Brochure

7-40
© 2019 Schneider Electric
All Rights Reserved
PowerPact™ Molded Case Circuit Breakers R-Frame Circuit Breakers
www.se.com/us
Class 612 / Refer to Catalog 0612CT0101
PowerPact R-Frame Molded Case Circuit Breakers (3000 A)
R-Frame Unit-Mount
Table 7.76: R-Frame Interrupting Ratings
Voltage
R-Frame Interrupting Rating
G J K L
240 Vac 65 kA 100 kA 65 kA 125 kA
480 Vac 35 kA 65 kA 65 kA 100 kA
600 Vac 18 kA 25 kA 65 kA 50 kA
Table 7.77: R-Frame Termination Options
Termination Letter
A = I-Line (See Section 9—Panelboards)
F = No Lugs (Includes terminal nut kit on both ends)
RJ F 3 6 3 0 0 U 4 1 A
For factory-installed termination, place termination letter in the third
block of the circuit breaker catalog number.
Dimensions see page 7-81
Trip Unit Options see page 7-60
Optional Lugs see page 7-54
Alternate Rating Plugs see page 7-62
Enclosures see page 7-82
Accessories see page 7-49
Micrologic electronic trip protection from 600–3000A up to 600 Vac
2-, 3- and 4-pole construction
UL listed interrupting ratings from 35 to 100 kA at 480Vac
Built-in Modbus protocol
Standard (80%) and 100% rating
UL, CSA, NOM, CCC and IEC certified and CE marked for global acceptance
Table 7.78: R-Frame 3000 A (600 Vac, 50/60 Hz) 3P Circuit Breaker with Electronic
Trip Unit
Electronic Trip Unit [43]
Sensor
Rating
Cat. No. [44]
Type
Function
Trip Unit
Basic Electronic Trip
Unit
(Not Interchangeable)
Fixed
long-time,
Adjustable
Instantaneous
ET1.0I
1200 A R■F36120
1600 A R■F36160
2000 A R■F36200
2500 A R■F36250
Micrologic
Interchangeable
Standard Trip Unit
LI 3.0
600 A
R■F36060(C)U31A
800 A
R■F36080(C)U31A
1000 A
R■F36100(C)U31A
1200 A
R■F36120(C)U31A
1600 A
R■F36160(C)U31A
2000 A
R■F36200(C)U31A
2500 A
R■F36250(C)U31A
3000 A
R■F36300(C)U31A
LSI 5.0
600 A
R■F36060(C)U33A
800 A
R■F36080(C)U33A
1000 A
R■F36100(C)U33A
1200 A
R■F36120(C)U33A
1600 A
R■F36160(C)U33A
2000 A
R■F36200(C)U33A
2500 A
R■F36250(C)U33A
3000 A
R■F36300(C)U33A
Micrologic
Interchangeable
Ammeter
Trip Unit
LI 3.0A
600 A
R■F36060(C)U41A
800 A
R■F36080(C)U41A
1000 A
R■F36100(C)U41A
1200 A
R■F36120(C)U41A
1600 A
R■F36160(C)U41A
2000 A
R■F36200(C)U41A
2500 A
R■F36250(C)U41A
3000 A
R■F36300(C)U41A
LSI 5.0A
600 A
R■F36060(C)U43A
800 A
R■F36080(C)U43A
1000 A
R■F36100(C)U43A
1200 A
R■F36120(C)U43A
1600 A
R■F36160(C)U43A
2000 A
R■F36200(C)U43A
2500 A
R■F36250(C)U43A
3000 A
R■F36300(C)U43A
LSIG 6.0A
600 A
■F36060(C)U44A
800 A
R■F36080(C)U44A
1000 A
R■F36100(C)U44A
1200 A
R■F36120(C)U44A
1600 A
R■F36160(C)U44A
2000 A
R■F36200(C)U44A
2500 A
R■F36250(C)U44A
3000 A
R■F36300(C)U44A
Micrologic
Interchangeable Power
Trip Unit
LSI 5.0P
600 A
R■F36060(C)U63AE1
800 A
R■F36080(C)U63AE1
1000 A
R■F36100(C)U63AE1
1200 A
R■F36120(C)U63AE1
1600 A
R■F36160(C)U63AE1
2000 A
R■F36200(C)U63AE1
2500 A
R■F36250(C)U63AE1
3000 A
R■F36300(C)U63AE1
LSIG 6.0P
600 A
R■F36060(C)U64AE1
800 A
R■F36080(C)U64AE1
1000 A
R■F36100(C)U64AE1
1200 A
R■F36120(C)U64AE1
1600 A
R■F36160(C)U64AE1
2000 A
R■F36200(C)U64AE1
2500 A
R■F36250(C)U64AE1
3000 A
R■F36300(C)U64AE1
Micrologic
Interchangeable
Harmonic Trip Unit
LSI 5.0H
600 A
R■F36060(C)U73AE1
800 A
R■F36080(C)U73AE1
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[43] For 2P and 4P information see Catalog 0612CT0101.
[44] To complete the catalog number: Replace the with the appropriate interrupting rating (G, J, K or L).; For 100% rated circuit breakers, add a “C” in the 9th character place. For example, the
catalog number for a 100% rated trip unit with LI trip functions at 2500 A would be RGF36025CU31A.
9/13/2019