I
H
B
A