PowerPact™ Molded Case Circuit Breakers PowerPact L-Frame Electronic-Trip Circuit
Breakers
www.se.com/us
Class 611 / Refer to Catalogs: 0611CT1001
PowerPact L-Frame Molded Case Circuit Breakers (600 A)
PowerPact L-Frame with Micrologic™ Trip Unit
A flexible, high performance offer certified to global standards.
•
Micrologic trip protection from 250–600 A up to 600 Vac
•
3- and 4-pole design; wide range of trip units to protect most applications
•
High performance UL listed interrupting ratings from 18 to 200 kA at 480 Vac
•
Standard (80%) or 100% rating
•
UL, CSA, NOM, IEC, CCC certified and CE marked for global acceptance
Table 7.65: L-Frame 600 A Standard (80% Rated) UL Current-Limiting
[26] Circuit Breakers with Lugs and Factory-Sealed Electronic Trip
Units Suitable for Reverse Connection
[27][28]
Electronic Trip Unit
Sensor
Rating
Interrupting Rating (80% Rated)
D G
J [26] L [26] R [26]
Terminal
Type
Function
Trip Unit
600 Vac, 50/60 Hz, 3P
Micrologic
Standard
LI
3.3 [29]
250 A LDL36250U31X LGL36250U31X LJL36250U31X LLL36250U31X LRL36250U31X
AL400L61K3 [30]
400 A LDL36400U31X LGL36400U31X LJL36400U31X LLL36400U31X LRL36400U31X
AL600LS52K3
600 A LDL36600U31X LGL36600U31X LJL36600U31X LLL36600U31X LRL36600U31X
Micrologic
Standard
LSI
3.3S [29]
[31]
250 A LDL36250U33X LGL36250U33X LJL36250U33X LLL36250U33X LRL36250U33X
AL400L61K3 [32]
400 A LDL36400U33X LGL36400U33X LJL36400U33X LLL36400U33X LRL36400U33X
AL600LS52K3
600 A LDL36600U33X LGL36600U33X LJL36600U33X LLL36600U33X LRL36600U33X
Micrologic
Ammeter
LSI 5.3A
400 A LDL36400U43X LGL36400U43X LJL36400U43X LLL36400U43X LRL36400U43X
AL600LS52K3
600 A LDL36600U43X LGL36600U43X LJL36600U43X LLL36600U43X LRL36600U43X
Micrologic
Energy
LSI 5.3E
400 A LDL36400U53X LGL36400U53X LJL36400U53X LLL36400U53X LRL36400U53X
600 A LDL36600U53X LGL36600U53X LJL36600U53X LLL36600U53X LRL36600U53X
Micrologic
Ammeter
LSIG 6.3A
400 A LDL36400U44X LGL36400U44X LJL36400U44X LLL36400U44X LRL36400U44X
600 A LDL36600U44X LGL36600U44X LJL36600U44X LLL36600U44X LRL36600U44X
Micrologic
Energy
LSIG
6.3E [33]
400 A LDL36400U54X LGL36400U54X LJL36400U54X LLL36400U54X LRL36400U54X
600 A LDL36600U54X LGL36600U54X LJL36600U54X LLL36600U54X LRL36600U54X
600 Vac, 50/60 Hz, 4P
Micrologic
Standard
LI 3.3
250 A LDL46250U31X LGL46250U31X LJL46250U31X LLL46250U31X LRL46250U31X AL400L61K4
400 A LDL46400U31X LGL46400U31X LJL46400U31X LLL46400U31X LRL46400U31X
AL600LS52K4
600 A LDL46600U31X LGL46600U31X LJL46600U31X LLL46600U31X LRL46600U31X
Micrologic
Standard
LSI
3.3S[31]
250 A LDL46250U33X LGL46250U33X LJL46250U33X LLL46250U33X LRL46250U33X AL400L61K4
400 A LDL46400U33X LGL46400U33X LJL46400U33X LLL46400U33X LRL46400U33X
AL600LS52K4
600 A LDL46600U33X LGL46600U33X LJL46600U33X LLL46600U33X LRL46600U33X
Micrologic
Ammeter
LSI 5.3A
400 A LDL46400U43X LGL46400U43X LJL46400U43X LLL46400U43X LRL46400U43X
AL600LS52K4
600 A LDL46600U43X LGL46600U43X LJL46600U43X LLL46600U43X LRL46600U43X
Micrologic
Energy
LSI 5.3E
400 A LDL46400U53X LGL46400U53X LJL46400U53X LLL46400U53X LRL46400U53X
600 A LDL46600U53X LGL46600U53X LJL46600U53X LLL46600U53X LRL46600U53X
Micrologic
Ammeter
LSIG 6.3A
400 A LDL46400U44X LGL46400U44X LJL46400U44X LLL46400U44X LRL46400U44X
600 A LDL46600U44X LGL46600U44X LJL46600U44X LLL46600U44X LRL46600U44X
Micrologic
Energy
LSIG 6.3E
400 A LDL46400U54X LGL46400U54X LJL46400U54X LLL46400U54X LRL46400U54X
600 A LDL46600U54X LGL46600U54X LJL46600U54X LLL46600U54X LRL46600U54X
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[26] Circuit breakers with J, L, and R interrupting ratings are UL certified as current limiting.
[27] See Supplemental Digest Section 3 for circuit breakers with field interchangeable trip units.
[28] For applications requiring communications see page 7-62.
[29] 3P circuit breakers with this trip unit can be used for 2P applications.
[30] AL600LS52K3 terminal wire range is (2) 2/0 AWG 500 kcmil Al/Cu
[31] Fixed ST and LT delays.
[32] AL400L61K3 terminal wire ranges are (1) 2 AWG–600 kcmil Cu or 1) 2 AWG–500 kcmil Al.
[33] 3-pole circuit breakers can be used for 2-pole applications. (For such instances, Micrologic 6.2 Ammeter and Energy trip units can be used for ground fault protection. Additional metering
capabilities are not guaranteed when using Micrologic Ammeter and Energy trip units for this type of application.)