Submittal Sheet

1-34
© 2019 Schneider Electric
All Rights Reserved
Combination Service Entrance Devices Rainproof, All-In-Ones, 100 to 225 A
Maximum
www.se.com/us
Class 4120
1
LOAD CENTERS
Meter Mains and All-In-Ones (100 to 225 A Maximum)
Ring or ringless type meter socket designs available
UL Listed, suitable only for use as service equipment
Meets EUSERC standards
Service disconnect(s) are supplied factory-installed, except
where noted
Semiflush-reverse design available, supplied with load
center (indoor access)
Supplied with 100% branch neutrals, all unused terminals
may be used for equipment grounding wires.
Meets Federal Specification W-P-115c as Type 1, Class 2
Table 1.76: All-In-One Combination Service Entrance Devices
Ampere Rating
Bypass Type
Service
(Type
of Feed)
UL and
EUSERC
Short Circuit
Current Rating
Cat. No.
(DE3A)
Service Disconnect(s)
Load Center and Branch
Circuit Breakers
(Order separately [33])
Hub Type [34]
(Order separately )
Line
Side
Main
Lugs
AWG/
kcmil
(Al/Cu)
Service
Ground
Lug
AWG/
kcmil
(Al/Cu)
Weight
Each
(Lbs)
and
Pallet
Qty.
Max. Quantity
Ampere
Rating Max.
Spaces
1P
2P
Circuits
(Max.)
Type
(Factory
Installed)
Ampere
Rating
Max.
Circuits
Tan-
dems
Ring Type, Homeline
Surface Mount Only
100 A None OH/UG 10 kA SC1624M100S 1 HOM2100 100 A 16 24 8 100 A
A 6–2/0 6–2/0
32, 24
125 A None OH/UG 10 kA SC1624M125S 1 HOM2125 125 A 16 24 8
125 A
[35]
200 A None OH/UG 22 kA SC2040M200S 1
QOM2200VH
200 A 20 40 20
200 A
[36]
A-L 4–250 6–2/0
45, 10
200 A None OH/UG 10 kA
SC2040M200C [37]
1 HOM2200 200 A 20 40 20 100 A
A or
A-L
6–300 8–1/0
47, 18
200 A None UG 10 kA
SU2040M200C [37]
1 HOM2200 200 A 20 40 20 100 A
A or
A-L
6–300 8–1/0
47, 18
Semiflush Mount Only
100 A None OH/UG 10 kA SC1624M100F 1 HOM2100 100 A 16 24 8 100 A A or
B30-
0
6–2/0 6–2/0
44, 20
125 A None
OH/UG 10 kA SC1624M125F 1 HOM2125 125 A 16 24 8 110 A
OH[38]/UG
22 kA SC2040M125F 1
QOM2125VH
125 A 20 40 20 110 A
A-L 4–250 8–2/0
51, 10
200 A None
OH[38]/UG
22 kA SC2040M200F 1
QOM2200VH
200 A 20 40 20
200 A
[36]
OH[39]/UG
22 kA
SC2636M200FPV [40]
1
QOM2200VH
200 A 26 36 10 100 A
A-L 4–250 8–2/0
56, 10
SC3040M200F 1
QOM2200VH
200 A 30 40 10 200 A
225 A None
OH[39]/UG
22 kA
SC3040M225F 1
QOM2225VH
225 A 30 40 10 200 A
SC2636M225FPV [40]
1
QOM2225VH
225 A 26 36 10 100 A
Surface Mount Only
100 A None
OH[41]
10 kA SO1020M100S 1 HOM2100 100 A 10 20 10 80 A A 6–1 8–4
20, 42
200 A None
OH[41]
22 kA SO2040M200S 1
QOM2200VH
200 A 20 40 20 200 A A 6–350 8–2/0
43, 21
200 A None OH/UG 22 kA
SC3040M200S 1
QOM2200VH
200 A 30 40 10 200 A
A-L
4–250 8–2/0
50, 10
SC40M200S 1
QOM2200VH
200 A 40 40 0 200 A 4–250 8–2/0
52, 10
REVERSE All-In-One—Semiflush Mount with Service Disconnect (outdoor access) and Load Center (indoor access)
200 A None UG 10 kA SU3040M200R 1
QOM2200VH
200 A
30 40 10
200 A
[36]
A or
B30-
0
6–300 12–1/0
60, 15
225 A None UG 10 kA SU3040M225R 1
QOM2225VH
225 A
Ringless, Homeline
Surface Mount Only
100 A
