Technical Data Bulletin

1-24
© 2020 Schneider Electric
All Rights Reserved
12/02/2020
Homeline™ Load Centers
Homeline Load Centers, Indoor,
www.se.com/us
Class 1170 / Refer to Catalog 1100CT0501
1
LOAD CENTERS
1Ø, Field-Installed Mains Kits
QOL125 QOL225
Table 1.55: Field Installed Main Lug Kits Use with Convertible Main Load
Centers Only
Field-
Installed
Main Type
Frame Size
Main [17]
Ampere Rating
Use on Convertible
Load Center with
Mains Rating
Cat. No.
Lug Wire Size
[18]
AWG/kcmil
Main Lugs
[19]
125 A 100–125 A
QOL125
6–2/0 Al or Cu
125 A 100–125 A
QOL125VD
6–4/0 Al or Cu
225 A 150–225 A
QOL225
6–300 Al or Cu
Main Circuit
Breaker [20]
QOM1
 50 A 100–125 A
QOM50VH
12–2/0 Al or Cu
 60 A 100–125 A
QOM60VH
 70 A 100–125 A
QOM70VH
 80 A 100–125 A
QOM80VH
 90 A 100–125 A
QOM90VH
100 A 100–125 A
QOM100VH
110 A 125 A
QOM110VH
125 A 125 A
QOM125VH
QOM2 [21]
100 A 150–225 A
QOM2100VH
4–300 Al or Cu
125 A 150–225 A
QOM2125VH
150 A 150–225 A
QOM2150VH
175 A 200–225 A
QOM2175VH
200 A 200–225 A
QOM2200VH
225 A 225 A
QOM2225VH
HOM Plug-on Neutral Load Centers with Qwik-Grip
(1Ø3W—120/240 Vac Indoor—UL Listed)
HOM Plug-on Neutral
Load Center with Qwik-Grip
The Square D Homeline plug-on neutral load centers with Qwik-Grip simplify rough-in by
eliminating the need to remove knockouts, install wire connectors, and blindly pull wire
into the load center. A quick bend of the wire using the wire bend guide on the Qwik-Grip
insert and the wire slides into the slot. Once inserted, the Qwik-Grip shield snaps on to
keep the wire behind the router for a secure, code-compliant installation.
Table 1.56: Plug-on Neutral Load Centers with Qwik-Grip (Compatible with HOM Plug-on Circuit Breakers and HOM Plug-on Neutral
Circuit Breakers)
Main
Ratings
Spaces
Max. 1P
Circuits
Max. Tandem
Circuit
Breakers
Load Center
Box, Interior and Cover
Main Wire Size AWG/
kcmil
Equipment
Ground Bar Kit
Box
No.
Al Cu
I
N
D
O
O
R
125 A
24 48 24
HOM2448L125PQGC
6–2/0 6–1/0 PKGTALP2 Included
8Q
30 60 30
HOM3060L125PQGC
6–2/0 6–2/0 PKGTALP2 Included
10Q
Convertible Mains—Factory-Installed Main Lugs, 10 kA Short Circuit Current Rating— QOM2 Main Frame Size, Convertible to Main Circuit Breaker
225 A
30 60 30
HOM3060L225PQGC
4–250 PKGTALP2 Included
 10Q
40 80 40
HOM4080L225PQGC
4–250 PKGTALP3 Included
 12Q
42 84 42
HOM4284L225PQGC
4–250 PKGTALP3 Included
 12Q
Convertible Mains—Factory-Installed Main Circuit Breaker, 22 kA Short Circuit Current Rating— QOM2 Main Circuit Breaker Frame Size, Convertible to Main Lugs or Main Circuit Breaker
200 A
30 60 30
HOM3060M200PQC
4–250
PK23GTA (Order seperately)
10Q
40 80 40
HOM4080M200PQC
4–250
PK27GTA (Order seperately)
12Q
42 84 42
HOM4284M200PQC
4–250
PK27GTA (Order seperately)
12Q
Homeline Service Upgrade Load Centers
(1Ø3W—120/240 Vac Special Applications—UL Listed)
Table 1.57: Service Upgrade Load Centers with Removable End Walls
(Compatible with HOM Plug-on Circuit Breakers and HOM Plug-on Neutral Circuit Breakers)
Mains
Rating
Spaces
Max. 1P
Circuits [22]
Max.
Tandem
Circuit
Breakers
Load Center
Box and Interior
Extra Long Cover with Door
(Order Seperately)
Main Wire Size
AWG / Kcmil
Equipment
Ground Bar Kit
(Order
Separately)
Box No.
[23]
Flush Surface Al Cu
Convertible Mains—Factory-Installed Main Circuit Breaker—22KA
QOM2 Main Frame Size—Convertible to Main Lugs or Lower Amperage Main Circuit Breaker (See page 1-19)—Copper Bus [24]
INDOOR 200 A 30 60 30
HOM3060M200PCEP [25]
HOMC30UFL 4-250 PK23GTA 10
[17] Do not exceed the load center mains rating.
[18] Wire range listed for main device kits is the wire range of that device. To find out maximum wire size permitted in a particular load center per UL, see tables in page 1-9 and page 1-26 under
Main Wire Size.
[19] If main circuit breaker knockout has been removed from the load center’s trim, order appropriate filler plate from page 1-27.
[20] 22 k AIR main circuit breaker UL Listed for use ahead of HOM and HOMT 10 k AIR branch circuit breakers to permit their application on systems with up to 22 kA available fault current.
[21] Add suffix 1021 for 120, 208, 240 Vac shunt trip.
[22] Maximum single pole branch circuits utilizing QO and/or QOT circuit breakers.
[23] See page 1-31
[24] 22 k AIR main circuit breaker UL Listed for use ahead of QO, QOT and QO-PL 10 k AIR branch circuit breakers to permit their application on systems with up to 22 kA available fault current.
[25] Ships with standard length cover.