UL 60947-4-1 and UL 98 Disconnect
Switches
TeSys™ VLS Disconnect Switches
schneider-electric.us
Refer to Catalog 9400CT1601
8
OPERATING MECHANISMS AND
DISCONNECT SWITCHES
Product Overview
VLS3P016R1–
VLS3P063R1
Compact Size
The three-pole 16–63 A disconnect switches are made up of a single unit body, a mere
36 mm (1.4 in.) wide, while those rated 63–125 A are only 70 mm (2.8 in.) wide.
Accessory Flexibility
Mounting and removal of the fourth pole and add-on blocks are simple and quick
operations with no need for tools.
Certifications
All VLS disconnect switches are certified by cCSAus and are UL Listed for Canada and
USA:
16–63 A types: certified according to UL 60947-4-1 / CSA 22.2 60947-4-1-14
standards
63–125 A types: certified according to UL 98 / CSA 22.2 4 standards
Three-Pole Disconnect Switches
VLS3P063R2–
VLS3P125R2
VLS3P016D1–
VLS3P040D1
VLS3P063D2–
VLS3P125D2
Strokes of VLS switch poles
Travel 0 1 30° 60° 90°
60°
60°
55°
55°
Off On
VLS3P016R1–VLS3P063R1
VLS3P016D1–VLS3P040D1
VLS3P063R2–VLS3P125R2
VLS3P063D2–VLS3P125D2
Table 8.29: Certifications and Compliance (● = certification obtained)
Catalog number cULus per UL 60947-4-1 /
CSA C22.2 60947-4-1-14
UL Listed (File E487906)
cULus per UL 98 /
CSA C22.2 4
UL Listed (File E487907)
IEC/EN 60947-1,
IEC/EN 60947-3
VLS3P016R1–
VLS3P040R1
Compliant
VLS3P063R1
VLS3P016D1–
VLS3P040D1
VLS3P063R2–
VLS3P125R2
VLS3P063D2–
VLS3P125D2
Table 8.30: Selection—Three-Pole Disconnect Switches
Catalog
number
IEC conventional free air
thermal current (Ith), AC21A
(≤690 V)
(A)
IEC rated operational current (Ie)
AC22A (≤690 V), AC23A (≤415 V)
(A)
UL general use at
600 Vac
(A)
DIN rail mounting version, complete with black handle. For rear-mounting version, separately purchase the handle
and shaft extension. Refer to page 8-16 and page 8-18.
VLS3P016R1 16 16 16
VLS3P025R1 25 25 25
VLS3P032R1 32 32 32
VLS3P040R1 40 40 40
VLS3P063R1 63 45 60
VLS3P063R2 63 63 60
VLS3P080R2 80 80 100
VLS3P100R2 100 100 100
VLS3P125R2 125 125 100
Door-mounting version (no shaft required). Separately purchase the handle. Refer to page page 8-16.
VLS3P016D1 16 16 16
VLS3P025D1 25 25 25
VLS3P032D1 32 32 32
VLS3P040D1 40 40 40
VLS3P063D2 63 63 60
VLS3P080D2 80 80 100
VLS3P100D2 100 100 100
VLS3P125D2 125 125 100
Table 8.31: UL / CSA Ratings
Catalog number Horsepower General use
at 600 Vac
(A)
Short-circuit rating
at 600 Vac
(kA)
Max. fuse rating
at 600 V
(A)
1 phase 3 phase
120 V 240 V 200–208 V 240 V 480 V 600 V
UL 60947-4-1 and CSA 22.2 60947-4-1-14 [1]
VLS3P016•• 1 2 5 5 10 10 16 5
30 (Type RK5)
VLS3P025•• 1.5 3 7.5 7.5 15 20 25 5
30 (Type RK5)
VLS3P032•• 2 5 10 10 20 20 32 5
45 (Type RK5)
VLS3P040•• 2 5 10 15 20 25 40 5
45 (Type RK5)
VLS3P063R1 2 7.5 10 15 30 30 60 5
45 (Type RK5)
UL 98 and CSA C22.2 4 [2]
VLS3P063•• 3 7.5
20 [3]
20 40 40 60 50 60
VLS3P080•• 3 10
25 [3]
25 40 40 100 50 100
VLS3P100•• 5 10
30 [3]
30 50 50 100 50 100
VLS3P125•• 7.5 10
30 [3]
30 60 60 100 50 100
[1] Ratings are valid for VLS3P•••R• and VLS3P•••D• types, according to UL 60947-4-1 and CSA 22.2 60947-4-1-14. UL Listed for USA and Canada (cULus - File E487907) as Manual Motor
Controllers, while the UL designation is “General Purpose Switch. Interrupteur Usage General” and “Suitable As Motor Disconnect.”
[2] Ratings are valid for VLS3P•••R• and VLS3P•••D• types, according to UL 98 and CSA C22.2 4. UL Listed for USA and Canada (cULus - File E487907) as Open Type Switches Open
type unfused switch, while UL designation is “General Purpose Switch. Interrupteur Usage General.”
[3] Voltage value is not considered in UL98 / CSA 22.2 4 standards, and so is not indicated in the UL product marking.