Homeline Accessories
Homeline™ Miniature Circuit Breakers
Class 1170 / Refer to Catalog 1100CT0501
Homeline Circuit Breaker Wire Sizes
Table 1.48: Wire Sizes for Homeline Circuit Breakers
Breaker Type Ampere Rating
Wire Size (AWG/kcmil) [8]
Aluminum
Copper
HOM
1P
15–30 A 14–8 AWG
14–8 AWG or
(2) 14–10 AWG
40–50 A 8–2 AWG 8–2 AWG
HOM
2P
15–30 A 14–8 AWG
14–8 AWG or
(2) 14–10 AWG
35–70 A 8–2 AWG 8–2 AWG
 80–125 A 4–2/0 AWG 4–2/0 AWG
150–200 A 4 AWG–300 kcmil 4 AWG–300 kcmil
HOMT and Quad
15–30 A 14–8 AWG 14–8 AWG
Quad Only
40–50 A 6–12 AWG 6–14 AWG
HOM-GFI - 1P 15–20 A 14–10 AWG 14–10 AWG
HOM-GFI - 2P 15–50 A 12–4 AWG 14–6 AWG
Accessories for Homeline Circuit Breakers
Table 1.49: Accessories for Use with Homeline Circuit Breakers
Description
Cat. No.
Handle Attachments
Handle Tie: Converts any two adjacent 120/240 Vac single HOM circuit breakers to independent trip 2P
HOM1HT
Handle Tie: Converts any two adjacent 120/240 Vac
1P side-by-side HOMT circuit breakers to independent trip 2P
HOMTHT
Handle Clamp: Clamp for holding HOM 1P handle in the ON or OFF position
QO1LO
Handle Blocking Device: Attaches to standard HOM 2P circuit breakers for holding the handle in the OFF position
HOM2HBD
Handle Padlock Attachment: For padlocking 1P Standard HOM breakers in the ON or OFF position
HOM1PA
Handle Padlock Attachment: For
padlocking 2P Standard HOM circuit breakers in ON or OFF position
15–70 A HOM2PALA
80–125 A HOM2PAHA
150–200 A HOM2PAVHA
Handle Padlock Attachment: For padlocking 1P CAFI, DF, GFI, and EPD HOM breakers in ON or OFF position
HOMELEC1PA
Handle Padlock Attachment: For padlocking 2P CAFI, GFI, and EPD HOM breakers in ON or OFF position
HOMELEC2PALA
Handle Padlock Attachment: For padlocking center poles of Homeline Quad breakers in the OFF position
HOMQPA
Handle Padlock Attachment: For padlocking main circuit breakers in convertible load center in OFF position
50–125 A
QOM1PA [9]
100–225 A
QOM2PA [9]
Sub-Feed Lugs
125 A 2P plug-on—2 spaces required
HOML2125
225 A 2P plug-on—4 spaces required HOML2225 [10]
1
LOAD CENTERS
[8] 15–30 A circuit breakers are suitable for use with 60
o
C or 75
o
C conductors. 40–125 A circuit breakers are suitable for use with 75
o
C conductors.
[9] 50–125 A QOM1 frame size; 100–225 A QOM2 frame size.
[10] Requires four spaces (1 AWG–300 kcmil Al/Cu). Use only in panel rated 150 A or greater.