Plug-On Circuit Breakers Homeline™ Miniature Circuit Breakers
Class 1170 / Refer to Catalog 1100CT0501
Homeline Ground-Fault Circuit Breaker (HOM-GFI)
HOM 1P GFI
(With Ground Fault
Circuit Interrupter)
1 Space Required
HOM 2P GFI
(With Ground Fault
Circuit Interrupter)
2 Spaces Required
HOM-GFI circuit breakers provide overload and short circuit protection, combined with
Class A ground fault protection. Class A denotes a ground fault circuit interrupter that will
trip when a fault current to ground is 6 milliamperes or more.
Table 7.31: HOM-GFI Circuit Breakers
Ampere
Rating
AIR
1P—120 Vac
1 Space Required
2P—120/240 Vac
Common Trip
2 Spaces Required
15 A 10 kA HOM115GFI HOM215GFI
20 A 10 kA HOM120GFI HOM220GFI
30 A 10 kA HOM230GFI
40 A 10 kA HOM240GFI
50 A 10 kA HOM250GFI
Homeline Equipment Protection Device (HOM-EPD)
Homeline Equipment Protection Device—Circuit Breakers with 30 mA Equipment
Ground Fault Protection (UL Listed).
Table 7.32: HOM-EPD Circuit Breakers
Amperes
1P—120 Vac
2P—120/240 Vac
Common Trip
15 A HOM115EPD HOM215EPD
20 A HOM120EPD HOM220EPD
25 A HOM225EPD
30 A HOM230EPD
40 A HOM240EPD
50 A HOM250EPD
Homeline Tandem and Quad Tandem Circuit Breakers (HOMT)
Table 7.33: HOMT Tandem Circuit Breakers
Ampere Rating [5]
AIR
1P Tandem—120/240 Vac (One Space Required)
15 and 15 A 10 kA
HOMT1515 [6]
15 and 20 A 10 kA
HOMT1520 [6]
20 and 20 A 10 kA
HOMT2020 [6]
30 and 15 A 10 kA
HOMT3015 [6]
30 and 20 A 10 kA
HOMT3020 [6]
HOMT Quad
Circuit Breaker
2 Spaces Required
Table 7.34: HOMT Quad Tandem Circuit Breakers
Ampere Rating [5]
AIR
2P Tandem—120/240 Vac (Two Spaces
Required)
1P 2P
(2) 15 A
15 A 10 kA
HOMT1515215 [6]
(2) 15 A
20 A 10 kA
HOMT1515220 [6]
(2) 15 A
25 A 10 kA
HOMT1515225 [6]
(2) 15 A
30 A 10 kA
HOMT1515230 [6]
(2) 15 A
40 A 10 kA
HOMT1515240 [6]
(2) 15 A
50 A 10 kA
HOMT1515250 [6]
(2) 20 A
20 A 10 kA
HOMT2020220 [6]
(2) 20 A
25 A 10 kA
HOMT2020225 [6]
(2) 20 A
30 A 10 kA
HOMT2020230 [6]
(2) 20 A
40 A 10 kA
HOMT2020240 [6]
(2) 20 A
50 A 10 kA
HOMT2020250 [6]
NOTE: Typical catalog number (e.g. HOMT 1515230) represents two 1P, outer poles
(two 15 A 1P CBs) and one 2P inner circuit breaker with common trip (one 30 A 2P
CB).
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[5] 15– 20 A tandem or quad tandem circuit breakers are suitable for use with 60
o
C or 75
o
C conductors. 25– 50 A tandem or quad tandem circuit breakers are suitable for use with 75
o
C
conductors only.
[6] UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment haing motor group combinations and marked for use with HACR type circuit breakers.