Brochure

7-46
© 2019 Schneider Electric
All Rights Reserved
Motor Circuit Protectors PowerPact™ Electronic Motor Circuit
Protectors
www.se.com/us
Class 611 / Refer to Catalog 0611CT1001
PowerPact Motor Circuit Protection (AC Only)
Standard
Energy Efficient
Energie Efficace
Energia Eficiente
S
t
an
da
rd
E
ne
r
g
y E
f
f
icie
nt
E
ne
r
g
i
e
E
ffi
c
a
c
e
E
nergia
E
fici
e
nt
e
J-Frame Motor Circuit Protector
JJL36250M75
PowerPact electronic Motor Circuit Protectors (MCP) are magnetic-only instantaneous-
trip circuit breakers. Designed to offer short circuit protection, they are National Electrical
Code (NEC) compliant when installed as part of a combination controller having motor
overload protection.
Sensor ratings from 30–1200 A at up to 600 Vac
Electronic trip units with adjustable instantaneous trip ranges
3-pole available in unit mount and I-Line construction
Accept the same accessories and terminals as equivalent PowerPact circuit breakers
UL, CSA, IEC certified and CE marked for global acceptance
Selection
Determine the hp rating from the nameplate of the motor. Select a MCP with an ampere
rating recommended for the hp and voltage involved. When using the automatic settings
the MCP microprocessor automatically adjusts the trip settings for both current and time
to align with the start-up characteristic for the motor type, whether it is a standard or
energy-efficient motor. This includes a dampening means to accommodate a transient
motor in-rush current without nuisance tripping of the circuit breaker.
I
t
Standard
Energy Efficient
Energie Efficace
Motor Type / Tipo de Motor / Type de Moteur
Energia Eficiente
Table 7.92: Magnetic Only Electronic Motor Circuit Protection (MCP), 3–Pole, 600 Vac, 50/60 Hz—Three Device Solutions
Frame
Sensor
Rating
Full Load
Amperes
Range
Adjustable
Instantaneous
Trip Range
Trip Unit
Suffix
G
(See SCCR Cat.
No. Table Below)
J
(See SCCR Cat.
No. Table Below)
L
(See SCCR Cat.
No. Table Below)
R
(See SCCR Cat. No.
Table Below)
H-Frame
30 A 1.5–25 A 9–325 A
2.2M
M71 HGL36030M38X HJL36030M38X HLL36030M38X HRL36030M38X
50 A 14–42 A 84–546 A M72 HGL36050M38X HJL36050M38X HLL36050M38X HRL36050M38X
100 A 30–80 A 180–1040 A M73 HGL36100M38X HJL36100M38X HJL36100M38X HRL36100M38X
150 A 58–130 A 348–1690 A M74 HGL36150M38X HJL36150M38X HLL36150M38X HRL36150M38X
J-Frame 250 A 114–217 A 684–2500 A 2.2M M75 JGL36250M38X JJL36250M38X JLL36250M38X JRL36250M38X
L-Frame [6]
400 A 125–400 A 500–1200%
2.3M
M37X LGL36400M38X LJL36400M38X LLL36400M38X LRL36400M38X
600 A 200–600 A 500–1200 A M37X LGL36600M38X LJL36600M38X LLL36600M38X LRL36600M38X
P-Frame [6]
600 A 630 A 1200–10000 A
ET1.0M
M68 - PJL36060M68 PLL34060M68
800 A 600–800 A 1200–10000 A M68 PJL36080M68 PLL34080M68
1000 A 600–1000 A 1200–10000 A M69 PJL36100M69 PLL34100M69
1200 A 600–1200 A 1200–10000 A M70 PJL36120M70 PLL34120M70
Table 7.93: Maximum Rating or Setting of PowerPact Motor Protective Devices [1]
Type of Motor
Percentage of Full-load Current
Setting Not to Exceed[2]
A, B, C, D
Standard 800% 1300%
B, E
Energy Efficient
1100% 1700%
Table 7.94: Short Circuit Current Ratings (SCCR)
Contactor/Starter
Interrupting Rating
J L
200–240 Vac 480 Vac 600 Vac 200–240 Vac 480 Vac 600 Vac
Tesys D-line and F-line
100 kA 65 kA 25 kA 125 kA 100 kA 50 kA
NEMA Type S
100 kA 65 kA 25 kA 125 kA 100 kA 50 kA
See www.us.schneider-electric.us for specific ratings and combination ID numbers.
Accessories see page 7-49
Lugs see page 7-54
Dimensions see page 7-81
Enclosures see page 7-82
To select combination starters and motor controllers using MCP’s Meeting NEC
Article 430, refer to Section 16.
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[1] Based on 2017 NEC Table 430.52.
[2] See NEC Exception No. 1 to Table 430.52. The NEC 1300% maximum setting may be inadequate for instantaneous trip circuit breakers to withstand current surges typical of the
magnetization current of autotransformer type reduced voltage starters, or open transition wye-delta starters during transfer from “start” to “run,” constant hp multi-speed motors, and motors
labeled “high efficiency.”
9/13/2019