Circuit Breaker Enclosures
Enclosures
www.se.com/us
Class 610
LA/LH/Q4 Circuit Breaker Enclosures
LA/LH/Q4 Thermal-Magnetic Circuit Breaker Enclosures
LA400AWK
LA400S
LA400R
The enclosures for the LA/LH/Q4 thermal-magnetic circuit breakers are UL listed and
CSA certified. The enclosures are suitable for service entrance equipment when neutral
assembly is installed. The short circuit ratings of these enclosed circuit breakers are
equal to the interrupter rating, at the supply voltage marked on the circuit breaker
installed.
The LA400R enclosure has a blank top end wall and requires field cut openings. For
details and hub catalog numbers see Digest Section 3.
Table 7.173: LA/LH/Q4 Thermal-Magnetic Circuit Breaker Enclosures
Circuit Breaker Enclosure
Neutral
Assembly Kit
Service
Ground Kit
Cat. No.
Prefix
Rating
Poles Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
NEMA 1
Flush
NEMA 1
Surface
NEMA 3R
LAL, LHL,
Q4L
125–225 A
2, 3
LA400F[24] LA400S[24]
LA400R
SN225KA
PKOGTA2
225–400 A 400SN
LAL 125–400 3 —
LA400LS [25]
[26][27][28]
— SN400LA
NEMA 4, 4X,
5 [29] Type
304 Stainless
Steel [30]
NEMA 12K
With
Knockouts
NEMA 12/3R
Without
Knockouts
[30]
LAL, LHL,
Q4L
125–225 A
2, 3
LA400DS[27]
—
LA400AWK
[27]
SN225KA
PKOGTA2
225–400 A SN400LA
Enclosures for Special Applications
Hazardous Locations: NEMA 7 And NEMA 9 Circuit Breaker Enclosures
The NEMA 7 and 9 enclosures are cULus listed unless otherwise noted. They are rated
for use in hazardous locations as defined in NEC Article 500. The short circuit current
rating of the enclosed circuit breakers is equal to the rating of the circuit breaker installed
unless otherwise noted. They are suitable for use as service entrance equipment when
neutral is installed. Enclosures require the use of 75°C copper wire only. The NEMA 7
enclosures are suitable for rainproof applications when the included PKDB1 breather
and drain kit is installed.
Table 7.174: NEMA 7 and NEMA 9 Circuit Breaker Enclosures;
Thermal-Magnetic B-Frame and PowerPact J-Frame Cicuit Breakers
Circuit Breaker
Enclosure Catalog Number
Neutral
Assembly
Kit Cat. No.
Service
Ground Kit
Cat. No.
Threaded
Conduit
Provisions,
Inches
Cat. No.
Prefix
Rating
Poles
NEMA 7/9
Cast
Aluminum
[31][32]
NEMA 9 Cast
Aluminum
[32]
BKL 15–30 A 2
B100X — 100SNA Included 1 1//4 in.
BDL, BGL,
BJL
15–100 A
2, 3
JDL, JGL
150–225 A
2, 3
J225X [33][34] J225Y [33][34]
225SNA Included 2 1/2 in.
Enclosed Molded Case Switches
For information on enclosed molded case switches, see Supplemental Digest Section 3.
7
MINIATURE AND MOLDED CASE
CIRCUIT BREAKERS
[24] Enclosures are provided with the Handle Padlock Attachment (HPALM) for field installation to lock the circuit breaker in the “ON” or “OFF” positions.
[25] Use copper conductors only.
[26] Maximum short circuit and voltage is 30 kAIR at 480 Vac.
[27] LAL or LHL circuit breakers with an MB or MT suffix are not compatible with these enclosures: LA400DS, LA400AWK, and LA400LS.
[28] Enclosure cover has an integral padlock provision to provide a means to lock the circuit breaker in the “ON” or “OFF” position.
[29] Complete rating is NEMA 3, 3R, 4, 4X, 5, and 12.
[30] For NEMA 3R applications, remove drain screw from bottom endwall.
[31] NEMA 7 — Indoor Hazardous Locations — Division 1 and 2, Class I, Groups C and D; Class II, Groups E, F and G; Class III
[32] NEMA 9 — Indoor Hazardous Locations — Division 1 and 2, Class ii, Groups E, F and G; Class iii
[33] Short circuit current rating: 65 kAIR at 240 Vac, 25 kAIR at 480 Vac, and 18 kAIR at 600 Vac
[34] Not cULus listed due to wire bending space.
9/13/2019