Submittal Sheet

1-18
© 2019 Schneider Electric
All Rights Reserved
Homeline™ Miniature Circuit Breakers Homeline Plug-On Circuit Breakers
www.se.com/us
Class 1170 / Refer to Catalog 1100CT0501
1
LOAD CENTERS
Homeline Standard Plug-On Circuit Breakers
HOM 1P
1 Space Required
HOM 2P
2 Spaces Required
HOM2200BB
Branch Circuit Breaker
4 Spaces Required
The Square D Homeline circuit breakers are in a 1 in. wide format for 1-pole circuit
breakers. They are designed to plug into Homeline load centers.
Table 1.39: Standard HOM Plug-on Circuit Breakers
Ampere
Rating
AIR
1P—120/240 Vac
Cat. No.
2P—120/240 Vac Common Trip
Cat. No.
 15 A 10 kA
HOM115 [1][2] HOM215 [2]
 20 A 10 kA
HOM120 [1][2] HOM220 [2]
 25 A 10 kA
HOM125 [2] HOM225 [2]
 30 A 10 kA
HOM130 [2] HOM230 [2]
 35 A 10 kA
HOM235 [2]
 40 A 10 kA
HOM140 [2] HOM240 [2]
 45 A 10 kA
HOM245 [2]
 50 A 10 kA
HOM150 [2] HOM250 [2]
 60 A 10 kA
HOM260 [2]
 70 A 10 kA
HOM270 [2]
 80 A 10 kA
HOM280 [2]
 90 A 10 kA
HOM290 [2]
100 A 10 kA
HOM2100 [2]
110 A 10 kA
HOM2110 [2]
125 A 10 kA
HOM2125 [2]
150 A 10 kA
HOM2150BB [2][3]
175 A 10 kA
HOM2175BB [2][3]
200 A 10 kA
HOM2200BB [2][3]
Homeline High Magnetic Circuit Breakers (HOM-HM)
High magnetic trip circuit breakers are recommended for applications where high initial
inrush current may occur.
Table 1.40: HOM-HM Circuit Breakers
Amperes
1P—120/240 Vac 2Ps
15 A
HOM115HM [2]
20 A
HOM120HM [2]
Homeline Ground-Fault Circuit Breaker (HOM-GFI)
HOM 1P GFI
(With Ground Fault
Circuit Interrupter)
1 Space Required
HOM 2P GFI
(With Ground Fault
Circuit Interrupter)
2 Spaces Required
HOM-GFI circuit breakers provide overload and short circuit protection, combined with
Class A ground fault protection. Class A denotes a ground fault circuit interrupter that will
trip when a fault current to ground is 6 milliamperes or more.
Table 1.41: HOM-GFI Circuit Breakers
Ampere
Rating
AIR
1P—120 Vac
1 Space Required
2P—120/240 Vac
Common Trip
2 Spaces Required
15 A 10 kA HOM115GFI HOM215GFI
20 A 10 kA HOM120GFI HOM220GFI
30 A 10 kA HOM230GFI
40 A 10 kA HOM240GFI
50 A 10 kA HOM250GFI
Homeline Combination Arc Fault Circuit Interrupters (HOM-CAFI)
HOM 1P CAFI
Plug-on Neutral
HOM 1P CAFI
Pigtail
Homeline Combination Arc Fault Circuit Interrupters—Provide overload and short circuit
protection, plus arc fault protection in accordance with the NEC and UL1699.
Table 1.42: HOM-CAFI Circuit Breakers
Circuit Breaker Type Ampere Rating
Poles
120 Vac
Cat. No.
One-Pole
Combination Arc-Fault Circuit
Interrupter with Pigtail Neutral
15 A 1
HOM115CAFI [2]
20 A 1
HOM120CAFI [2]
Plug-On Neutral Combination
Arc-Fault Interrupter
15 A 1
HOM115PCAFI [2]
20 A 1
HOM120PCAFI [2]
Two-Pole
Combination Arc-Fault Circuit
Interrupter with Pigtail Neutral
15 A 2
HOM215CAFI [2] [4]
20 A 2
HOM220CAFI [2] [4]
[1] UL Listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
[2] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers.
[3] Requires four spaces (1 AWG–300 kcmil Al/Cu). Use only in panel rated 150 A or greater.
[4] For 120/240 V only, not for 208Y/120 V.
9/13/2019