Technical Data Bulletin

1-6
© 2020 Schneider Electric
All Rights Reserved
12/02/2020
QO™ Miniature Circuit Breakers QO Plug-On Circuit Breakers
www.se.com/us
Class 685, 690, 730, 912, 950 / Refer to Catalog: 0730CT9801
1
LOAD CENTERS
QO-EPD/EPE Circuit Breakers
QO 1P
With Shunt Trip
QO-EPD/EPE circuit breakers provide overload and short circuit protection combined
with Class B ground fault protection. They are designed to provide ground fault
protection of equipment at a 30 mA level (EPD) or 100 mA level (EPE). They are not
designed to protect people from electrical shock.
Table 1.9: QO-EPD Circuit Breakers
Ampere
Rating
[19]
1P
120 Vac
10 k AIR
1 Space Required
2P Common Trip
120/240 Vac
10 k AIR
2 Spaces Required
3P Common Trip
240 Vac
10 k AIR
3 Spaces Required
15
QO115EPD QO215EPD
QO315EPD [20] QO315EPE [20]
20
QO120EPD QO220EPD
QO320EPD [20] QO320EPE [20]
25
QO125EPD QO225EPD
30
QO130EPD QO230EPD
QO330EPD [20] QO330EPE [20]
40
QO240EPD
QO340EPD [20] QO340EPE [20]
50
QO250EPD
QO350EPD [20] QO350EPE [20]
60
QO260EPD [21]
QO Switch Neutral Common Trip Circuit Breakers (QO-SWN)
Two-wire
QO-SWN
Three-wire
QO-SWN
Switch Neutral Common Trip 2008 NEC
®
514.11
Table 1.10: QO-SWN Circuit Breakers
Ampere
Rating [22]
2 Wire 120 Vac
10 k AIR
2 Spaces Required
3 Wire 120/240 Vac
10 k AIR
3 Spaces Required
10
QO210SWN QO310SWN
15
QO215SWN QO315SWN
20
QO220SWN QO320SWN
25
QO225SWN QO325SWN
30
QO230SWN QO330SWN
40
QO240SWN QO340SWN
50
QO250SWN QO350SWN
QO High Intensity Discharge Circuit Breakers (QO-HID)
HID circuit breakers are for use on circuits feeding fluorescent and high intensity
discharge (HID) lighting systems such as mercury vapor, metal halide, or high pressure
sodium. These circuit breakers are physically interchangeable with QO circuit breakers.
Table 1.11: QO-HID Circuit Breakers
Ampere
Rating [22]
1P 120/240 Vac
10 k AIR
1 Space Required
2P Common Trip
120/240 Vac
10 k AIR
2 Spaces Required
3P Common Trip
240 Vac
10 k AIR
3 Spaces Required
15
QO115HID [23]
QO215HID QO315HID
20
QO220HID QO320HID
25
QO125HID QO225HID QO325HID
30
QO130HID QO230HID QO330HID
40
QO140HID QO240HID
50
QO150HID QO250HID
QO Key Operated Circuit Breakers (QO-K)
QO-K Key Operated
Key operated QO circuit breakers are available in single-pole construction and can be
mounted in any single-pole space which will accept a standard QO circuit breaker. These
circuit breakers can be turned ON or OFF or to RESET with a special key (catalog
number QOK10) included with the circuit breaker. These circuit breakers are UL Listed
and available as shown in the table.
Table 1.12: QO-K Circuit Breakers
120 Vac—10 k AIR (1 Space Required)
Ampere
Rating [22]
Cat. No.
Ampere
Rating [22]
Cat. No.
10
QO110K
25
QO125K
15
QO115K
30
QO130K
20
QO120K
[19] 10–30 A circuit breakers are suitable for use with 60
o
C or 75
o
C conductors. 35–60 A circuit breakers are suitable for use with 75
o
C conductors.
[20] See note in Instruction Bulletin when using in an enclosure with a QO403 or QON prefix.
[21] Suitable only for feeding 240 Vac and 208 Vac two-wire loads. Does not contain load neutral connection.
[22] 10–30 A circuit breakers are suitable for use with 60oC or 75oC conductors. 35–60 A circuit breakers are suitable for use with 75oC conductors.
[23] UL Listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.