Brochure

8-36
© 2019 Schneider Electric
All Rights Reserved
Flange Mounted and Cable Operated Accessories, Disconnect Switches
schneider-electric.us
Class 9422 / Refer to Catalog 9420CT9701
8
OPERATING MECHANISMS AND
DISCONNECT SWITCHES
Table 8.84: Dimensions 30, 60, and 100 A Class 9422 Disconnect Switches
Switch
Type
Maximum Voltage Fuse Type
Dimension A Dimension B
30 A
30 A, 250 V H, K, R
1.625
30 A, 600 V H, K, R
4.25
30 A, 600 V
J 1.625
60 A
60 A, 250 V H, K, R
2.25
60 A, 600 V H, K, R
4.75
60 A, 600 V
J 1.625
100 A
100 A, 250 V H, K, R
3.25
100 A, 600 V H, K, R
5.25
100 A, 600 V
J 3.25
D
Disconnect
Device
ON
OFF
0.38
10
0.38
10
F
C
A E
0.38
10
Fused
Non Fused
and Circuit
Breaker
Disconnect
Device
(2) 0.38
Dia. Mounting Holes
10
(For back panel support if necessary.)
Table 8.85: Dimensions
Type
A
in. (mm)
C
in. (mm)
D
in. (mm)
Min. Enclosure
Depth [19]
in. (mm)
E
in. (mm)
F
in. (mm)
Fusible
Device
BTCN, BTDN,
BTEN
6.56 (167) 8.00 (203)
BTCF, BTDF, BTEF
9.50 (241) 1.88 (48) 8.56 (217) 10.00 (254) 11.88 (302) 6.38 (162)
TFB1
11.50 (292) 3.88 (99) 9.50 (241) 12.00 (305)
13.19 (335)
NOTE: Back panel support is recommended for Types TFB1, 2, & 3. Other devices
may also require support if the flange is not sufficiently rigid.
[19] The minimum enclosure depth is greater than Dimension D since additional space is needed when mounting the mechanism.