None
OH/UG
[41]
10 kA
RC1624M100S 1 HOM2100 100 A
16 24 8
100 A
A
6–2/0 6–2/0
32, 24
125 A RC1624M125S 1 HOM2125 125 A
 125 A
[35]
125 A Horn
OH/UG[41]
22 kA
RC2040M125SH [42] [43]
1
QOM2125VH
125 A 20 40 20 125 A
6–350 8–2/0
43, 21
125 A Horn
OH/UG[41]
22 kA
RC2040M125CH [42][44]
1
QOM2125VH
125 A 20 40 20 125 A
40, 21
150 A
Horn
OH/UG[41]
22 kA
RC2040M150SH [42] [43]
1
QOM2150VH
150 A 20 40 20 150 A
43, 21
Horn
OH/UG[41]
22 kA
RC2040M150CH [42][44]
1
QOM2150VH
150 A 20 40 20 150 A
40, 21
Lever
OH/UG[41]
22 kA
RC3040M150SL [45]
1
QOM2150VH [35]
200 A 30 40 10 150 A 76 / 12
200 A
None
OH/UG[41]
22 kA
RC2040M200S [42] [43]
1
QOM2200VH
200 A 20 40 20 200 A
43, 21
None
OH/UG[41]
22 kA
RC2040M200C [42]
1
QOM2200VH
200 A 20 40 20 200 A
40, 21
Horn
OH/UG[41]
22 kA
RC2040M200SH [42] [43]
1
QOM2200VH
200 A 20 40 20 200 A
43, 21
Horn
OH/UG[41]
22 kA
RC2040M200CH [42]
1
QOM2200VH
200 A 20 40 20 200 A
40, 21
Lever
OH/UG[41]
22 kA
RC3040M200SL [45]
1
QOM2200VH [35]
200 A 30 40 10 200 A 76 / 12
None
OH/UG[41]
22 kA RC2040M200CGP 1
QOM2200VH
200 A 20 40 20 200 A 48 / 21
Ringless, QO
Surface Mount Only
150 A Horn
OH/UG[41]
22 kA
QC2442M150SH [42]
[43]
1
QOM2150VH
150 A 24 42 18 150 A
A 6–350 8–2/0
43, 21
200 A
None
OH/UG[41]
22 kA
QC2442M200S [42] [43]
1
QOM2200VH
200 A 24 42 18 200 A
43, 21
None
OH/UG[41]
22 kA
QC2442M200C [42]
1
QOM2200VH
200 A 24 42 18 200 A
40, 21
Horn
OH/UG[41]
22 kA
QC2442M200SH [42]
[43]
1
QOM2200VH
200 A 24 42 18 200 A
43, 21
Horn
OH/UG[41]
22 kA
QC2442M200CH [42][44]
1
QOM2200VH
200 A 24 42 18 200 A
40, 21
200 A
None
OH/UG[41]
22 kA
QC3040M200S [43]
1
QOM2200VH
200 A 30 40 10 200 A
40, 21
Hom
OH/UG[41]
22 kA
QC3040M200SH [43]
1
QOM2200VH
200 A 30 40 10 200 A
40, 21
[33] To order branch circuit breakers, see QO Plug-On Circuit Breakers, page 1-3
[34] To order hubs, see Accessories and Hubs for CSEDs, page 1-37
[35] 125 A Homeline
2P circuit breaker can be installed in top position only. All other positions are limited to 100 A max.
[36] Use only 15–110 A and 150–200 A circuit breakers.
[37] Convertible to semiflush with SC200F flange kit (order separately).
[38] Suitable for OH service with addition of tunnel kit (SCTK20). Order separately.
[39] Suitable for OH service with addition of tunnel kit (SCTK30). Order separately.
[40] For use with Photovoltaic Systems. Provisions for field-installed CT. If required by adopted code, order retaining kit PK2SCPV separately, see Table 1.80 Accessories, page 1-37.
[41] Device does not meet EUSERC Specifications.
[42] Device supplied with barrel lock provisions factory-installed.
[43] Suitable for load wires to exit top endwall with addition of Tunnel Kit OHBS, (see Table 1.80 Accessories, page 1-37, check with local utility for approval.
[44] 5th jaw factory-installed.
[45] Suitable for load wires to exit top endwall with addition of Tunnel Kit OHBL, (see Table 1.80 Accessories, page 1-37, check with local utility for approval.
9/13/2019