QO™ and QOU Miniature Circuit Breakers QO Plug-On Circuit Breakers
www.se.com/us
Class 685, 690, 730, 912, 950 / Refer to Catalog: 0730CT9801
QO Switch Neutral Common Trip Circuit Breakers (QO-SWN)
Two-wire
QO-SWN
Three-wire
QO-SWN
Switch Neutral Common Trip 2008 NEC
®
514.11
Table 7.10: QO-SWN Circuit Breakers
Ampere
Rating [19]
2 Wire 120 Vac
10 k AIR
2 Spaces Required
3 Wire 120/240 Vac
10 k AIR
3 Spaces Required
10
QO210SWN QO310SWN
15
QO215SWN QO315SWN
20
QO220SWN QO320SWN
25
QO225SWN QO325SWN
30
QO230SWN QO330SWN
40
QO240SWN QO340SWN
50
QO250SWN QO350SWN
QO High Intensity Discharge Circuit Breakers (QO-HID)
HID circuit breakers are for use on circuits feeding fluorescent and high intensity
discharge (HID) lighting systems such as mercury vapor, metal halide, or high pressure
sodium. These circuit breakers are physically interchangeable with QO circuit breakers.
Table 7.11: QO-HID Circuit Breakers
Ampere
Rating [19]
1P 120/240 Vac
10 k AIR
1 Space Required
2P Common Trip
120/240 Vac
10 k AIR
2 Spaces Required
3P Common Trip
240 Vac
10 k AIR
3 Spaces Required
15
QO115HID [20]
QO215HID QO315HID
20 —
QO220HID QO320HID
25
QO125HID QO225HID QO325HID
30
QO130HID QO230HID QO330HID
40
QO140HID QO240HID
—
50
QO150HID QO250HID
—
QO Key Operated Circuit Breakers (QO-K)
QO-K Key Operated
Key operated QO circuit breakers are available in single-pole construction and can be
mounted in any single-pole space which will accept a standard QO circuit breaker. These
circuit breakers can be turned ON or OFF or to RESET with a special key (catalog
number QOK10) included with the circuit breaker. These circuit breakers are UL Listed
and available as shown in the table.
Table 7.12: QO-K Circuit Breakers
120 Vac—10 k AIR (1 Space Required)
Ampere
Rating [19]
Cat. No.
Ampere
Rating [19]
Cat. No.
10
QO110K
25
QO125K
15
QO115K
30
QO130K
20
QO120K
QO High Magnetic Trip Circuit Breakers (QO-HM)
High magnetic trip circuit breakers are recommended for applications where high initial
inrush may occur and for individual dimmer applications.
Table 7.13: QO-HM Circuit Breakers
120 Vac—10 k AIR
Ampere Rating [19]
1P
15 A
QO115HM [21] [20]
20 A
QO120HM [21] [20]
Non-Automatic (Standard) Miniature Switches
Miniature non-automatic switches have the same physical packaging as miniature circuit
breakers, but open only when the handle is switched to the OFF position.
Non-automatic switches provide no overcurrent protection or short circuit protection.
They must not be used on systems that have an available fault current greater than the
values listed in the table. Non-automatic switches are UL Listed per UL 1087 and are
CSA certified.
Table 7.14: QO Non-Automatic Miniature Switches, 240 Vac 10 kA
Ampere Rating
2P 3P
60
QO200 QO300
100
QO2000 QO3000
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[19] 10–30 A circuit breakers are suitable for use with 60oC or 75oC conductors. 35–60 A circuit breakers are suitable for use with 75oC conductors.
[20] UL Listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
[21] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers.
9/13/2019