Rainproof, Meter Mains and All-In-Ones,
150 to 200 A Maximum
RC/QC Solar Ready CSEDs
Class 4120
Meter Mains and All-In-Ones
Ringless Meter Sockets with barrel lock provisions factory
installed except for Cat. No. SO2040M200SS which is a
Ring Style meter socket with no provisions for barrel lock to
secure the meter cover
UL Listed, suitable only for use as service equipment
Service disconnect(s) are supplied factory-installed, except
where noted
Supplied with 100% branch neutrals, all unused terminals
may be used for equipment grounding wires
Meets Federal Specification W-P-115c as Type 1, Class 2
All devices have a 3" KO in the bottom endwall
Provisions for Field Installed CTs All Devices
Solar Ready kit SR69064A fits All Devices Below, order
from Table 1.66
Table 1.83: All-In-One Combination Service Entrance Devices
Ampere Rating
Bypass Type
Service
Type
Short
Circuit
Cur-
rent
Rating
Cat. No.
Service Disconnect(s)
Load Center and Branch
Circuit Breakers
(Order Separately [1]) Hub
Type
(Order
Sepa-
rately
[2])
Line
Side
Main
Lugs
AWG/
kcmil
(Al/Cu)
Service
Ground
Lug
AWG/
kcmil
(Al/Cu)
Max. Quantity
Ampere
Rating Max.
Spaces
1P
Circuits
Tan-
dems
2P
Circuits
(Max.)
Type
(Factory Installed
except where
noted)
Ampere
Rating
Meter Mains[3]
Surface Mount Only
Surface Mount—Supplied with Feed-Thru Lugs and Provisions for Branch Circuit Breakers
150
A
None OH/UG 22 kA
QC816F150SS [4] [5]
1
QOM2150VH
150 A 8 16 8 150 A
A 350 8–2/0
Lever OH/UG 22 kA
QC816F150SLS [4] [6]
1
QOM2150VH
150 A 8 16 8 150 A
200
A
None OH/UG 22 kA
QC816F200SS [4] [5]
1
QOM2200VH
200 A 8 16 8 200 A
Lever OH/UG 22 kA
QC816F200SLS [4] [6]
1
QOM2200VH
200 A 8 16 8 200 A
Surface Mount—Supplied with Feed-Thru Lugs and provisions for Branch Circuit Breakers
150
A
None OH/UG 22 kA
RC816F150SS [4] [5]
1
QOM2150VH
150 A 8 16 8 150 A A 6-350 8–2/0
Lever OH/UG 22 kA
RC816F150SLS [4] [6]
1
QOM2150VH
150 A 16 8 150 A A 6-350 8–2/0
200
A
None OH/UG 22 kA
RC816F200SS [4] [5]
1
QOM2200VH
200 A 8 16 8 200 A A 6-350 8–2/0
Horn OH/UG 22 kA
RC816F200SHS [4] [7] [5]
1
QOM2200VH
200 A 8 16 8 200 A A 6-350 8–2/0
Lever OH/UG 22 kA
RC816F200SLS [4] [6]
1
QOM2200VH
200 A 16 8 200 A A 6-350 8–2/0
All-in-One Combination Service Entrance Devices [3]
Surface Mount Only
200
A
None OH/UG 22 kA
QC2442M200SS [5]
1
QOM2200VH
200 A 24 42 18 200 A A 6-350 8–2/0
Horn OH/UG 22 kA
QC2442M200SHS [7] [5]
1
QOM2200VH
200 A 24 42 18 200 A A 6-350 8–2/0
150
A
Horn OH/UG 22 kA
RC2040M150SHS [7] [5]
1
QOM2150VH
150 A 20 40 20 150 A A 6-350 8–2/0
Lever OH/UG 22 kA
RC3040M150SLS [6]
1
QOM2150VH
150 A 30 40 10 150 A A 6-350 8–2/0
200
A
None OH/UG 22 kA
RC2040M200SS [5]
1
QOM2200VH
200 A 20 40 20 200 A A 6-350 8–2/0
Horn OH/UG 22 kA
RC2040M200SHS [7] [5]
1
QOM2200VH
200 A 20 40 20 200 A A 6-350 8–2/0
None OH 22 kA
SO2040M200SS [5]
1
QOM2200VH
200 A 20 40 20 200 A A 6-350 8–2/0
Lever OH/UG 22 kA
RC3040M200SLS [6]
1
QOM2200VH
200 A 30 40 10 200 A A 6-350 8–2/0
* Kit is to be installed between meter socket and Main Disconnect. May be used with Solar PV, Wind, fuel generators, and other power generation sources up to 80% of Mains Rating Maximum
160 A.
2
1
/
2
" Max “A” Hub
10.94
278
40.93
1040
18.35
466
5.32
135
C,D,E,F
E,F,G,H
A,B,C
A,B
12.57
319
48.62
1235
Lever
ByPass
Devices
RC816F150SS
RC816F200SS
RC816F200SHS
QC816F150SS
QC816F200SS
RC2040M150SHS
RC2040M200SS
RC2040M200SHS
SO2040M200SS
QC2442M200SS
QC2442M200SHS
QC816F150SLS
RC816F150SLS
RC3040M150SLS
QC816F200SLS
RC816F200SLS
RC3040M200SLS
Table 1.84: Knockouts
Symbol
A B C D E F G H I J
Conduit Size
(in.)
1/2 3/4 1 1-1/4 1-1/2 2 2-1/2 3 3-1/2 4
Table 1.85: All-in-One Combination Service Entrance Devices—Plug on Neutral
Main Breaker
Bus Bar
Ampere Rating
Bypass Type
Service
Type
Short Circuit
Current Rating
Cat. No.
Service Disconnect(s)
Load Center and Branch
Circuit Breakers
(Order Separately )
Hub Type (Order
Separately )
Line
Side
Main
Lugs
AWG/
kcmil
(Al/Cu)
Service
Ground
Lug
AWG/
kcmil
(Al/Cu)
Max. Quantity
Ampere
Rating Max.
Spaces
1P
Circuits
Tandems
2P
Circuits
(Max.)
Type
(Factory Installed
except where noted)
Homeline Surface Mount Only
200 A 200 A None OH/UG 22 kA
RC3042M200PS [5]
1
QOM2200VH
30 42 12 200 A A 6-350 12–2/0
1
LOAD CENTERS
[1] To order load centers and branch circuit breakers, see QO Plug-On Circuit Breakers, page 1-3 and Homeline Plug-On Circuit Breakers, page 1-18
[2] See Bolt-On Hubs, page 1-30
[3] Solar Ready Kit Part Number SR69064A * (This Kit Fits All Solar Ready Devices)
[4] Supplied with load side feed-thru lugs, for 4AWG-250 kcmil Al/Cu conductors.
[5] Suitable for load wires to exit top endwall with addition of Tunnel Kit OHBS. See (see Table 1.80 Accessories, page 1-37, check with local utility for approval.
[6] Suitable for load wires to exit top endwall with addition of Tunnel Kit OHBL. See(see Table 1.80 Accessories, page 1-37, check with local utility for approval.
[7] Device supplied with horn bypass and 5th jaw factory installed
9/13/2019